K0355 · Fairlane Gardens Nursing and Rehab at Reading (PA)
Surveyed 07/29/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random…

View Full Plan Text
K0355 Correction Date: 09/15/2026 1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random audits weekly x 4 weeks then monthly to ensure fire extinguishers are not blocked. 4) A summary of the audit's findings will be submitted to the QAPI committee for recommendations
K0355 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No…

View Full Plan Text
K0355 Correction Date: 08/05/2026 0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No residents were affected. All residents have the potential to be affected. Signage to be installed by the Maintenance Director/designee near the Laundry Chemical Room to identify the portable fire extinguisher by 05AUG2026. Maintenance Director/Designee completed an audit of all portable fire extinguishers in the facility on 09JUL2026 to ensure proper identifying signage. On 21JUL2026, NHA educated the Maintenance Director and maintenance department on the importance of maintaining proper identifying signage for portable fire extinguishers per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits weekly x4 weeks then monthly x 2 months to ensure fire extinguisher signage meets the regulatory requirement. Results will be submitted to the quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0355 · Sanatoga Center (PA)
Surveyed 07/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide…

View Full Plan Text
K0355 Correction Date: 08/11/2026 The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide audit of all fire extinguishers to verify they are properly installed, accessible, fully charged, inspected, and hung accordingly. The Maintenance Director/designee was educated on placement of portable fire extinguishers The Maintenance Director/designee will conduct monthly audits of all portable fire extinguishers x 3 months to verify continued compliance. Audit results will be reviewed through QAPI x 3 months
K0355 · Arbor Grove Village (IN)
Surveyed 05/27/2026 · Spot-checks: daily for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. What corrective action will this alleged deficient practice. Sign was placed on activity room door on 5/28/26 identifying fire extinguisher location in activity room. (See attachment I) 2.…

View Full Plan Text
K0355 Completion Date: 06/25/2026 1. What corrective action will this alleged deficient practice. Sign was placed on activity room door on 5/28/26 identifying fire extinguisher location in activity room. (See attachment I) 2. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action will be taken; All residents could potentially be affected by this alleged deficient practice. Maintenance director in-serviced on 5/28/26 on sign placement on all room doors identifying fire extinguisher location. 3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or designee will use Life safety code/QAPI tool to audit sign placement on all doors identifying fire extinguisher location where applicable. 4. How the corrective action will be monitored to ensure the deficient practice will not monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The Maintenance Director will audit daily (5x week) for 4 weeks, monthly x 6 months, using Life Safety/QAPI Audit tool and thereafter QAPI committee will determine need for further review. The results of these audits will be reviewed by the QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed.
K0355 · Northampton Post Acute (PA)
Surveyed 05/27/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1,…

View Full Plan Text
K0355 Correction Date: 06/12/2026 1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1, 2026. 2. Maintenance Director/Designee will conduct weekly random audits for 4 weeks to ensure that signage stating staff are to employ the ansul system before using the fire extinguishing device is present by the K-Type portable fire extinguisher located in the dietary department. Findings of the audits will be reported to the Quality Assurance Performance Improvement (QAPI) Committee for further action planning if required.
K0355 · Chambersburg Skilled Nursing and Rehabilitation Center (PA)
Surveyed 05/18/2026 · Spot-checks: weekly for 2 months
✓ Passed Re-Inspection Use K0355 →

1. and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current. 3. Maintenance department will be educated on the standards of…

View Full Plan Text
K0355 Correction Date: 06/19/2026 1.and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current. 3. Maintenance department will be educated on the standards of ensuring the facility has completed the monthly inspection of portable fire extinguishers. 4. Maintenance or facility designee will audit the facilities monthly inspection of portable fire extinguishers weekly for 2 months, then every 60 days throughout the year and results of the audit will be reported to the QAPI committee.
K0355 · Cedarbrook Senior Care and Rehabilitation (PA)
Surveyed 04/29/2026 · Spot-checks: monthly for 3 months
✓ Passed Re-Inspection Use K0355 →

1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for…

View Full Plan Text
K0355 Correction Date: 06/09/2026 1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee. b) D7 portable fire extinguisher indicator light near Dining Room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee. 2. The facility's vendor will ensure all portable fire extinguisher will be inspected on a monthly basis. Facility staff will monitor all portable fire extinguishers on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
K0355 · Twinbrook Healthcare and Rehabilitation Center (PA)
Surveyed 04/22/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10,…

