K0363 · Concordia at Rp Home (PA)
Surveyed 08/17/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1) Corridor door to resident room latches and closes upon discovery (removed enhanced barrier precaution supplies) 2) Corridor door to 309 latches and closes upon discovery (removed enhanced…

View Full Plan Text
K0363 Correction Date: 10/01/2026 1) Corridor door to resident room latches and closes upon discovery (removed enhanced barrier precaution supplies) 2) Corridor door to 309 latches and closes upon discovery (removed enhanced barrier precaution supplies) 3) resident room door was repaired with working doorknob 8/17/26. Work order on file with NHA. 4) Monitor resident doors monthly to ensure they latch and secure and with working doorknobs. 5) Staff re-educated to not store enhanced barrier precaution supplies on resident hallway door and to report when door is not in working condition. Education on file with NHA. 6) QAPI committee provided monitor and tracking
K0363 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

0363: Corridor - Doors: The facility failed to maintain the positive latching of corridor doors, affecting two of seven smoke compartments within the component No residents were affected. All…

View Full Plan Text
K0363 Correction Date: 08/05/2026 0363: Corridor - Doors: The facility failed to maintain the positive latching of corridor doors, affecting two of seven smoke compartments within the component No residents were affected. All residents have the potential to be affected. The hardware was replaced to the door opening to the Employee lounge by the Director of Maintenance. A whole house audit was completed by the Director of Maintenance/designee on 17JUL2026 to ensure all door strike plates are free from obstruction and close without impairment. An audit of the facility's remaining resident corridor doors was completed on 17JUL2026 by the Director of Maintenance/designee to ensure that all doors meet the regulatory requirement for latching hardware. On 21JUL2026, NHA educated Director of Maintenance and maintenance staff on maintaining corridor doors to meet the requirement of smoke tight integrity and latch properly. The Maintenance Director/Designee will conduct monthly random audits of corridor doors to check function and integrity. NHA/Designee will audit quarterly Life Safety Binder with Maintenance Director to ensure compliance. Results will be submitted to the quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0363 · Sanatoga Center (PA)
Surveyed 07/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

The corridor doors identified during Life Safety code survey were immediately adjusted to ensure proper operation. The doors were tested to verify they close completely and latch to frame, and…

View Full Plan Text
K0363 Correction Date: 08/11/2026 The corridor doors identified during Life Safety code survey were immediately adjusted to ensure proper operation. The doors were tested to verify they close completely and latch to frame, and maintain the required resistance to processing smoke. The hardware identified for replacement is in the process of installation. The Maintenance Director/designee conducted a facility wide inspection of all corridor doors to verify they close properly, positively latch, and are free of excessive gaps or damage. Any additional deficiencies identified during inspection were corrected immediately. The Maintenance director/designee will include routine inspection of all corridor doors monthly. The maintenance director was educated on Life Safety Code requirements related to corridor doors, including positive latching, self closing function, and maintaining smoke-resistant construction. Any deficiencies identified during routine inspection will be corrected promptly and documented The Maintenance Director/designee will perform and document monthly audits of corridor door compliance x 3 months to verify continued compliance. Results will be reviewed during QAPI x 3 months
K0363 · Chapel Manor (PA)
Surveyed 06/30/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. Room C205 and basement kitchen doors have been repaired to ensure the door properly closes and latches. 2. NHA will educate the Maintenance department to ensure all corridor doors close and…

View Full Plan Text
K0363 Correction Date: 08/12/2026 1.Room C205 and basement kitchen doors have been repaired to ensure the door properly closes and latches. 2.NHA will educate the Maintenance department to ensure all corridor doors close and latch as designed. 3.NHA/designee will complete random weekly audits x 3 weeks and monthly x 1 month to ensure that all corridor doors close and latch as designed. 4.Maintenance Director will report audit findings to the QAPI Committee x 3 months for review.
K0363 · Phoebe Allentown Health Care Center (PA)
Surveyed 06/23/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

