K0355 · Fairlane Gardens Nursing and Rehab at Reading (PA)
Surveyed 07/29/2026 · Spot-checks: weekly for 4 weeks
1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random…
View Full Plan Text
K0355 Correction Date: 09/15/2026
1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random audits weekly x 4 weeks then monthly to ensure fire extinguishers are not blocked. 4) A summary of the audit's findings will be submitted to the QAPI committee for recommendations
K0355 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: weekly for 4 weeks
0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No…
View Full Plan Text
K0355 Correction Date: 08/05/2026
0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No residents were affected. All residents have the potential to be affected. Signage to be installed by the Maintenance Director/designee near the Laundry Chemical Room to identify the portable fire extinguisher by 05AUG2026. Maintenance Director/Designee completed an audit of all portable fire extinguishers in the facility on 09JUL2026 to ensure proper identifying signage. On 21JUL2026, NHA educated the Maintenance Director and maintenance department on the importance of maintaining proper identifying signage for portable fire extinguishers per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits weekly x4 weeks then monthly x 2 months to ensure fire extinguisher signage meets the regulatory requirement. Results will be submitted to the quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0355 · Sanatoga Center (PA)
Surveyed 07/01/2026 · Spot-checks: monthly for 4 weeks
The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide…
View Full Plan Text
K0355 Correction Date: 08/11/2026
The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide audit of all fire extinguishers to verify they are properly installed, accessible, fully charged, inspected, and hung accordingly. The Maintenance Director/designee was educated on placement of portable fire extinguishers The Maintenance Director/designee will conduct monthly audits of all portable fire extinguishers x 3 months to verify continued compliance. Audit results will be reviewed through QAPI x 3 months
K0355 · Northampton Post Acute (PA)
Surveyed 05/27/2026 · Spot-checks: weekly for 4 weeks
1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1,…
View Full Plan Text
K0355 Correction Date: 06/12/2026
1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1, 2026.
2. Maintenance Director/Designee will conduct weekly random audits for 4 weeks to ensure that signage stating staff are to employ the ansul system before using the fire extinguishing device is present by the K-Type portable fire extinguisher located in the dietary department. Findings of the audits will be reported to the Quality Assurance Performance Improvement (QAPI) Committee for further action planning if required.
K0355 · Chambersburg Skilled Nursing and Rehabilitation Center (PA)
Surveyed 05/18/2026 · Spot-checks: weekly for 2 months
1. and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current. 3. Maintenance department will be educated on the standards of…
View Full Plan Text
K0355 Correction Date: 06/19/2026
1.and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current.
3. Maintenance department will be educated on the standards of ensuring the facility has completed the monthly inspection of portable fire extinguishers.
4. Maintenance or facility designee will audit the facilities monthly inspection of portable fire extinguishers weekly for 2 months, then every 60 days throughout the year and results of the audit will be reported to the QAPI committee.
K0355 · Cedarbrook Senior Care and Rehabilitation (PA)
Surveyed 04/29/2026 · Spot-checks: monthly for 3 months
1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for…
View Full Plan Text
K0355 Correction Date: 06/09/2026
1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee. b) D7 portable fire extinguisher indicator light near Dining Room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
2. The facility's vendor will ensure all portable fire extinguisher will be inspected on a monthly basis. Facility staff will monitor all portable fire extinguishers on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
K0355 · Twinbrook Healthcare and Rehabilitation Center (PA)
Surveyed 04/22/2026 · Spot-checks: monthly for 4 weeks
1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10,…
View Full Plan Text
K0355 Correction Date: 05/08/2026
1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10, Standard for Portable Fire Extinguishers by May 1,2026.
2. The Maintenance Director or Designee will ensure that all portable fire extinguishers will audit monthly for three months. The Maintenance Director will add the inspection of all portable fire extinguishers to the monthly Preventative Maintenance schedule beginning May 2026.
