K0920 · Markley Rehabilitation and Healthcare Center (PA)
Surveyed 07/23/2026 · Spot-checks: weekly for 4 weeks
The extension cord in resident resident room was removed. Maintenance staff conducted an audit of resident rooms, and no additional extension cords were in use. NHA/Maintenance…
View Full Plan Text
K0920 Correction Date: 08/26/2026
The extension cord in resident resident room was removed. Maintenance staff conducted an audit of resident rooms, and no additional extension cords were in use. NHA/Maintenance Director/Designee will in-service staff on the regulations regarding extension cord usage in the facility. The Maintenance Director/Designee will conduct an audit on random resident rooms once a week for 4 weeks, then once a month for 2 months to ensure that no extension cords are being used in resident rooms. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendations needed.
K0920 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: monthly for 4 weeks
920: Electrical Equipment - Power Cords and Extens: The facility failed to monitor the use of extension cords and surge suppressors within the facility, affecting two of seven smoke…
View Full Plan Text
K0920 Correction Date: 08/05/2026
920: Electrical Equipment - Power Cords and Extens: The facility failed to monitor the use of extension cords and surge suppressors within the facility, affecting two of seven smoke compartments within the component. No residents were affected. All residents have the potential to be affected. The extension cord was removed from the interstitial space, above the suspended ceiling, behind the nurse's station by the Maintenance Director and permanent electrical outlet put in place by 05AUG2026. The surge suppressor was removed from the Dialysis room by the maintenance director on 08JUL2026. Maintenance Director/Designee completed an audit 08JUL2026 to ensure that no unauthorized surge protectors or extension cords in use. On 21JUL2026, NHA educated the Maintenance Director and maintenance team on the importance of ensuring safe usage of extension cords and surge suppressors per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits monthly x 12 months, to ensure the facility meets regulatory requirements. NHA/Designee will audit quarterly Life Safety Binder with Maintenance Director to ensure compliance. Results will be submitted to the quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0920 · The Gardens at Easton (PA)
Surveyed 05/21/2026 · Spot-checks: weekly for 4 weeks
NFPA 101 Electrical Equipment- Power cords and Extensions 1. Multi outlet plug in device was removed from resident room. 2. House wide Education to all staff- multi outlet plug ins and power…
View Full Plan Text
K0920 Correction Date: 06/29/2026
K 920- NFPA 101 Electrical Equipment- Power cords and Extensions
1. Multi outlet plug in device was removed from resident room.
2. House wide Education to all staff- multi outlet plug ins and power strips are prohibited in facility and residents rooms. Remove and/or report to supervisor immediately if seen.
3. Weekly audits of all rooms to ensure no multi plug in outlets or power strips are in resident rooms x4 weeks then monthly x2 months.
4. Report findings to QAPI
K0920 · Lehigh Valley Hospital Transitional Skilled Unit (PA)
Surveyed 05/06/2026 · Spot-checks: monthly for 4 weeks
1. The extension cord observed in room 5T27 was immediately removed. Approved power sources were confirmed for all patient care equipment in the room. 2. Nursing and Facilities staff completed…
View Full Plan Text
K0920 Correction Date: 05/27/2026
1. The extension cord observed in room 5T27 was immediately removed. Approved power sources were confirmed for all patient care equipment in the room.
2. Nursing and Facilities staff completed a unitwide inspection of all patient rooms and care areas to identify and remove unauthorized extension cords or nonapproved power strips.
3. Staff education was completed for nursing and ancillary departments on proper use of power strips and prohibition of extension cords per NFPA 99 and NFPA
70. Unit leadership will reinforce expectations during routine safety rounds.
4. Monthly environmental safety rounds will include specific audits for extension cord and power strip compliance, with findings reported to the QAPI committee.
K0920 · Spring Creek Rehabilitation and Nursing Center (PA)
Surveyed 05/01/2026 · Spot-checks: monthly for 4 weeks
The surge suppressor, suspended from electrical wiring, at the Ground Floor Nurses' Station was secured to the wall. The Nursing Home Administrator will educate the Maintenance Director and…
View Full Plan Text
K0920 Correction Date: 06/03/2026
The surge suppressor, suspended from electrical wiring, at the Ground Floor Nurses' Station was secured to the wall. The Nursing Home Administrator will educate the Maintenance Director and Maintenance team to ensure surge protectors are not suspended and must be secured to the wall. Random monthly audits will be done by the Maintenance Director/designee to ensure all compliance. Results of the audits will be reviewed/reported to the monthly QAPI committee to determine trends/compliance. QAPI committee will determine the need for continuance of audits.