The distance between the basement-level Dietary doors was corrected on 07/02/2026 by using approved fire rated trim. Perform monthly rounds for a quarter to make sure we are compliant and…

View Full Plan Text
K0363 Correction Date: 08/03/2026 The distance between the basement-level Dietary doors was corrected on 07/02/2026 by using approved fire rated trim. Perform monthly rounds for a quarter to make sure we are compliant and report out on our findings in our monthly QAPI meeting.
K0363 · Caring Heart Rehabilitation and Nursing Center (PA)
Surveyed 06/03/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

The first-floor Break Room corridor door hardware was adjusted to ensure automatic closing and positive latching. - The Maintenance Director was re-educated on repairing door alignment and…

View Full Plan Text
K0363 Correction Date: 07/20/2026 - The first-floor Break Room corridor door hardware was adjusted to ensure automatic closing and positive latching. - The Maintenance Director was re-educated on repairing door alignment and hardware to maintain smoke resistance barriers. - The Director of Maintenance or designee will audit break room door latching weekly x 4. Monthly audits times 3 will continue with results reported to the QA Committee.
K0363 · Advanced Health Care of Hanover (PA)
Surveyed 05/29/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

What systematic changes will be put into place to ensure that the deficiency does not recur, and how the corrective action(s) will be monitored: resident room and 117 will be repaired. All…

View Full Plan Text
K0363 Correction Date: 07/28/2026 What systematic changes will be put into place to ensure that the deficiency does not recur, and how the corrective action(s) will be monitored: resident room and 117 will be repaired. All doors were reviewed for similar smoke containment failure and will be adjusted to meet requirement. This will be completed effective 7/28/2026. What quality assurance program will be put into place, and the dates when corrective action will be completed. Monthly during fire drill training all doors will be checked for smoke containment and this will be documented in the fire drill report. The corrective action will be completed by 7/28/2026.
K0363 · Arbor Grove Village (IN)
Surveyed 05/27/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; No residents were affected by this alleged deficient practice. Doors…

View Full Plan Text
K0363 Completion Date: 06/25/2026 1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; No residents were affected by this alleged deficient practice. Doors for RR#408 and RR# 206 were adjusted and device to hold doors open were removed. (See attachment J, K) 2. How other residents having Maintenance director in-serviced on 5/28/26 on corridor doors to have no impediments or obstructions preventing them from closure. Doors for RR#408 and RR # 206 were adjusted and device to hold doors open were removed(5/28/26). (See attachment) 3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or designee will use Life safety code/QAPI tool to audit door closures to ensure deficient practice does not recur. 4. How the corrective action will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into place. Maintenance Director or designee will complete ongoing monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The review. The results of these audits will be reviewed by the QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed.
K0363 · Northampton Post Acute (PA)
Surveyed 05/27/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. The PT Gym door was made to close when released from the magnetic hold-open device on May 27, 2026. 2. Maintenance Director/Designee will conduct weekly random audits for 4 weeks to ensure…

View Full Plan Text
K0363 Correction Date: 06/12/2026 1. The PT Gym door was made to close when released from the magnetic hold-open device on May 27, 2026. 2. Maintenance Director/Designee will conduct weekly random audits for 4 weeks to ensure that all doors close without drag. Findings of the audits will be reported to the Quality Assurance Performance Improvement (QAPI) Committee for further action planning if required.
K0363 · Embassy of Scranton (PA)
Surveyed 05/26/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

The third-floor med charting room door was adjusted and now fully latches. The unapproved means holding open the second and third floor medication rooms doors have been removed. The…

View Full Plan Text
K0363 Correction Date: 06/30/2026 The third-floor med charting room door was adjusted and now fully latches. The unapproved means holding open the second and third floor medication rooms doors have been removed. The Maintenance Director/designee will audit medication rooms and charting room doors weekly x 4, then monthly to ensure they are not being held open by unapproved means and fully latch. These audits will be brought to the monthly QAPI committee meeting for further review and recommendations.
K0363 · Laurel Lakes Rehabilitation and Wellness Center (PA)
Surveyed 05/06/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. The unprotected penetrations identified above the door hardware on the Zone 1 East Side "C" Wing Clean Linen Room door and the Zone 2 "F" Wing Clean Linen Room door were repaired using…