3. The results of the audits will be reported to the Quality Assurance and Performance Improvement Committee for review at the next monthly meeting.
K0355 · Edenbrook North (PA)
Surveyed 04/15/2026 · Spot-checks: weekly for 4 weeks
The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no…
View Full Plan Text
K0355 Correction Date: 06/02/2026
The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no other fire extinguishes are hung in excess of 60 inches from the floor to the top of the handle. Results of this audit will be reported to the QA steering committee, at which time the committee will determine the need for future audits.
K0355 · Pocopson Home (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to…
View Full Plan Text
K0355 Correction Date: 04/02/2026
1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to handle. b. The portable fire extinguisher, located within the penthouse level Elevator Machine Room, has been checked. Maintenance will maintain fire extinguisher inspections on a monthly basis. Audit results will be reported to the Quality Improvement/Infection Control Committee. Preparation and submission of this Plan of Correction is required by State and Federal law. This Plan of Correction does not constitute an admission for purposes of general liability, professional malpractice or any other court proceeding
K0355 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency. 1. The Fire Extinguisher in…
View Full Plan Text
K0355 Correction Date: 05/08/2026
It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency.
1. The Fire Extinguisher in basement hallway has had the obstruction removed to remain accessible for use.
2. All Fire Extinguishers in the facility have been reinspected and are ready for use and the staff inspect the extinguisher areas to prevent this from happening in the future.
3. The Director of Maintenance has completed education with Maintenance staff regarding monitoring Fire Extinguishers by Maintenance Staff.
4. Every quarter for a year the Maintenance Director or designee will check Fire Extinguishers throughout the facility to ensure they are ready for use. This information will then be entered on a log and will be presented by the director to the monthly QAPI meeting for one year.
K0355 · Marywood Heights (PA)
Surveyed 03/10/2026 · Spot-checks: monthly for 4 weeks
Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to…
View Full Plan Text
K0355 Correction Date: 03/31/2026
Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to QAPI committee to ensure portable fire extinguishers are inspected.
K0355 · Embassy of Hearthside (PA)
Surveyed 02/09/2026 · Spot-checks: monthly for 4 weeks
Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS.…
View Full Plan Text
K0355 Correction Date: 03/30/2026
Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS. Maintenance will continue to monitor and report findings to monthly QAPI meetings.
K0355 · Liberty Pointe Rehabilitation and Healthcare Center (PA)
Surveyed 01/20/2026 · Spot-checks: weekly for 4 weeks
Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to…
View Full Plan Text
K0355 Correction Date: 02/23/2026
Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to the QAPI committee.
K0355 · Fairview Rehab and Care Center (PA)
Surveyed 01/13/2026 · Spot-checks: weekly for 4 weeks
Missing fire extinguisher Annual inspection to be completed and certificate for the inspection to be obtained. Maintenance team educated on timeliness of inspections each month and getting…
View Full Plan Text
K0355 Correction Date: 03/03/2026
K0355 Missing fire extinguisher Annual inspection to be completed and certificate for the inspection to be obtained. Maintenance team educated on timeliness of inspections each month and getting yearly certificate by Regional Maintenance Director. Maintenance team to audit all tickets are updated on all extinguishers Maintenance director to present update at qapi.
K0355 · Cedar Haven Healthcare Center (PA)
Surveyed 12/16/2025 · Spot-checks: weekly for 4 weeks
Med Cart was immediately removed from blocking the fire extinguisher Nursing staff will be rein-serviced about blocking fire extinguishers in hallways. Maintenance will do random weekly audits…
View Full Plan Text
K0355 Correction Date: 01/21/2026
Med Cart was immediately removed from blocking the fire extinguisher Nursing staff will be rein-serviced about blocking fire extinguishers in hallways. Maintenance will do random weekly audits x4 then monthly audits x2 to ensure fire extinguishers are not being blocked. Results of audits will be reviewed with the QAPI committee.
