K0222 · Spring Creek Rehabilitation and Nursing Center (PA)
Surveyed 05/01/2026 · Spot-checks: monthly for 4 weeks
The special locking arrangement signage has been placed on the 1st floor door to the stairtower, by Resident resident room. The Nursing Home Administrator will educate the Maintenance Director…
View Full Plan Text
K0222 Correction Date: 06/03/2026
The special locking arrangement signage has been placed on the 1st floor door to the stairtower, by Resident resident room. The Nursing Home Administrator will educate the Maintenance Director and Maintenance team to ensure locking arrangements signage are on access controlled egress doors. Random monthly audits will be done by the Maintenance Director/designee to ensure all compliance. Results of the audits will be reviewed/reported to the monthly QAPI committee to determine trends/compliance. QAPI committee will determine the need for continuance of audits.
K0222 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
It is the practice of the facility to have delayed egress functionality on exit doors, and all residents had the potential to be affected by this deficiency. 1. Facility has repaired the altar…
View Full Plan Text
K0222 Correction Date: 05/08/2026
It is the practice of the facility to have delayed egress functionality on exit doors, and all residents had the potential to be affected by this deficiency.
1. Facility has repaired the altar exit door and delayed egress is now functioning as per the design.
2. All delayed egress doors have been tested on 4/02/2026 and are functioning as per the design. All resident areas are free from hazard, and all systems are operating as designed.
3. The Director of Maintenance has completed education and training with Maintenance staff on testing delayed egress doors for proper function.
4. Every quarter for a year the Maintenance Director or designee will complete testing of delayed egress doors. This information will then be entered on a log and will be presented by the director to the monthly QAPI meeting for one year.
K0222 · Suburban Woods Health & Rehabilitation Center (PA)
Surveyed 03/25/2026 · Spot-checks: weekly for 4 weeks
1. The delayed egress locking door in the basement was repaired and concrete was shaved down by landscaping vendor allowing first floor egress door to open. 2. Maintenance audited all delayed…
View Full Plan Text
K0222 Correction Date: 05/22/2026
1. The delayed egress locking door in the basement was repaired and concrete was shaved down by landscaping vendor allowing first floor egress door to open.
2. Maintenance audited all delayed egress doors to ensure compliance
3. Maintenance Director was educated on the requirements of ensuring delayed egress locking doors should release after 15 seconds
4. NHA/designee will audit two random delayed egress locking doors weekly x4 and monthly x2. Results will be reviewed and revised as needed during monthly QAPI.
K0222 · Twin Lakes Rehabilitation and Healthcare Center (PA)
Surveyed 01/05/2026 · Spot-checks: weekly for 4 weeks
Immediately upon identification of the deficiency, all zip ties were removed from facility doors to ensure unrestricted egress and proper alarm functionality. Door alarms were tested to…
View Full Plan Text
K0222 Correction Date: 01/22/2026
Immediately upon identification of the deficiency, all zip ties were removed from facility doors to ensure unrestricted egress and proper alarm functionality. Door alarms were tested to confirm they were operational and functioning. All residents were assessed to ensure no harm occurred as a result of the deficient practice. No adverse outcomes were identified,
2. The facility completed a full environmental audit of exit doors, alarmed doors, and elopement prevention systems to ensure no devices, restraints or unauthorized modifications were in place. Door Company was called and contracted for same day inspection and fixing of the doors. Doors were adjusted and closures replaced as deemed necessary by the Company.
3. The facility has implemented a zero-tolerance policy for disabling, restraining, or modifying doors alarms, or safety systems in a manner inconsistent with manufacturer specifications and facility policy. A revised Safety Policy has been reviewed and re-issued, explicitly prohibiting the use of zip ties, restraints, or other devices to silence alarms or restrict doors. Maintenance and Nursing Leadership are now jointly responsible for ensuring alarm systems are properly maintained, adjusted and or repaired as needed. Any malfunctioning alarms will be addressed immediately through maintenance work orders or vendor call services.
