State surveyors inspect nursing homes on an unannounced 9-to-15 month cycle. Each sheet covers one of the 5 tags most frequently cited nearby in Manitowoc (WI) so nursing, dietary, and maintenance leads can audit units, ask staff three hallway questions, and log fixes for monthly QAPI review.
| Sheet | Tag & Care Area | Nearby Activity | Hand Sheet To | Result |
|---|---|---|---|---|
| Page 2 | F0689 — Free of Accident Hazards, Supervision, and Assistance Devices | 5 local write-ups | DON / Unit Nurse | [ ] Pass [ ] Fix |
| Page 3 | K0712 — Quarterly Fire Drills Conducted Across All Three Shifts | 4 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 4 | K0321 — Hazardous Areas - Enclosure and Self-Closing Smoke Doors | 4 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 5 | F0609 — Timely Reporting of Alleged Abuse, Neglect, or Injury of Unknown Source | 4 local write-ups | DON / Unit Nurse | [ ] Pass [ ] Fix |
| Page 6 | K0918 — Electrical Systems - Essential Electric System Maintenance and Generator Testing | 3 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| 1. | Do transfer methods and mechanical lift sling sizes used by CNAs match the resident's active care plan and Kardex? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Were new fall-prevention interventions put in place immediately after the resident's most recent fall? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are call lights within reach, floor mats positioned as ordered, and bed heights set appropriately? | [ ] Pass [ ] Fix | Fix note: |
| 4. | Are smoking aprons, oxygen safety signs, and elopement wander-guards functioning and checked per shift? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Before transferring a resident with a mechanical lift, where do you check how many staff and which sling size are required? | [ ] Answered Clearly [ ] Coached |
| Q2. | When a resident has an unwitnessed fall, what immediate checks and care-plan updates happen before end of shift? | [ ] Answered Clearly [ ] Coached |
| Q3. | Before walking out of a high-fall-risk resident's room, what three bedside items do you verify? | [ ] Answered Clearly [ ] Coached |
| 1. | Were unannounced fire drills completed at varied times at least once per quarter on Day, Evening, and Night shifts? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Do fire drill critique logs record alarm activation time, door closure, staff attendance, and corrective coaching? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were silent night-shift drills between 9 PM and 6 AM followed by audible testing during daytime hours? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | What do the four letters in RACE stand for when responding to smoke or fire on your nursing unit? | [ ] Answered Clearly [ ] Coached |
| Q2. | During a fire alarm, which residents near the fire origin are moved first beyond the smoke-barrier doors? | [ ] Answered Clearly [ ] Coached |
| Q3. | Where are the last 12 quarterly shift fire drill logs filed when a Life Safety surveyor asks to see them? | [ ] Answered Clearly [ ] Coached |
| 1. | Do all soiled utility, laundry, storage (>50 sq ft), and mechanical room doors self-close and positive-latch completely? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are wooden wedges, kick-down stops, or propped linen hampers completely absent from fire and smoke doors? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are penetrations around pipes and data cables in smoke/fire walls sealed with listed firestop material? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Why can staff never use a wedge or linen cart to prop open a soiled utility or storage room door, even for two minutes? | [ ] Answered Clearly [ ] Coached |
| Q2. | If you notice a hallway or storage door failing to latch shut on its own, how do you submit an urgent maintenance work order? | [ ] Answered Clearly [ ] Coached |
| Q3. | When the fire alarm sounds, what should happen automatically to corridor smoke-barrier doors? | [ ] Answered Clearly [ ] Coached |
| 1. | Were resident allegations involving serious injury or suspected abuse reported to the Administrator immediately and within 2 hours? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Were all other reportable resident safety incidents submitted to the state agency within 24 hours per facility policy? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were involved staff removed from resident care immediately while nursing leadership completed safety checks? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | If staff witness or hear any allegation of rough resident care or unexplained bruising, who must be notified immediately? | [ ] Answered Clearly [ ] Coached |
| Q2. | Within how many hours must serious resident injury or suspected abuse be reported to the Administrator and state? | [ ] Answered Clearly [ ] Coached |
| Q3. | What immediate resident safety steps happen while nursing and the Administrator investigate an incident? | [ ] Answered Clearly [ ] Coached |
| 1. | Are weekly generator visual inspections (fuel, battery electrolyte/specific gravity, coolant, oil) logged every single week? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are monthly 30-minute dynamic load tests (>= 30% nameplate kW or exhaust temperature threshold) documented for all 12 months? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are transfer switch time-delay seconds (< 10 seconds to restore emergency power) recorded on every monthly test sheet? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Which color electrical outlets at the nurses' station and resident rooms stay powered by the emergency generator? | [ ] Answered Clearly [ ] Coached |
| Q2. | Where is the emergency generator inspection binder stored if a Life Safety surveyor asks to review the last 12 monthly load tests? | [ ] Answered Clearly [ ] Coached |
| Q3. | Within how many seconds must emergency generator power come on if utility power fails? | [ ] Answered Clearly [ ] Coached |