K0355 · Care Pavilion Nursing and Rehabilitation Center (PA)
Surveyed 12/15/2025 · Spot-checks: monthly for 4 weeks
Correction: Effected fire extinguishers was properly mounted. Systemic Changes: Monthly fire extinguisher inspections were added immediately. Monitoring: Inspection logs will be reviewed…
View Full Plan Text
K0355 Correction Date: 01/30/2026
Correction: Effected fire extinguishers was properly mounted. Systemic Changes: Monthly fire extinguisher inspections were added immediately. Monitoring: Inspection logs will be reviewed monthly.
Completion Date: 1/30/26.
K0355 · Lecom at Village Square, LLC (PA)
Surveyed 12/11/2025 · Spot-checks: monthly for 6 months
Maintenance Director to complete whole house audit for all portable fire extinguishers in the facility to ensure proper inspection and function by 01/02/2026. Education will be provided to the…
View Full Plan Text
K0355 Correction Date: 01/16/2026
Maintenance Director to complete whole house audit for all portable fire extinguishers in the facility to ensure proper inspection and function by 01/02/2026. Education will be provided to the Maintenance Director and department by the Nursing Home Administrator regarding proper and timely inspections of the portable fire extinguishers by 01/09/2026. Maintenance Director or designee to monitor compliance monthly, as required. The monthly preventative maintenance schedule will be updated to include a mandatory, verifiable and dated monthly documentation step for fire extinguisher inspections. Nursing Home Administrator will complete monthly audits of these inspections monthly for 6 months. Results of these audits will be reviewed at the quarterly QAA meetings. Nursing Home Administrator will review the Life Safety checklist during the quarterly QAPI meeting.
K0355 · Trillium Place (PA)
Surveyed 12/08/2025 · Spot-checks: weekly for 4 weeks
The portable fire extinguisher located in the Susquehanna Elevator Machine Room has been removed from the floor and secured on the wall with the appropriate mounting hardware. -The plan of…
View Full Plan Text
K0355 Correction Date: 12/15/2025
The portable fire extinguisher located in the Susquehanna Elevator Machine Room has been removed from the floor and secured on the wall with the appropriate mounting hardware. -The plan of correction has been completed on 12/15/25. -Education has been provided to the maintenance team on 12/15/2025. -Audits will be conducted by the Assistant Director of Facilities or designee quarterly. -Audit reports will be reported to the Quality Assurance committee for review and further recommendations.
K0355 · Independence Rehab and Nursing (PA)
Surveyed 11/24/2025 · Spot-checks: monthly for 4 weeks
1. On 9/22/2025 the Maintenance assistant inspected the fire extinguishers in the elevator room and in the kitchen. 2. On 9/22/2025 the maintenance team conducted an audit of all fire…
View Full Plan Text
K0355 Correction Date: 12/29/2025
1. On 9/22/2025 the Maintenance assistant inspected the fire extinguishers in the elevator room and in the kitchen.
2. On 9/22/2025 the maintenance team conducted an audit of all fire extinguishers to verify that monthly inspection documentation was present.
3. On 10/2/2025 The NHA educated the Maintenance Director on fire extinguishers being properly installed, maintained, and inspected per code.
4. The Maintenance Director will conduct monthly inspections on fire extinguishers. Results of the inspections will be reviewed at the monthly QAPI meeting.
K0355 · Harborview Rehabilitation and Care Center at Doylestown (PA)
Surveyed 10/20/2025 · Spot-checks: monthly for 4 weeks
1. Maintenance staff replaced the light indicator for the fire extinguisher cabinet near resident room and verified all extinguishers are functional and properly identified. 2. Maintenance…
View Full Plan Text
K0355 Correction Date: 11/26/2025
1. Maintenance staff replaced the light indicator for the fire extinguisher cabinet near resident room and verified all extinguishers are functional and properly identified.
