Facility: Hardin Home Location: Savannah, TN (Hardin County) Last Survey: 2025-06-10 (17 mos ago)
How to Use Hand 1 Sheet to Each Department Lead

State surveyors inspect nursing homes on an unannounced 9-to-15 month cycle. Each sheet covers one of the 5 tags most frequently cited nearby in Hardin (TN) so nursing, dietary, and maintenance leads can audit units, ask staff three hallway questions, and log fixes for monthly QAPI review.

Today's 5 Sheets Top Tags Cited Nearby
Sheet Tag & Care Area Nearby Activity Hand Sheet To Result
Page 2 K0345 — Fire Alarm System Testing, Inspection, and Out-of-Service Fire Watch 4 local write-ups Maintenance Lead [   ] Pass   [   ] Fix
Page 3 E0039 — Survey Compliance Standard (E0039) 4 local write-ups DON / Unit Nurse [   ] Pass   [   ] Fix
Page 4 K0918 — Electrical Systems - Essential Electric System Maintenance and Generator Testing 3 local write-ups Maintenance Lead [   ] Pass   [   ] Fix
Page 5 F0727 — Survey Compliance Standard (F0727) 3 local write-ups DON / Unit Nurse [   ] Pass   [   ] Fix
Page 6 K0781 — Survey Compliance Standard (K0781) 2 local write-ups Maintenance Lead [   ] Pass   [   ] Fix
Administrator Sign-Off: ___________________ DON Sign-Off: ___________________ Date: __________
Page 2 of 6 · Walk-Around Clipboard 1 of 5 8.5" × 11" US Letter · Assign to Maintenance Director

K0345 (K-345): Fire Alarm System Testing, Inspection, and Out-of-Service Fire Watch

Facility: Hardin Home Local Hotspot: #1 (4 nearby citations) Checklist: LSC-K0345
Step 1 Walk the Unit & Check These 3 Items (5 Minutes)
1. Are semi-annual smoke detector sensitivity checks and annual fire alarm vendor inspection reports complete in the binder? [   ] Pass   [   ] Fix Fix note:
2. Is the main fire alarm panel clear of unaddressed trouble signals during maintenance shift rounds? [   ] Pass   [   ] Fix Fix note:
3. Do staff know the written Fire Watch log procedure if the fire alarm system goes offline for more than 4 hours? [   ] Pass   [   ] Fix Fix note:
Step 2 Ask 2 Staff on Shift These Quick Questions (2 Minutes)
Q1. If you hear a yellow trouble beep on the main fire alarm panel at the nurses' station, who do you call right away? [   ] Answered Clearly   [   ] Coached
Q2. Where is our facility Fire Watch clipboard kept if the alarm system is temporarily offline for maintenance? [   ] Answered Clearly   [   ] Coached
Q3. Where does the maintenance director file quarterly and annual fire alarm testing certificates? [   ] Answered Clearly   [   ] Coached
Checked By: _______________________ Unit / Wing: _______________ Date: ___________
Privacy Rule: Never write resident names or room numbers on walk-around sheets.
Page 3 of 6 · Walk-Around Clipboard 2 of 5 8.5" × 11" US Letter · Assign to DON / Unit Nurse

E0039 (E-039): Survey Compliance Standard (E0039)

Facility: Hardin Home Local Hotspot: #2 (4 nearby citations) Checklist: CMS-LTCSP
Step 1 Walk the Unit & Check These 3 Items (5 Minutes)
1. Do active resident care plans and physician orders match floor practice observed under E0039? [   ] Pass   [   ] Fix Fix note:
2. Can nursing and CNA staff demonstrate policy steps during shift rounds without missing items? [   ] Pass   [   ] Fix Fix note:
3. Were recent audit discrepancies corrected on the spot and reported to monthly QAPI? [   ] Pass   [   ] Fix Fix note:
Step 2 Ask 2 Staff on Shift These Quick Questions (2 Minutes)
Q1. What shift check do nursing staff complete to prevent citations under E-039? [   ] Answered Clearly   [   ] Coached
Q2. Where on the resident care plan or MAR do you verify current orders before care? [   ] Answered Clearly   [   ] Coached
Q3. Who do you notify right away if supplies, orders, or equipment are missing? [   ] Answered Clearly   [   ] Coached
Checked By: _______________________ Unit / Wing: _______________ Date: ___________
Privacy Rule: Never write resident names or room numbers on walk-around sheets.
Page 4 of 6 · Walk-Around Clipboard 3 of 5 8.5" × 11" US Letter · Assign to Maintenance Director