View Full Plan Text
K0363 Correction Date: 06/25/2026 1. The unprotected penetrations identified above the door hardware on the Zone 1 East Side "C" Wing Clean Linen Room door and the Zone 2 "F" Wing Clean Linen Room door were repaired using approved materials and methods to restore the smoke-resistant integrity of the corridor doors in accordance with NFPA 101 requirements. 2. The Director of Plant Operations, or designee, conducted a facility-wide inspection of corridor doors to identify any additional penetrations, hardware deficiencies, or conditions that could compromise smoke resistance. Any additional deficiencies identified during the inspection were corrected. 3. Maintenance staff were educated regarding NFPA 101 corridor door requirements and the importance of maintaining smoke-resistant assemblies. 4. The Director of Plant Operations, or designee, will: - Perform and document monthly inspections of corridor doors for three months, then quarterly thereafter. - Review inspection findings through the facility's Quality Assurance and Performance Improvement (QAPI) process. - Ensure any identified deficiencies are corrected promptly.
K0363 · Spring Creek Rehabilitation and Nursing Center (PA)
Surveyed 05/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

A. The 4th floor, door to the Nursery, across from Resident resident room will be adjusted to positively latch within the door frame. b. The 2nd floor, door to the Break Room, across from…

View Full Plan Text
K0363 Correction Date: 06/03/2026 a. The 4th floor, door to the Nursery, across from Resident resident room will be adjusted to positively latch within the door frame. b. The 2nd floor, door to the Break Room, across from Resident resident room will be adjusted to positively latch within the door frame. c. 2nd floor, door to the Social Services Room, across from Resident resident room will be adjusted to positively latch within the door frame. d. 1st floor, door to the Linen Room, across from Resident resident room will be positively latch within the door frame 2. The unprotected penetration of the door, to the 3rd floor Unit Manager's Office, above the door knob was removed. The Nursing Home Administrator will educate the Maintenance Director and Maintenance team to ensure all doors are positively latched with the frame. Random monthly audits will be done by the Maintenance Director/designee to ensure all compliance. Results of the audits will be reviewed/reported to the monthly QAPI committee to determine trends/compliance. QAPI committee will determine the need for continuance of audits.
K0363 · Cedarbrook Senior Care and Rehabilitation (PA)
Surveyed 04/29/2026 · Spot-checks: monthly for 3 months
✓ Passed Re-Inspection Use K0363 →

1. a) An astragal was installed at Resident resident room door to ensure smoke integrity. Facility staff will monitor the doors to ensure they maintain smoke integrity on a monthly basis for 3…

View Full Plan Text
K0363 Correction Date: 06/09/2026 1. a) An astragal was installed at Resident resident room door to ensure smoke integrity. Facility staff will monitor the doors to ensure they maintain smoke integrity on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee. b) Adjustments were made to Resident resident room door to ensure it fully closes and latches within its frame. Facility staff will monitor the doors to ensure they operate as designed to fully close and latch within its frame on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
K0363 · Riverstreet Manor (PA)
Surveyed 04/27/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

All corridor opening doors will be inspected for positive latching and to ensure gaps do not exceed one eighth inch. All future work orders and inspections will be monitored through TELS work…

View Full Plan Text
K0363 Correction Date: 06/26/2026 All corridor opening doors will be inspected for positive latching and to ensure gaps do not exceed one eighth inch. All future work orders and inspections will be monitored through TELS work order system and documentation will be filed in Life Safety Binder.
K0363 · Gino J. Merli Veterans Center (PA)
Surveyed 04/21/2026 · Spot-checks: weekly for 8 weeks
✓ Passed Re-Inspection Use K0363 →

Resident room door was immediately adjusted to insure proper closure. Resident room doors were inspected and adjusted. Random audits of resident room door closure will be conducted on 5 doors…

