K0932 · Premier Washington Rehabilitation and Nursing Center (PA)
Surveyed 04/27/2026 · Spot-checks: monthly for 3 months
✓ Passed Re-Inspection
Use K0932 →
1. On April 28, 2026, the required warning signage indicating the room was equipped with an FM-200 extinguishing system was installed at the entrance to the affected room. The Director of…
View Full Plan Text
K0932 Correction Date: 06/08/2026
1. On April 28, 2026, the required warning signage indicating the room was equipped with an FM-200 extinguishing system was installed at the entrance to the affected room. The Director of Maintenance verified the signage was properly posted and visible in accordance with applicable Life Safety Code and NFPA requirements.
2. On April 28, 2026, the Director of Maintenance conducted a facility-wide inspection of all rooms containing clean agent fire suppression systems, including FM-200 systems, to verify required warning signage was present. Any additional deficient areas identified during the inspection were corrected immediately.
3. Maintenance staff were re-educated regarding NFPA requirements for identification and warning signage associated with clean agent extinguishing systems.
4. The Director of Maintenance or designee will conduct monthly inspections for 3 months of all extinguishing system rooms to verify required signage remains in place and legible. Inspection findings will be documented and reviewed during the facility's (QAPI) meetings.