K0918 (K-918): Electrical Systems - Essential Electric System Maintenance and Generator Testing

Facility: Hardin Home Local Hotspot: #3 (3 nearby citations) Checklist: LSC-K0918
Step 1 Walk the Unit & Check These 3 Items (5 Minutes)
1. Are weekly generator visual inspections (fuel, battery electrolyte/specific gravity, coolant, oil) logged every single week? [   ] Pass   [   ] Fix Fix note:
2. Are monthly 30-minute dynamic load tests (>= 30% nameplate kW or exhaust temperature threshold) documented for all 12 months? [   ] Pass   [   ] Fix Fix note:
3. Are transfer switch time-delay seconds (< 10 seconds to restore emergency power) recorded on every monthly test sheet? [   ] Pass   [   ] Fix Fix note:
Step 2 Ask 2 Staff on Shift These Quick Questions (2 Minutes)
Q1. Which color electrical outlets at the nurses' station and resident rooms stay powered by the emergency generator? [   ] Answered Clearly   [   ] Coached
Q2. Where is the emergency generator inspection binder stored if a Life Safety surveyor asks to review the last 12 monthly load tests? [   ] Answered Clearly   [   ] Coached
Q3. Within how many seconds must emergency generator power come on if utility power fails? [   ] Answered Clearly   [   ] Coached
Checked By: _______________________ Unit / Wing: _______________ Date: ___________
Privacy Rule: Never write resident names or room numbers on walk-around sheets.
Page 5 of 6 · Walk-Around Clipboard 4 of 5 8.5" × 11" US Letter · Assign to DON / Unit Nurse

F0727 (F-727): Survey Compliance Standard (F0727)

Facility: Hardin Home Local Hotspot: #4 (3 nearby citations) Checklist: CMS-LTCSP
Step 1 Walk the Unit & Check These 3 Items (5 Minutes)
1. Do active resident care plans and physician orders match floor practice observed under F0727? [   ] Pass   [   ] Fix Fix note:
2. Can nursing and CNA staff demonstrate policy steps during shift rounds without missing items? [   ] Pass   [   ] Fix Fix note:
3. Were recent audit discrepancies corrected on the spot and reported to monthly QAPI? [   ] Pass   [   ] Fix Fix note:
Step 2 Ask 2 Staff on Shift These Quick Questions (2 Minutes)
Q1. What shift check do nursing staff complete to prevent citations under F-727? [   ] Answered Clearly   [   ] Coached
Q2. Where on the resident care plan or MAR do you verify current orders before care? [   ] Answered Clearly   [   ] Coached
Q3. Who do you notify right away if supplies, orders, or equipment are missing? [   ] Answered Clearly   [   ] Coached
Checked By: _______________________ Unit / Wing: _______________ Date: ___________
Privacy Rule: Never write resident names or room numbers on walk-around sheets.
Page 6 of 6 · Walk-Around Clipboard 5 of 5 8.5" × 11" US Letter · Assign to Maintenance Director

K0781 (K-781): Survey Compliance Standard (K0781)

Facility: Hardin Home Local Hotspot: #5 (2 nearby citations) Checklist: LSC
Step 1 Walk the Unit & Check These 3 Items (5 Minutes)
1. Are physical building zones and equipment covered by K0781 inspected and current in the maintenance log? [   ] Pass   [   ] Fix Fix note:
2. Are corridor doors, storage clearances, and life-safety test sheets free of open discrepancies? [   ] Pass   [   ] Fix Fix note:
3. Were any open maintenance work orders resolved and dated by plant operations staff? [   ] Pass   [   ] Fix Fix note:
Step 2 Ask 2 Staff on Shift These Quick Questions (2 Minutes)
Q1. Where are weekly and monthly inspection records for K-781 stored? [   ] Answered Clearly   [   ] Coached
Q2. How do staff submit an urgent maintenance work order if equipment needs repair on shift? [   ] Answered Clearly   [   ] Coached
Q3. What safety step happens on your unit when the fire alarm activates? [   ] Answered Clearly   [   ] Coached
Checked By: _______________________ Unit / Wing: _______________ Date: ___________
Privacy Rule: Never write resident names or room numbers on walk-around sheets.