View Full Plan Text
K0355 Correction Date: 05/08/2026 1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10, Standard for Portable Fire Extinguishers by May 1,2026. 2. The Maintenance Director or Designee will ensure that all portable fire extinguishers will audit monthly for three months. The Maintenance Director will add the inspection of all portable fire extinguishers to the monthly Preventative Maintenance schedule beginning May 2026. 3. The results of the audits will be reported to the Quality Assurance and Performance Improvement Committee for review at the next monthly meeting.
K0355 · Edenbrook North (PA)
Surveyed 04/15/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no…

View Full Plan Text
K0355 Correction Date: 06/02/2026 The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no other fire extinguishes are hung in excess of 60 inches from the floor to the top of the handle. Results of this audit will be reported to the QA steering committee, at which time the committee will determine the need for future audits.
K0355 · Pocopson Home (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to…

View Full Plan Text
K0355 Correction Date: 04/02/2026 1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to handle. b. The portable fire extinguisher, located within the penthouse level Elevator Machine Room, has been checked. Maintenance will maintain fire extinguisher inspections on a monthly basis. Audit results will be reported to the Quality Improvement/Infection Control Committee. Preparation and submission of this Plan of Correction is required by State and Federal law. This Plan of Correction does not constitute an admission for purposes of general liability, professional malpractice or any other court proceeding
K0355 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency. 1. The Fire Extinguisher in…

View Full Plan Text
K0355 Correction Date: 05/08/2026 It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency. 1. The Fire Extinguisher in basement hallway has had the obstruction removed to remain accessible for use. 2. All Fire Extinguishers in the facility have been reinspected and are ready for use and the staff inspect the extinguisher areas to prevent this from happening in the future. 3. The Director of Maintenance has completed education with Maintenance staff regarding monitoring Fire Extinguishers by Maintenance Staff. 4. Every quarter for a year the Maintenance Director or designee will check Fire Extinguishers throughout the facility to ensure they are ready for use. This information will then be entered on a log and will be presented by the director to the monthly QAPI meeting for one year.
K0355 · Marywood Heights (PA)
Surveyed 03/10/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to…

View Full Plan Text
K0355 Correction Date: 03/31/2026 Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to QAPI committee to ensure portable fire extinguishers are inspected.
K0355 · Embassy of Hearthside (PA)
Surveyed 02/09/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS.…

View Full Plan Text
K0355 Correction Date: 03/30/2026 Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS. Maintenance will continue to monitor and report findings to monthly QAPI meetings.
K0355 · Liberty Pointe Rehabilitation and Healthcare Center (PA)
Surveyed 01/20/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to…

View Full Plan Text
K0355 Correction Date: 02/23/2026 Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to the QAPI committee.
K0355 · Hickory Creek at Peru (IN)
Surveyed 01/15/2026 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

It is the intent of this facility to be accomplished for those residents found to have been affected by the alleged deficient practice. All residents have the potential to be affected, The…

View Full Plan Text
K0355 Completion Date: 01/30/2026 It is the intent of this facility to be accomplished for those residents found to have been affected by the alleged deficient practice. All residents have the potential to be affected, The fire extinguisher map on our facility floor plan has been updated to reflect all fire extinguishers available for facility. The fire extinguisher outside the kitchen door way has been inspected and labeled appropriately. How will you identify other residents having the potential to be affected by the same alleged deficient practice and what corrective action will be taken. All residents have the potential to be affected, The fire extinguisher map on our facility floor plan has been updated to reflect all fire extinguishers available for facility. Facility confirmed location of all fire extinguishers. All fire extinguishers were checked by the Maintenance Director to ensure they were inspected and properly labeled. What measures will be put into place or what systemic changes you will make to facility floor plan. Our fire extinguisher locations have been added to our Preventative Maintenance Program. Maintenance Director will round each month to ensure fire extinguishers were inspected and properly labeled. How the corrective action(s) will be monitored to ensure the alleged deficient practice will not recur, i.e., what quality assurance program will be put into place. All facility fire extinguishers will be inspected and documented monthly in our Preventative Maintenance Program, which will be conducted by our Maintenance Director. These inspections will be documented and reviewed for compliance during our monthly Safety Committee Meeting and our Quality Assurance Committee Meeting. If any fire extinguisher inspections are missing, the Safety Committee and Quality Assurance Committee will submit action plans for compliance.
K0355 · Fairview Rehab and Care Center (PA)
Surveyed 01/13/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Missing fire extinguisher Annual inspection to be completed and certificate for the inspection to be obtained. Maintenance team educated on timeliness of inspections each month and getting…