4. Directed Inservice from an approved provider will be conducted for all nursing staff, ancillary staff, and maintenance personnel on all aspects of and regulatory requirements under F0689. Attendance will be documented, and testing will be provided to ensure understanding of the regulation.
5. The maintenance director or designee will conduct weekly environmental rounds for 4 weeks, then monthly thereafter to ensure doors and alarms are functioning properly and remain free from unauthorized modifications. The Director of Nursing or designee will conduct random spot checks during routine rounds. Findings will be documented and reviewed at the Quality Assurance and Performance Improvement committee meetings. Any non-compliance will result in immediate correction and re-education
Completion Date: 01/22/2026 Status: Submitted Date:
K0222 · Brickyard Healthcare - Twelfth Street Care Center (IN)
Surveyed 12/09/2025 · Spot-checks: monthly for 4 weeks
The door code was posted above the keypad for the therapy hall exit door. This alleged deficient practice could affect residents in the vicinity. A monthly task was added to TELS to Check…
View Full Plan Text
K0222
Completion Date: 02/03/2026
The door code was posted above the keypad for the therapy hall exit door. This alleged deficient practice could affect residents in the vicinity. A monthly task was added to TELS to Check every egress door with a magnetic lock to ensure the code is posted clearly above the keypad. No special knowledge must be required to open. (15 second egress doors must have 15 second egress signange) the unit must know the code. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues.
K0222 · Delaware Valley Veterans' Home (PA)
Surveyed 07/28/2025 · Spot-checks: monthly for 4 weeks
Missing required wording has been added to egress signage on A-Wing Dining Room delayed-egress emergency exit door. Moving forward inspections of delayed egress doors will be done monthly to…
View Full Plan Text
K0222 Correction Date: 09/26/2025
Missing required wording has been added to egress signage on A-Wing Dining Room delayed-egress emergency exit door. Moving forward inspections of delayed egress doors will be done monthly to confirm signs are in place. The results of the audit will be reviewed at the Quality Assurance & Performance Improvement meetings. The Quality Assurance Committee will determine the need for additional audits/ interventions for ongoing compliance.
K0222 · Sunnyview Nursing and Rehabilitation Center (PA)
Surveyed 07/24/2025 · Spot-checks: monthly for 4 weeks
Audits will be held to ensure all exit doors are able to open entirely and free of any debris. Audits will be brought up at the monthly meeting and results will be added to the meeting minutes…
View Full Plan Text
K0222 Correction Date: 09/07/2025
Audits will be held to ensure all exit doors are able to open entirely and free of any debris. Audits will be brought up at the monthly meeting and results will be added to the meeting minutes to ensure compliance and need for further audits
K0222 · Wesley Enhanced Living - Doylestown (PA)
Surveyed 02/28/2025 · Spot-checks: monthly for 4 weeks
The missing hardware on double doors was replaced to cover the hole in the frame ensuring the fire rating of the assembly. The doors will be monitored on the monthly door inspections in our…
View Full Plan Text
K0222 Correction Date: 03/12/2025
The missing hardware on double doors was replaced to cover the hole in the frame ensuring the fire rating of the assembly. The doors will be monitored on the monthly door inspections in our TELS maintenance program by maintenance staff. Outcomes of the monthly door inspections will be reported on in monthly safety committee meetings. The Director of Facility Operations will monitor on the annual fire/smoke door inspections. The Director of Facility Operations will report the results and remediation, if necessary, in the Quarterly Quality Assurance Process Improvement (QAPI) Committee meeting that includes the Executive Director/Nursing Home Administrator and the Director of Nursing.