K0920 · Cedarbrook Senior Care and Rehabilitation (PA)
Surveyed 04/29/2026 · Spot-checks: monthly for 3 months
1. The surge suppressor within D1 PT Rehab office was removed. Facility staff will monitor the facility throughout for surge suppressor devices on a monthly basis for 3 months. Any…
View Full Plan Text
K0920 Correction Date: 06/09/2026
1. The surge suppressor within D1 PT Rehab office was removed. Facility staff will monitor the facility throughout for surge suppressor devices on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
K0920 · Suburban Woods Health & Rehabilitation Center (PA)
Surveyed 03/25/2026 · Spot-checks: weekly for 4 weeks
1. The outlet multiplier and extension cord were removed. 2. Maintenance Director audited all office spaces to ensure none are in use 3. Staff educated that extension cords are prohibited in…
View Full Plan Text
K0920 Correction Date: 05/22/2026
1. The outlet multiplier and extension cord were removed.
2. Maintenance Director audited all office spaces to ensure none are in use
3. Staff educated that extension cords are prohibited in the facility.
4. Random audits to be completed weekly x3 and monthly x1 to ensure there are no multipliers or extension cords being used. Results will be reviewed and revised as needed during monthly QAPI.
K0920 · Wesley Enhanced Living - Doylestown (PA)
Surveyed 03/16/2026 · Spot-checks: weekly for 4 weeks
Extension cords removed from area and Housekeeping staff in serviced on prohibition of using them. Placed into TELS maintenance program for quarterly inspections. Also placed into semi-annual…
View Full Plan Text
K0920 Correction Date: 05/15/2026
Extension cords removed from area and Housekeeping staff in serviced on prohibition of using them. Placed into TELS maintenance program for quarterly inspections. Also placed into semi-annual safety surveillance rounds and reported on during Wesley Enhanced Living's safety committee meetings. Also to be reported during quarterly Quality Assurance committee that includes the Executive Director/Nursing Home Administrator, Director of Nursing, and Director of Facility Operations.
K0920 · Onyx Nursing & Rehabilitation (PA)
Surveyed 03/11/2026 · Spot-checks: weekly for 4 weeks
1. Maintenance staff removed extension cord from residence room and unplugged AC unit from power strip and plugged unit into wall outlet. 2. NHA/designee conducted audit of residence rooms to…
View Full Plan Text
K0920 Correction Date: 04/08/2026
Preparation and submission of this Plan of Correction does not constitute an admission or agreement with the facts alleged or conclusions stated in the Statement of Deficiencies. This Plan of Correction is submitted solely because it is required by Federal and State regulations.
1. Maintenance staff removed extension cord from residence room and unplugged AC unit from power strip and plugged unit into wall outlet.
2. NHA/designee conducted audit of residence rooms to ensure no, non pcree usage of power strips in Resident room. No other issues identified.
3. NHA/designee educated maintenance staff on requirements to ensure no non-PCREE equipment are plugged into power strips in patient care areas and power strips used for PCREE meet UL1363 or UL 606011.and power strips for non-PCREE when use is permitted must be certified, UL1363. And all electrical equipment are in good repair.
4. NHA/designee will audit, patient rooms, weekly X4 then monthly X2. or until substantial is attained to ensure no extension cords improperly in use. Results will be brought to QAPI for further evaluation and recommendations.