View Full Plan Text
K0355 Correction Date: 03/03/2026 K0355 Missing fire extinguisher Annual inspection to be completed and certificate for the inspection to be obtained. Maintenance team educated on timeliness of inspections each month and getting yearly certificate by Regional Maintenance Director. Maintenance team to audit all tickets are updated on all extinguishers Maintenance director to present update at qapi.
K0355 · Cedar Haven Healthcare Center (PA)
Surveyed 12/16/2025 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Med Cart was immediately removed from blocking the fire extinguisher Nursing staff will be rein-serviced about blocking fire extinguishers in hallways. Maintenance will do random weekly audits…

View Full Plan Text
K0355 Correction Date: 01/21/2026 Med Cart was immediately removed from blocking the fire extinguisher Nursing staff will be rein-serviced about blocking fire extinguishers in hallways. Maintenance will do random weekly audits x4 then monthly audits x2 to ensure fire extinguishers are not being blocked. Results of audits will be reviewed with the QAPI committee.
K0355 · Care Pavilion Nursing and Rehabilitation Center (PA)
Surveyed 12/15/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

Correction: Effected fire extinguishers was properly mounted. Systemic Changes: Monthly fire extinguisher inspections were added immediately. Monitoring: Inspection logs will be reviewed…

View Full Plan Text
K0355 Correction Date: 01/30/2026 Correction: Effected fire extinguishers was properly mounted. Systemic Changes: Monthly fire extinguisher inspections were added immediately. Monitoring: Inspection logs will be reviewed monthly. Completion Date: 1/30/26.
K0355 · Lecom at Village Square, LLC (PA)
Surveyed 12/11/2025 · Spot-checks: monthly for 6 months
✓ Passed Re-Inspection Use K0355 →

Maintenance Director to complete whole house audit for all portable fire extinguishers in the facility to ensure proper inspection and function by 01/02/2026. Education will be provided to the…

View Full Plan Text
K0355 Correction Date: 01/16/2026 Maintenance Director to complete whole house audit for all portable fire extinguishers in the facility to ensure proper inspection and function by 01/02/2026. Education will be provided to the Maintenance Director and department by the Nursing Home Administrator regarding proper and timely inspections of the portable fire extinguishers by 01/09/2026. Maintenance Director or designee to monitor compliance monthly, as required. The monthly preventative maintenance schedule will be updated to include a mandatory, verifiable and dated monthly documentation step for fire extinguisher inspections. Nursing Home Administrator will complete monthly audits of these inspections monthly for 6 months. Results of these audits will be reviewed at the quarterly QAA meetings. Nursing Home Administrator will review the Life Safety checklist during the quarterly QAPI meeting.
K0355 · Brickyard Healthcare - Twelfth Street Care Center (IN)
Surveyed 12/09/2025 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

The obstruction was removed from in front of the portable fire extinguisher in the activity area. All residents in the vicinity have potential to be affected by this alleged deficient…

View Full Plan Text
K0355 Completion Date: 02/03/2026 The obstruction was removed from in front of the portable fire extinguisher in the activity area. All residents in the vicinity have potential to be affected by this alleged deficient practice. A weekly task was added to TELS to Check hallway egress and exit assemblies to ensure no carts or objects without wheels are present. Remove immediately if found. morning meeting. Furniture of any kind should not be unsecured in hallway and should never obstruct the width of the hallway to less than 6 feet even if secured to the wall or the floor. Ensure no fire door assemblies, extinguishers, electrical panels or fire pull stations are blocked by any object or cart. Any of these items found need to be removed immediately. If it is recurring report to administration. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues. A door obstruction task was added to TELS that states: No door attached to the corridor or egress assembly can be blocked with any object. The only allowable door holding devices must be automatically released by the fire alarm system when activated. Check all egress assembly doors to include offices, closets, storage areas, hazardous areas, utility areas, dining areas, resident room doors, fire doors, smoke doors, again ALL doors in the hallway, egress, or exit assembly to ensure they are free from obstructions, wedges, or devices that would hold the door open in any way and remove immediately. All staff was trained to keep all doors unobstructed in the exit corridors and assemblies. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues.
K0355 · Trillium Place (PA)
Surveyed 12/08/2025 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