View Full Plan Text
K0363 Correction Date: 06/09/2026 resident room door was immediately adjusted to insure proper closure. Resident room doors were inspected and adjusted. Random audits of resident room door closure will be conducted on 5 doors on each nursing unit weekly for 8 weeks. Corridor doors will be inspected semi-annually for proper closure. Any doors found to be not closing properly are adjusted or replaced.
K0363 · Edenbrook North (PA)
Surveyed 04/15/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

Holes were patched in the affected doors. Maintenance director/designee will conduct an audit of facility doors to ensure no other doors are affected. Results of this audit will be reported to…

View Full Plan Text
K0363 Correction Date: 06/02/2026 Holes were patched in the affected doors. Maintenance director/designee will conduct an audit of facility doors to ensure no other doors are affected. Results of this audit will be reported to the QA steering committee, at which time the committee will determine the need for future audits.
K0363 · Holy Family Home (PA)
Surveyed 04/06/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. Approved latching hardware and self-closing devices were installed on both doors of Storage resident room. 2. A door inspection audit was conducted on all corridors area doors. 3. Results…

View Full Plan Text
K0363 Correction Date: 05/13/2026 1. Approved latching hardware and self-closing devices were installed on both doors of Storage resident room. 2. A door inspection audit was conducted on all corridors area doors. 3. Results will be documented and reviewed by the Safety Committee.
K0363 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

It is the practice of the facility to ensure smoke, Fire and corridor doors will operate as per design and all residents had the potential to be affected by this deficiency. 1. The doors in…

View Full Plan Text
K0363 Correction Date: 05/08/2026 It is the practice of the facility to ensure smoke, Fire and corridor doors will operate as per design and all residents had the potential to be affected by this deficiency. 1. The doors in resident room,435,314 have had the doors repaired and now they close, latch and are gap free as design. 2. Doors throughout the facility were checked to allow for closure, all residents are free from hazards and all systems are operating. 3. Education completed with Maintenance staff regarding monitoring doors and rating labels to ensure they close properly. 4. Every quarter for a year the Maintenance Director or designee will check random doors throughout the facility to ensure the doors are fully closed. This information will then be entered on a log and will be presented to the monthly QAPI meeting.
K0363 · Suburban Woods Health & Rehabilitation Center (PA)
Surveyed 03/25/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. Hardware was replaced, and door can now latch for basement corridor door. Tape from 2nd floor supply room was removed and can now be latched. Basement Housekeeping closet door scheduled to…

View Full Plan Text
K0363 Correction Date: 05/22/2026 1. Hardware was replaced, and door can now latch for basement corridor door. Tape from 2nd floor supply room was removed and can now be latched. Basement Housekeeping closet door scheduled to replaced 5/15/26. 2. Maintenance Director and Maintenance assistant were educated on the requirements of ensuring doors can latch. 3. NHA/designee will monitor that doors are able to latch. Results will be reviewed and revised as needed during monthly QAPI.
K0363 · Linwood Nursing and Rehabilitation Center (PA)
Surveyed 03/16/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

Resident resident room door latch was adjusted to ensure positive latching. No other doors were affected. The Director of Maintenance/designee will audit resident room door latch, smoke…

View Full Plan Text
K0363 Correction Date: 04/21/2026 Resident resident room door latch was adjusted to ensure positive latching. No other doors were affected. The Director of Maintenance/designee will audit resident room door latch, smoke barrier door right leaf latch (F-374) and 3 other random door latches (5 doors total) 1x/week for 4 weeks, then 1x/ month for 2 months to ensure the door latches are positively latching. The results of the audit will be presented to the QA committee for review and recommendations.
K0363 · Wesley Enhanced Living - Doylestown (PA)
Surveyed 03/16/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

Proper door hardware to be installed so that the door positively latches upon exit. Placed into TELS maintenance program for quarterly inspections. Also placed into semi-annual safety…

