State surveyors inspect nursing homes on an unannounced 9-to-15 month cycle. Each sheet covers one of the 5 tags most frequently cited nearby in Geary (KS) so nursing, dietary, and maintenance leads can audit units, ask staff three hallway questions, and log fixes for monthly QAPI review.
| Sheet | Tag & Care Area | Nearby Activity | Hand Sheet To | Result |
|---|---|---|---|---|
| Page 2 | K0921 — Survey Compliance Standard (K0921) | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 3 | K0920 — Power Strips, Extension Cords, and Electrical Equipment Safety | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 4 | K0918 — Electrical Systems - Essential Electric System Maintenance and Generator Testing | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 5 | K0511 — Utilities, HVAC, and Medical Gas Equipment Compliance | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| Page 6 | K0374 — Survey Compliance Standard (K0374) | 1 local write-ups | Maintenance Lead | [ ] Pass [ ] Fix |
| 1. | Are physical building zones and equipment covered by K0921 inspected and current in the maintenance log? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are corridor doors, storage clearances, and life-safety test sheets free of open discrepancies? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were any open maintenance work orders resolved and dated by plant operations staff? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Where are weekly and monthly inspection records for K-921 stored? | [ ] Answered Clearly [ ] Coached |
| Q2. | How do staff submit an urgent maintenance work order if equipment needs repair on shift? | [ ] Answered Clearly [ ] Coached |
| Q3. | What safety step happens on your unit when the fire alarm activates? | [ ] Answered Clearly [ ] Coached |
| 1. | Are physical building zones and equipment covered by K0920 inspected and current in the maintenance log? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are corridor doors, storage clearances, and life-safety test sheets free of open discrepancies? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were any open maintenance work orders resolved and dated by plant operations staff? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Where are weekly and monthly inspection records for K-920 stored? | [ ] Answered Clearly [ ] Coached |
| Q2. | How do staff submit an urgent maintenance work order if equipment needs repair on shift? | [ ] Answered Clearly [ ] Coached |
| Q3. | What safety step happens on your unit when the fire alarm activates? | [ ] Answered Clearly [ ] Coached |
| 1. | Are weekly generator visual inspections (fuel, battery electrolyte/specific gravity, coolant, oil) logged every single week? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are monthly 30-minute dynamic load tests (>= 30% nameplate kW or exhaust temperature threshold) documented for all 12 months? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Are transfer switch time-delay seconds (< 10 seconds to restore emergency power) recorded on every monthly test sheet? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Which color electrical outlets at the nurses' station and resident rooms stay powered by the emergency generator? | [ ] Answered Clearly [ ] Coached |
| Q2. | Where is the emergency generator inspection binder stored if a Life Safety surveyor asks to review the last 12 monthly load tests? | [ ] Answered Clearly [ ] Coached |
| Q3. | Within how many seconds must emergency generator power come on if utility power fails? | [ ] Answered Clearly [ ] Coached |
| 1. | Are physical building zones and equipment covered by K0511 inspected and current in the maintenance log? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are corridor doors, storage clearances, and life-safety test sheets free of open discrepancies? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were any open maintenance work orders resolved and dated by plant operations staff? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Where are weekly and monthly inspection records for K-511 stored? | [ ] Answered Clearly [ ] Coached |
| Q2. | How do staff submit an urgent maintenance work order if equipment needs repair on shift? | [ ] Answered Clearly [ ] Coached |
| Q3. | What safety step happens on your unit when the fire alarm activates? | [ ] Answered Clearly [ ] Coached |
| 1. | Are physical building zones and equipment covered by K0374 inspected and current in the maintenance log? | [ ] Pass [ ] Fix | Fix note: |
| 2. | Are corridor doors, storage clearances, and life-safety test sheets free of open discrepancies? | [ ] Pass [ ] Fix | Fix note: |
| 3. | Were any open maintenance work orders resolved and dated by plant operations staff? | [ ] Pass [ ] Fix | Fix note: |
| Q1. | Where are weekly and monthly inspection records for K-374 stored? | [ ] Answered Clearly [ ] Coached |
| Q2. | How do staff submit an urgent maintenance work order if equipment needs repair on shift? | [ ] Answered Clearly [ ] Coached |
| Q3. | What safety step happens on your unit when the fire alarm activates? | [ ] Answered Clearly [ ] Coached |