K0920 · Accela Rehab and Care Center at Somerton (PA)
Surveyed 02/24/2026 · Spot-checks: weekly for 4 weeks
Preparation and /or execution of this plan does not constitute admission or agreement by the provider of the truths or facts alleged or conclusions set forth in the statement of deficiencies.…
View Full Plan Text
K0920 Correction Date: 04/21/2026
Preparation and /or execution of this plan does not constitute admission or agreement by the provider of the truths or facts alleged or conclusions set forth in the statement of deficiencies. The plan of correction is prepared and/or executed with federal and state law requirements. Identification of other residents or areas having the potential to be affected due to the nature of the deficiency: The deficient practice has the potential to affect all residents. Corrective action 1.Extension cords in laundry room and A32 were removed 2.Maintenance director or designee to re-educate maintenance staff on the importance of NFPA regulations regarding power strips 3.Maintenance director or designee to randomly audit laundry rooms and resident rooms for inappropriate usage of powers strips. Weekly X4 Monthly X3 4.Results will be reviewed at the quarterly QAPI meeting
K0920 · Bethany Village Retirement Center (PA)
Surveyed 01/06/2026 · Spot-checks: monthly for 3 months
Following discovery the relocatable power tap was promptly removed. A full building survey was undertaken and completed by January 16 to identify and remove any and all relocatable power taps.…
View Full Plan Text
K0920 Correction Date: 02/06/2026
Following discovery the relocatable power tap was promptly removed. A full building survey was undertaken and completed by January 16 to identify and remove any and all relocatable power taps. Administrator or designee will continue monthly inspections for 3 months; as well as quarterly for 1 year to identify, report, and remove any additional relocatable power taps. Instances discovered will be tracked and corrected. Facilities staff were educated on the necessity of checking for and removing any relocatable power taps when working in resident rooms and throughout the building. Results of the inspections, additional discoveries addressed, and education of staff will be included in the facility's monthly 2026 Quality Assurance and Performance Improvement (QAPI) meetings for review and approval.
K0920 · Easton Skilled Nursing and Rehabilitation Center (PA)
Surveyed 12/30/2025 · Spot-checks: weekly for 4 weeks
1. Extension cord removed from resident resident room. Education on electrical extension cords 3. Will Audit weekly x4 to ensure compliance.
View Full Plan Text
K0920 Correction Date: 01/14/2026
1. Extension cord removed from resident resident room. Education on electrical extension cords
3. Will Audit weekly x4 to ensure compliance.
K0920 · Cedar Crest Post Acute (PA)
Surveyed 12/17/2025 · Spot-checks: monthly for 4 weeks
1. Power strip removed from respiratory therapy office on 1st floor. Maintenance Director and/or designee will install hospital grade, hard wired outlet in office. 2. Monthly audit of offices…
View Full Plan Text
K0920 Correction Date: 01/15/2026
1. Power strip removed from respiratory therapy office on 1st floor. Maintenance Director and/or designee will install hospital grade, hard wired outlet in office.
2. Monthly audit of offices will be completed for unauthorized use of power strips. Identified areas of concern will be addressed. Identified trends to be reviewed during QAPI.
K0920 · Cedar Haven Healthcare Center (PA)
Surveyed 12/16/2025 · Spot-checks: weekly for 4 weeks
Both surge suppressors were removed in the finance dept. Room. The surge suppressor was removed that the microwave was plugged into on the ground floor activities office. Microwave was plugged…
View Full Plan Text
K0920 Correction Date: 01/21/2026
Both surge suppressors were removed in the finance dept. Room. The surge suppressor was removed that the microwave was plugged into on the ground floor activities office. Microwave was plugged directly into the receptacle. Current staff reeducated on use of surge suppressors . Maintenance will do random weekly audits x4 then monthly audits x2 to ensure surge suppressors are being used correctly. Results of audits will be reviewed with the QAPI committee
K0920 · Trillium Place (PA)
Surveyed 12/08/2025 · Spot-checks: weekly for 4 weeks
The surge suppressor supplying electrical power to another surge suppressor in the Medical Records Room has been removed from service. -The plan of correction has been completed on 12/15/25.…
View Full Plan Text
K0920 Correction Date: 12/15/2025
The surge suppressor supplying electrical power to another surge suppressor in the Medical Records Room has been removed from service. -The plan of correction has been completed on 12/15/25. -Education has been provided to the maintenance team on 12/15/2025. -Audits will be conducted by the Assistant Director of Facilities or designee quarterly. -Audit reports will be reported to the Quality Assurance committee for review and further recommendations.
