Past Winning Plans
Real state-approved Plans of Correction and their spot-check schedules.
Federal CMS Precedents Shown for Virginia: CMS SOM § 7304 Plan-of-Correction rules apply nationwide. Below are verified Passed-Revisit examples you can adapt for Virginia, or view local county stats in
Virginia State Guides →
K0325 · Arbor Grove Village (IN)
Surveyed 05/27/2026 · Spot-checks: daily for 4 weeks
1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; No residents were affected by this alleged deficient practice. Alcohol…
View Full Plan Text
K0325
Completion Date: 06/25/2026
1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; No residents were affected by this alleged deficient practice. Alcohol based hand rub dispenser was immediately relocated to an area not above an ignition source. (See attachment F, G)
2. How other residents having the potential to be affected by to be affected by this alleged deficient practice. Maintenance director in-serviced on 5/28/26 on proper location of all Alcohol based hand rub dispensers to ensure deficient practice does not recur.
3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or designee will use Life safety code/QAPI tool to audit Alcohol based hand rub dispensers and confirm proper location to ensure deficient practice does not recur.
4. How the corrective action will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into place. Maintenance Director or designee will complete ongoing monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The Maintenance Director will audit daily (5x week) for 4 weeks, QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed. residents found to have been affected by the deficient practice; No residents were affected by this alleged deficient practice. Hole around the sprinkler head in the employee breakroom was repaired on 5/28/26, ensuring no area for smoke to escape. Regular inspection schedule of all sprinklers will be conducted for need for repairs. (See attachment H)
2. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action will be taken; All residents have the potential to be affected by this alleged deficient practice. Maintenance director was in-serviced on 5/28/26 on maintaining proper covering of the annular space around a sprinkler.
3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or not recur.
4. How the corrective action will be monitored to ensure the deficient practice will not recur, i.e., what quality assurance program will be put into place. Maintenance Director or designee will complete ongoing monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The Maintenance Director will audit daily (5x week) for 4 weeks, monthly x 6 months, using Life Safety/QAPI Audit tool and thereafter QAPI committee will determine need for further review. The results of these audits will be reviewed by the QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed.
K0325 · The Village at Penn State (PA)
Surveyed 05/19/2026 · Spot-checks: weekly for 4 weeks
1. Alcohol based hand rub (ABHR) sanitizer dispensers in resident rooms will be relocated away from electrical sources. 2. Maintenance staff will check all ABHR dispensers in the facility to…
View Full Plan Text
K0325 Correction Date: 06/30/2026
1. Alcohol based hand rub (ABHR) sanitizer dispensers in resident rooms will be relocated away from electrical sources.
2. Maintenance staff will check all ABHR dispensers in the facility to ensure the location is away from electric source.
3. Date of compliance June 30, 2026
K0325 · Chambersburg Skilled Nursing and Rehabilitation Center (PA)
Surveyed 05/18/2026 · Spot-checks: weekly for 2 months
1. and2. Maintenance Director has removed both alcohol-based hand rub dispensers located between room B8 and B10, and room D8. Maintenance Director completed facility wide audit on location of…
View Full Plan Text
K0325 Correction Date: 06/19/2026
1.and2. Maintenance Director has removed both alcohol-based hand rub dispensers located between room B8 and B10, and room D8. Maintenance Director completed facility wide audit on location of alcohol-based hand rub dispensers.
3. Maintenance department will be educated on the standards of ensuring the facility does not hang alcohol-based hand rub dispensers above an ignition source.
4. Maintenance or facility designee will audit the facilities location of hand-based hand rub dispensers to ensure they are not located above an ignition source weekly for 2 months, then every 60 days throughout the year and results of the audit will be reported to the QAPI committee.
K0325 · Lecom at Village Square, LLC (PA)
Surveyed 12/11/2025 · Spot-checks: monthly for 3 months
Maintenance Director immediately removed and relocated the alcohol-based hand rub dispenser to an appropriate wall placement not above an electrical outlet upon discovery on 12/11/2025.…
View Full Plan Text
K0325 Correction Date: 01/16/2026
Maintenance Director immediately removed and relocated the alcohol-based hand rub dispenser to an appropriate wall placement not above an electrical outlet upon discovery on 12/11/2025. Maintenance Director or designee to audit all wall-mounted alcohol-based hand rub dispensers in the facility to ensure compliance with outline safety standards including proximity to electrical outlets. This initial audit will be completed by 01/02/2026. This will be added to the Life Safety checklist. Nursing Home Administrator will review the Life Safety checklist during the quarterly QAPI meeting. Nursing Home Administrator or designee will complete audits monthly for 3 months to ensure compliance. Results of these audits will be reviewed at monthly QAA meeting.