View Full Plan Text
K0363 Correction Date: 05/15/2026 Proper door hardware to be installed so that the door positively latches upon exit. Placed into TELS maintenance program for quarterly inspections. Also placed into semi-annual safety surveillance rounds and reported on during Wesley Enhanced Living's safety committee meetings. Also to be reported and reviewed during quarterly Quality Assurance committee that includes the Executive Director/Nursing Home Administrator, Director of Nursing, and Director of Facility Operations.
K0363 · Onyx Nursing & Rehabilitation (PA)
Surveyed 03/11/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

1. A) Small Conference room door latch was repaired and is fully functional. B) paper towels were removed from door strike at first floor clean linen room allowing door to positively latch. c)…

View Full Plan Text
K0363 Correction Date: 04/08/2026 Preparation and submission of this Plan of Correction does not constitute an admission or agreement with the facts alleged or conclusions stated in the Statement of Deficiencies. This Plan of Correction is submitted solely because it is required by Federal and State regulations. 1. A) Small Conference room door latch was repaired and is fully functional. B) paper towels were removed from door strike at first floor clean linen room allowing door to positively latch. c) staff bathroom door was repaired and latching hardware replaced allowing door to positively latch ensuring smoke resistance. d) Electrical room off activities lounge door hardware was installed and pad lock removed allowing door to positively latch and ensuring smoke resistance. 2. NHA / Designee conducted audits of facility doors to ensure all hardware is intact and doors can positively latch. Plan developed to address identified repairs based on priority. 3. NHA / Designee educated maintenance staff on requirements to ensure all doors positively latch and all hardware is intact. 4. NHA / Designee will audit facility doors weekly x4 then monthly x2 or until substantial compliance is obtained. To ensure all doors are intact and can latch, results will be brought to qapi for further evaluation and recommendation.
K0363 · Carnegie Park Post Acute (PA)
Surveyed 03/10/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

On March 13, 2026, the door to Resident resident room was repaired and adjusted to ensure it properly latches when tested. A facility-wide inspection of corridor doors was conducted to ensure…

View Full Plan Text
K0363 Correction Date: 04/27/2026 On March 13, 2026, the door to Resident resident room was repaired and adjusted to ensure it properly latches when tested. A facility-wide inspection of corridor doors was conducted to ensure compliance. The Maintenance Director or designee will monitor compliance during routine environmental rounds to ensure all corridor doors remain in proper working order. Completion date: March 13, 2026.
K0363 · Hempfield Manor (PA)
Surveyed 03/10/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

On 3/10/26, the resident resident room door was repaired and tested for latching to ensure proper working order. Maintenance Director educated on facility door checks and proper latching by…

View Full Plan Text
K0363 Correction Date: 04/14/2026 On 3/10/26, the resident resident room door was repaired and tested for latching to ensure proper working order. Maintenance Director educated on facility door checks and proper latching by Nursing Home administrator. The Maintenance Director or Designee will audit via facility walkthroughs to ensure doors are operating properly. These audits will be completed weekly for four weeks, then monthly for three months, then quarterly. Results of Audits will be reviewed at quarterly QAPI meetings.
K0363 · Marywood Heights (PA)
Surveyed 03/10/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0363 →

Resident room not smoke tight Door seal was ordered and was installed. - 216 not smoke tight Door seal to 216 was installed to ensure smoke tight. - Conference room doors exceeded 1/8 inch…

View Full Plan Text
K0363 Correction Date: 03/31/2026 - resident room not smoke tight Door seal was ordered and was installed. - 216 not smoke tight Door seal to 216 was installed to ensure smoke tight. - Conference room doors exceeded 1/8 inch astragal was purchased and installed. - Social services door not smoke tight Door seal was installed to ensure smoke tight. - Therapy room doors lacked positive latching capabilities Doors have been replaced to ensure positive latching capabilities. Astragal was purchased and installed. Maintenance Director or designee will conduct quarterly audits and submit to QAPI committee to ensure doors are smoke tight, do not exceed 1/8 inch gap, and have a positive latch.