K0920 · Ivory Nursing & Rehabilitation (PA)
Surveyed 11/24/2025 · Spot-checks: weekly for 4 weeks
The extension cord was immediately removed from the DON office. All residents may be affected by this deficient practice. Administrative nursing staff will be educated on the use of power…
View Full Plan Text
K0920 Correction Date: 12/30/2025
The extension cord was immediately removed from the DON office. All residents may be affected by this deficient practice. Administrative nursing staff will be educated on the use of power strips and extension cords. Maintenance director or designee will randomly audit the facility weekly x 4 weeks to ensure that no extension cords are being used. Findings of these audits will be presented at the facility's QAPI meeting. It will be determined at that time if continued audits are necessary.
K0920 · Graduate Post Acute (PA)
Surveyed 11/24/2025 · Spot-checks: monthly for 3 weeks
Maintenance removed extension cord in kitchen that was used for osculative fan Maintenance to audit center to ensure power strips are being utilized with general precautions. NHA/Designee will…
View Full Plan Text
K0920 Correction Date: 01/15/2026
Maintenance removed extension cord in kitchen that was used for osculative fan Maintenance to audit center to ensure power strips are being utilized with general precautions. NHA/Designee will audit center to ensure power strips are being utilized with general precautions three times a week for 3 weeks and 2 times monthly for 2 months. Audits will be reviewed by the QAPI committee during Quality Assurance meetings, and any variances will be addressed.
K0920 · Sterling Health Care and Rehab Center (PA)
Surveyed 11/20/2025 · Spot-checks: weekly for 90 days
1. Maintenance Director will remove the power strip being used to plug in the refrigerator inside DON office. 2. Maintenance Director will monitor DON office to ensure refrigerator is plugged…
View Full Plan Text
K0920 Correction Date: 01/12/2026
1. Maintenance Director will remove the power strip being used to plug in the refrigerator inside DON office.
2. Maintenance Director will monitor DON office to ensure refrigerator is plugged into a wall outlet for 90 days.
3. Maintenance director will conduct random audits of offices to ensure no power strips in place.
4. Findings will be reported to QAPI and Safety Committee for 90 days to ensure compliance.
K0920 · West Chester Rehabilitation and Healthcare Center (PA)
Surveyed 10/28/2025 · Spot-checks: weekly for 4 weeks
1. The extension cord at bed "B" in resident room on the first floor was removed. 2. Staff were educating on the regulations concerning the use of extension cords and power strips. 3. An audit…
View Full Plan Text
K0920 Correction Date: 12/04/2025
1. The extension cord at bed "B" in resident room on the first floor was removed.
2. Staff were educating on the regulations concerning the use of extension cords and power strips.
3. An audit of all resident rooms was conducted to identify if extension cords or power strips were being used incorrectly. 10 random resident rooms will be audited weekly for 4 weeks followed by monthly for 2 months to ensure extension cords and power strips are not being used incorrectly. Audit results will be submitted to Quality Assurance Performance Improvement Committee for additional review and recommendations as needed. Further audit frequency will be determined based on audit findings.
K0920 · Harborview Rehabilitation and Care Center at Doylestown (PA)
Surveyed 10/20/2025 · Spot-checks: monthly for 4 weeks
1. Maintenance staff removed all unauthorized extension cords and power strips in nursing office and re-educated staff on appropriate electrical usage. 2. Nursing and maintenance staff will…
View Full Plan Text
K0920 Correction Date: 11/26/2025
1. Maintenance staff removed all unauthorized extension cords and power strips in nursing office and re-educated staff on appropriate electrical usage. 2.Nursing and maintenance staff will ensure all equipment is connected to appropriate outlets.
3. Maintenance Director/designee will conduct audits of electrical use during environmental rounds monthly x 3.
4. Results will be reported to the QAPI Committee.
K0920 · Midtown Oaks Health & Rehab Center (PA)
Surveyed 09/17/2025 · Spot-checks: weekly for 3 months
Maintenance Director unplugged electric coffee pot and microwave from power strip. The Administrator and/or designee will re-educate facility management team on K0920 specific to electrical…
View Full Plan Text
K0920 Correction Date: 10/14/2025
Maintenance Director unplugged electric coffee pot and microwave from power strip. The Administrator and/or designee will re-educate facility management team on K0920 specific to electrical appliance plugs and power strip usage. Maintenance Director and/or designee will audit classroom 1x weekly for 3 months to ensure no appliances are plugged into power stip. Results of this audit will be reviewed at the Quality Assurance and Performance Improvement meeting.