The portable fire extinguisher located in the Susquehanna Elevator Machine Room has been removed from the floor and secured on the wall with the appropriate mounting hardware. -The plan of…

View Full Plan Text
K0355 Correction Date: 12/15/2025 The portable fire extinguisher located in the Susquehanna Elevator Machine Room has been removed from the floor and secured on the wall with the appropriate mounting hardware. -The plan of correction has been completed on 12/15/25. -Education has been provided to the maintenance team on 12/15/2025. -Audits will be conducted by the Assistant Director of Facilities or designee quarterly. -Audit reports will be reported to the Quality Assurance committee for review and further recommendations.
K0355 · Independence Rehab and Nursing (PA)
Surveyed 11/24/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. On 9/22/2025 the Maintenance assistant inspected the fire extinguishers in the elevator room and in the kitchen. 2. On 9/22/2025 the maintenance team conducted an audit of all fire…

View Full Plan Text
K0355 Correction Date: 12/29/2025 1. On 9/22/2025 the Maintenance assistant inspected the fire extinguishers in the elevator room and in the kitchen. 2. On 9/22/2025 the maintenance team conducted an audit of all fire extinguishers to verify that monthly inspection documentation was present. 3. On 10/2/2025 The NHA educated the Maintenance Director on fire extinguishers being properly installed, maintained, and inspected per code. 4. The Maintenance Director will conduct monthly inspections on fire extinguishers. Results of the inspections will be reviewed at the monthly QAPI meeting.
K0355 · Harborview Rehabilitation and Care Center at Doylestown (PA)
Surveyed 10/20/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. Maintenance staff replaced the light indicator for the fire extinguisher cabinet near resident room and verified all extinguishers are functional and properly identified. 2. Maintenance…

View Full Plan Text
K0355 Correction Date: 11/26/2025 1. Maintenance staff replaced the light indicator for the fire extinguisher cabinet near resident room and verified all extinguishers are functional and properly identified. 2. Maintenance staff were re-educated on monthly extinguisher inspections and documenting findings. 3. Maintenance Director/designee will conduct audits of extinguisher documentation monthly x 3. 4. All results will be reported to the QAPI Committee.
K0355 · Normandie Ridge (PA)
Surveyed 09/11/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1. The unsecured fire extinguisher was removed off the floor from the nurse's station. The fire extinguisher was taken out of service. 2. Staff will be educated on the proper placement of fire…

View Full Plan Text
K0355 Correction Date: 09/22/2025 1. The unsecured fire extinguisher was removed off the floor from the nurse's station. The fire extinguisher was taken out of service. 2. Staff will be educated on the proper placement of fire extinguishers into hangers or notification to maintenance if unable to hang appropriately. The Facilities Director/designee will audit one time per week for three months to ensure all fire extinguishers are secured appropriately within the building. Audits will continue monthly as part of monthly fire extinguisher checks. 3. Audits will be reported at the QAPI meeting monthly for further follow up and review.
K0355 · Bethlehem South Skilled Nursing and Rehabilitation Center (PA)
Surveyed 09/08/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection Use K0355 →

1) Immediate Corrective Action: a. Maintenance staff were re-educated on extinguisher locations. b. A facility-wide check confirmed all extinguishers were present and accessible.M…

View Full Plan Text
K0355 Correction Date: 09/21/2025 1) Immediate Corrective Action: a. Maintenance staff were re-educated on extinguisher locations. b. A facility-wide check confirmed all extinguishers were present and accessible.M 2)Identification of Other Residents and Corrective Action: a. All residents could be impacted if extinguishers are not inspected properly. b. The facility conducted a complete audit to confirm compliance with monthly checks. 3)Systemic Changes/Implemented Measures to Prevent Reoccurrence: a. All maintenance staff were retrained on extinguisher locations and monthly inspection requirements. b. Cross-checks after departmental inspections were implemented to verify proper documentation. c. Quality assurance rounds now include verification that extinguishers are receiving monthly inspections. 4)Monitoring Corrective Measures & Quality Assurance: a. The maintenance supervisor will complete monthly audits of extinguisher inspections. b. Results will be reported to QAPI for oversight and corrective action if needed.