K0222 · Majestic Care of Lafayette (IN)
Surveyed 09/29/2026 · Spot-checks: weekly for 6 months
"PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS". What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur;…
View Full Plan Text
K0222
Completion Date: 10/16/2026
K222 What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice. A sticker reading "PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS" Was immediately placed on the doorway leading from the service hall in accordance with the regulation. How other residents having the potential to be affected by the regulation requiring appropriate signage on doors equipped with delayed egress. All doors equipped with delayed egress were inspected to ensure the appropriate signage was located on them instructing: "PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS". What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; how the corrective action(s) will be monitored to ensure the deficient practice will not recur. All doors equipped with delayed egress will be inspected weekly for 6 months for compliant signage. What quality assurance program will be put into place; and by what date the systemic changes for each deficiency will be completed. Results of audit tools will be presented to the QAPI Committee Monthly to review for compliance and follow-up. will be submitted to the QAPI committee overseen by the ED for review and follow-up.
K0222 · Harborview Rehabilitation and Care Center at Doylestown (PA)
Surveyed 09/21/2026 · Spot-checks: weekly for 4 weeks
8. 0222 Egress Doors Delayed Egress: 1. Delayed egress release and signage: .a. The delayed-egress release was repaired by Current Technology on the same day the deficiency was identified. b.…
View Full Plan Text
K0222 Correction Date: 11/10/2026
8. 0222 Egress Doors Delayed Egress:
1. Delayed egress release and signage: .a. The delayed-egress release was repaired by Current Technology on the same day the deficiency was identified. b. The required delayed-egress signage was posted on the cited first-floor corridor door the same day. c. The Maintenance Director/designee checked all similar delayed-egress doors to ensure proper operation and signage. d. The Maintenance Director/designee will audit delayed-egress doors weekly for four weeks, then monthly for three months. Findings and corrective actions will be reviewed through QAPI.
K0222 · Independence Rehab and Nursing (PA)
Surveyed 09/16/2026 · Spot-checks: weekly for 4 weeks
The Maintenance Director installed the proper signage on the facility's delayed egress doors including the west exit doors. Delayed egress repaired by vendor. Maintenance Director will inspect…
View Full Plan Text
K0222 Correction Date: 10/13/2026
The Maintenance Director installed the proper signage on the facility's delayed egress doors including the west exit doors. Delayed egress repaired by vendor. Maintenance Director will inspect the signage weekly for four weeks to ensure that is installed per code. The QAPI Committee will monitor the facility's ongoing compliance with door maintenance and inspection procedures to ensure that corrective actions remain effective and are consistently maintained.
K0222 · Kadima Rehabilitation & Nursing at New Castle (PA)
Surveyed 05/12/2026 · Spot-checks: weekly for 4 weeks
Corrective Action The bread carts were removed by the dietary manager immediately from the area in front of the kitchen exit door. The exit door was inspected and verified to open fully and…
View Full Plan Text
K0222 Correction Date: 07/07/2026
Corrective Action The bread carts were removed by the dietary manager immediately from the area in front of the kitchen exit door. The exit door was inspected and verified to open fully and provide unobstructed egress in accordance with NFPA 101 requirements. Identification of Other Areas The Maintenance Director and Dietary Manager conducted an inspection of all exit doors, exit access corridors, and means of egress throughout the facility to identify any additional obstructions that could impede emergency evacuation. Any identified obstructions were removed immediately. Measures to Prevent Recurrence The facility Administrator has re-educated dietary staff, maintenance staff, and department managers regarding the requirement to keep all exit doors, exit access pathways, and means of egress clear and unobstructed at all times. The Dietary Department has designated approved storage locations for bread carts and other equipment to ensure that items are not placed in front of exit doors or within required egress pathways. The facility's Environmental and Life Safety rounds process has been updated to include monitoring of exit doors and surrounding areas for potential obstructions. Monitoring The Maintenance Director or designee will conduct weekly inspections of all exit doors and egress pathways for a period of three months and monthly inspections thereafter for an additional nine months to verify compliance. Any identified deficiencies will be corrected immediately and documented. Results of the inspections will be reported to the facility's Quality Assurance and Performance Improvement (QAPI) Committee quarterly for review and follow-up as necessary.