K0920 · The Gardens at West Shore (PA)
Surveyed 08/20/2025 · Spot-checks: weekly for 4 weeks
1. The daisy chained surge suppressors in the activity's storage room was removed. 2. Maintenance Director/ Designee will conduct an audit of storage rooms to ensure surge suppressors are not…
View Full Plan Text
K0920 Correction Date: 09/23/2025
K0920
1. The daisy chained surge suppressors in the activity's storage room was removed.
2. Maintenance Director/ Designee will conduct an audit of storage rooms to ensure surge suppressors are not daisy chained together. If it is found that surge suppressors are daisy chained together, they will be removed immediately.
3. Maintenance Director/Designee will conduct an audit of storage rooms to ensure surge suppressors are not daisy chained together quarterly. Results to QAPI.
4. Date of Compliance 9/23/25
K0920 · Maybrook Hills Rehabilitation and Healthcare Center (PA)
Surveyed 08/12/2025 · Spot-checks: monthly for 4 weeks
Electrical power strips were removed from the Human Resources office and DON office. Areas throughout the building were reviewed for other concerns and addressed as applicable. Maintenance…
View Full Plan Text
K0920 Correction Date: 08/18/2025
Electrical power strips were removed from the Human Resources office and DON office. Areas throughout the building were reviewed for other concerns and addressed as applicable. Maintenance staff are aware of the need for monthly checks for improper power strip usage and other electrical issues concerning Life Safety compliance, as well as new areas of noted concern and corrective action to take place as applicable. The Maintenance Director/designee will complete a monthly check for power strips. And to ensure compliance, maintenance will check monthly for six months, findings will be reviewed at monthly Quality Assurance meetings for compliance, improvement and need for continued auditing.
K0920 · Homeland Center (PA)
Surveyed 08/05/2025 · Spot-checks: weekly for 4 weeks
Preparation and submission of this Plan of Correction is required by state and federal law. This plan does not constitute an admission for purposes of general liability, professional…
View Full Plan Text
K0920 Correction Date: 09/22/2025
Preparation and submission of this Plan of Correction is required by state and federal law. This plan does not constitute an admission for purposes of general liability, professional malpractice, or any other court proceeding. Homeland Center appreciates the efforts of the state survey team to serve the best interest of Homeland Center Residents. Observation 1 corrected by removing suspended surge suppressor from the Director of Nursing office. All staff will receive additional in-service education for complete understanding of proper usage of a surge suppressor. Quality Assurance (CQI) process to occur, on an on-going basis, with visual monitoring, to ensure proper use, including not having surge suppressor(s) suspended from an outlet, as well as not plugging any inappropriate electrical device into a surge suppressor, and will either be mounted, or firmly positioned on the ground. The Administrator, Director of Maintenance/Emergency Preparedness/Purchasing and Director of QAPI will be responsible for consistent, on-going compliance.
K0920 · Aventura at Pembrooke (PA)
Surveyed 08/05/2025 · Spot-checks: weekly for 4 weeks
The facility failed to monitor for the unauthorized use of surge protectors and extension cords, on two of four floors. No residents were affected. All residents have the potential to be…
View Full Plan Text
K0920 Correction Date: 09/12/2025
The facility failed to monitor for the unauthorized use of surge protectors and extension cords, on two of four floors. No residents were affected. All residents have the potential to be affected. The extension cord in resident room at B-bed on 2nd floor was removed to meet the requirement. The surge protector in resident room A-bed on 2nd floor was removed to meet the requirement. The extension cord in resident room at A-bed on 1st floor was removed to meet the requirement. An audit was completed by the Maintenance Director to ensure that no unauthorized surge protectors or extension cords are in use. Director of Maintenance and maintenance staff were educated by the Administrator on the requirement. The Maintenance Director/Designee will conduct one weekly audit to ensure compliance with unauthorized use of surge protector and extension cords for 4 weeks an than monthly thereafter. The audits will include new residents decorated areas and new equipment. Results of audits will be reviewed at the Quarterly Quality Assurance and Improvement Committee Meeting over the duration of the audit process. Based on the results of the audits, a decision will be made regarding the need for continued submission and reporting.