K0325 · Fairlane Gardens Nursing and Rehab at Reading (PA)
Surveyed 08/26/2025 · Spot-checks: weekly for 4 weeks
1. The alcohol-based hand rub dispenser was moved from over the light switch in the Conference Room. 2. Maintenance Director was educated on proper installation requirements of the…
View Full Plan Text
K0325 Correction Date: 10/01/2025
1. The alcohol-based hand rub dispenser was moved from over the light switch in the Conference Room.
2. Maintenance Director was educated on proper installation requirements of the alcohol-based hand rub dispensers.
3. Whole house audit completed to ensure the alcohol-based hand rub dispensers were mounted correctly. Quarterly rounds to ensure alcohol-based hand rub dispensers are mounted correctly.
4. A summary of the audit findings will be submitted to the QA Committee for recommendations. Quarterly round documentation will be recorded in TELS.
K0325 · Avalon Care Center (PA)
Surveyed 06/18/2025 · Spot-checks: weekly for 4 weeks
Facility has removed the (ABHR) dispenser from the area identified on the survey that was conducted June 18,2025. Maintenance Department will perform a full house audit to verify that all…
View Full Plan Text
K0325 Correction Date: 08/14/2025
Facility has removed the (ABHR) dispenser from the area identified on the survey that was conducted June 18,2025. Maintenance Department will perform a full house audit to verify that all (ABHR) dispensers are compliant with Life Safey codes. Any (ABHR) dispenser that does not meet the requirements as stated in K0325 deficiency will be removed and placed in an area that is appropriate. Any concerns will be presented to the Quality Assurance Performance improvement committee.
K0325 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/28/2025 · Spot-checks: weekly for 4 weeks
This provider submits the following plan of correction in good faith and to comply with Federal Law. This plan is not an admission of wrongdoing, nor does it reflect agreement with the facts…
View Full Plan Text
K0325 Correction Date: 06/01/2025
This provider submits the following plan of correction in good faith and to comply with Federal Law. This plan is not an admission of wrongdoing, nor does it reflect agreement with the facts and conclusions stated in the statement of deficiencies. It is the practice of the facility to ensure the ABHR is correctly installed.
1. The ABHR's found by resident room has been moved to not be located directly over a power outlet on 5/5/2025.
2. All other areas of the facility have been checked and no ABHR's were found to be over outlets.
3. Education completed with Maintenance staff regarding proper installation of ABHR's being near power outlets.
4. Every quarter for a year, the Maintenance Director or designee will check random ABHR's to ensure proper installation. This information will then be entered on a log and will be presented at QAPI meeting.
K0325 · Park Lane Post Acute LLC (PA)
Surveyed 03/25/2025 · Spot-checks: weekly for 4 weeks
1. Alcohol based hand rub dispenser was removed from above electrical outlet and placed in an acceptable area. 2. All alcohol -based hand rub dispensers were checked to ensure there were not…
View Full Plan Text
K0325 Correction Date: 05/14/2025
1. Alcohol based hand rub dispenser was removed from above electrical outlet and placed in an acceptable area.
2. All alcohol -based hand rub dispensers were checked to ensure there were not any placed above an outlet.
3. Education provided to Maintenance staff regarding proper placement of alcohol-based hand rub dispensers.
4. Administrator or designee will perform audits of any newly installed or moved alcohol-based hand rub dispensers will be conducted to ensure proper installment/placement. Results of the audit will be forwarded to the QAPI Committee for follow up as needed.
K0325 · Lecom at Presque Isle, Inc. (PA)
Surveyed 01/16/2025 · Spot-checks: weekly for 4 weeks
The main floor wound care room hand dispenser has been moved to a location in accordance with 8.7.3.1. The Maintenance Director and/or designee will audit all hand dispenser to ensure that…
View Full Plan Text
K0325 Correction Date: 03/03/2025
The main floor wound care room hand dispenser has been moved to a location in accordance with 8.7.3.1. The Maintenance Director and/or designee will audit all hand dispenser to ensure that they are placed in accordance with 8.7.3.1.
K0325 · Edenbrook South (PA)
Surveyed 01/06/2025 · Spot-checks: weekly for 4 weeks
Cited: Alcohol based hand sanitizer was placed on the wall over an electrical outlet and immediately removed. Sweep: Hand sanitizers will be audited to ensure they are not placed over an…
View Full Plan Text
K0325 Correction Date: 02/10/2025
Cited: Alcohol based hand sanitizer was placed on the wall over an electrical outlet and immediately removed. Sweep: Hand sanitizers will be audited to ensure they are not placed over an electrical outlet. Education: The maintenance director will be educated by the NHA on regulation K0325. Audits: An audit will be completed weekly x3 weeks, then monthly x2 months to ensure hand sanitizers are not located over electrical outlets. Results will be taken through QAPI.