State surveyors inspect nursing homes on an unannounced 9-to-15 month cycle. Each sheet covers one of the 5 tags most frequently cited nearby in Chesterfield (VA) so nursing, dietary, and maintenance leads can audit units, ask staff three hallway questions, and log fixes for monthly QAPI review.
| Sheet | Tag & Care Area | Nearby Activity | Hand Sheet To | Result |
|---|---|---|---|---|
| Page 2 | F0842 — Complete and Accurate Resident Clinical Records | 2 local write-ups | DON / Unit Nurse | [ ] Pass [ ] Fix |
| Page 3 | K0918 — Electrical Systems - Essential Electric System Maintenance and Generator Testing | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 4 | K0712 — Quarterly Fire Drills Conducted Across All Three Shifts | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 5 | K0353 — Sprinkler System - Maintenance, Inspection, and 18-Inch Storage Clearance | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 6 | F0908 — Survey Compliance Standard (F0908) | 1 local write-ups | DON / Unit Nurse | [ ] Pass [ ] Fix |
| 1. | Do active resident care plans and physician orders match floor practice observed under F0842? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Can nursing and CNA staff demonstrate policy steps during shift rounds without missing items? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were recent audit discrepancies corrected on the spot and reported to monthly QAPI? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | What shift check do nursing staff complete to prevent citations under F-842? | [ ] Answered Clearly [ ] Coached |
| Q2. | Where on the resident care plan or MAR do you verify current orders before care? | [ ] Answered Clearly [ ] Coached |
| Q3. | Who do you notify right away if supplies, orders, or equipment are missing? | [ ] Answered Clearly [ ] Coached |
| 1. | Are weekly generator visual inspections (fuel, battery electrolyte/specific gravity, coolant, oil) logged every single week? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are monthly 30-minute dynamic load tests (>= 30% nameplate kW or exhaust temperature threshold) documented for all 12 months? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are transfer switch time-delay seconds (< 10 seconds to restore emergency power) recorded on every monthly test sheet? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Which color electrical outlets at the nurses' station and resident rooms stay powered by the emergency generator? | [ ] Answered Clearly [ ] Coached |
| Q2. | Where is the emergency generator inspection binder stored if a Life Safety surveyor asks to review the last 12 monthly load tests? | [ ] Answered Clearly [ ] Coached |
| Q3. | Within how many seconds must emergency generator power come on if utility power fails? | [ ] Answered Clearly [ ] Coached |
| 1. | Were unannounced fire drills completed at varied times at least once per quarter on Day, Evening, and Night shifts? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Do fire drill critique logs record alarm activation time, door closure, staff attendance, and corrective coaching? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were silent night-shift drills between 9 PM and 6 AM followed by audible testing during daytime hours? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | What do the four letters in RACE stand for when responding to smoke or fire on your nursing unit? | [ ] Answered Clearly [ ] Coached |
| Q2. | During a fire alarm, which residents near the fire origin are moved first beyond the smoke-barrier doors? | [ ] Answered Clearly [ ] Coached |
| Q3. | Where are the last 12 quarterly shift fire drill logs filed when a Life Safety surveyor asks to see them? | [ ] Answered Clearly [ ] Coached |
| 1. | Do staff maintain at least 18 inches of vertical safety clearance below sprinkler heads in dietary, linen, and supply closets? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are sprinkler heads in resident rooms and corridors clean and free of paint, lint, or hanging items during maintenance inspection? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are quarterly flow tests and annual sprinkler inspection logs current in the facility maintenance binder? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | How many inches of open safety space must staff keep below sprinkler heads on top shelves of storage closets? | [ ] Answered Clearly [ ] Coached |
| Q2. | Can staff ever hang privacy curtains, clothes, or wires from sprinkler piping in a resident room? | [ ] Answered Clearly [ ] Coached |
| Q3. | Where does the maintenance director keep quarterly and annual sprinkler inspection records? | [ ] Answered Clearly [ ] Coached |
| 1. | Do active resident care plans and physician orders match floor practice observed under F0908? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Can nursing and CNA staff demonstrate policy steps during shift rounds without missing items? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were recent audit discrepancies corrected on the spot and reported to monthly QAPI? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | What shift check do nursing staff complete to prevent citations under F-908? | [ ] Answered Clearly [ ] Coached |
| Q2. | Where on the resident care plan or MAR do you verify current orders before care? | [ ] Answered Clearly [ ] Coached |
| Q3. | Who do you notify right away if supplies, orders, or equipment are missing? | [ ] Answered Clearly [ ] Coached |