2. Maintenance staff were re-educated on monthly extinguisher inspections and documenting findings.
3. Maintenance Director/designee will conduct audits of extinguisher documentation monthly x 3.
4. All results will be reported to the QAPI Committee.
K0355 · Normandie Ridge (PA)
Surveyed 09/11/2025 · Spot-checks: monthly for 4 weeks
1. The unsecured fire extinguisher was removed off the floor from the nurse's station. The fire extinguisher was taken out of service. 2. Staff will be educated on the proper placement of fire…
View Full Plan Text
K0355 Correction Date: 09/22/2025
1. The unsecured fire extinguisher was removed off the floor from the nurse's station. The fire extinguisher was taken out of service.
2. Staff will be educated on the proper placement of fire extinguishers into hangers or notification to maintenance if unable to hang appropriately. The Facilities Director/designee will audit one time per week for three months to ensure all fire extinguishers are secured appropriately within the building. Audits will continue monthly as part of monthly fire extinguisher checks.
3. Audits will be reported at the QAPI meeting monthly for further follow up and review.
K0355 · Bethlehem South Skilled Nursing and Rehabilitation Center (PA)
Surveyed 09/08/2025 · Spot-checks: monthly for 4 weeks
1) Immediate Corrective Action: a. Maintenance staff were re-educated on extinguisher locations. b. A facility-wide check confirmed all extinguishers were present and accessible.M…
View Full Plan Text
K0355 Correction Date: 09/21/2025
1) Immediate Corrective Action: a. Maintenance staff were re-educated on extinguisher locations. b. A facility-wide check confirmed all extinguishers were present and accessible.M 2)Identification of Other Residents and Corrective Action: a. All residents could be impacted if extinguishers are not inspected properly. b. The facility conducted a complete audit to confirm compliance with monthly checks. 3)Systemic Changes/Implemented Measures to Prevent Reoccurrence: a. All maintenance staff were retrained on extinguisher locations and monthly inspection requirements. b. Cross-checks after departmental inspections were implemented to verify proper documentation. c. Quality assurance rounds now include verification that extinguishers are receiving monthly inspections. 4)Monitoring Corrective Measures & Quality Assurance: a. The maintenance supervisor will complete monthly audits of extinguisher inspections. b. Results will be reported to QAPI for oversight and corrective action if needed.
K0355 · Centennial Healthcare and Rehabilitation Center (PA)
Surveyed 08/18/2025 · Spot-checks: monthly for 4 weeks
A certification is on file for the technician who performed annual portable fire extinguisher test All areas have the potential to be affected. Maintenance staff will be educated ensuring that…
View Full Plan Text
K0355 Correction Date: 10/01/2025
A certification is on file for the technician who performed annual portable fire extinguisher test All areas have the potential to be affected. Maintenance staff will be educated ensuring that fire extinguishers are maintained. Random audits will be conducted by the maintenance director or designee Monthly x2 with reports to QAPI to ensure that fire extinguishers are maintained
K0355 · Jewel Healthcare and Rehabilitation Center (PA)
Surveyed 08/14/2025 · Spot-checks: weekly for 4 weeks
1. Trash bag on the Fire extinguisher in kitchen was removed. 2. Maintenance director and or designee will conduct random audits ensuring Fire extinguishers aren't blocked from view. 3.…
View Full Plan Text
K0355 Correction Date: 09/25/2025
1. Trash bag on the Fire extinguisher in kitchen was removed.
2. Maintenance director and or designee will conduct random audits ensuring Fire extinguishers aren't blocked from view.
3. Maintenance director and or designee will educate staff on not blocking Fire extinguishers from view.
4. Maintenance director and or designee will conduct random weekly audits then monthly x3 ensuring Fire extinguishers aren't blocked from view. Findings to be discussed in qapi
K0355 · Homeland Center (PA)
Surveyed 08/05/2025 · Spot-checks: weekly for 4 weeks
Preparation and submission of this Plan of Correction is required by State and Federal law. This plan does not constitute an admission for purposes of general liability, professional…
View Full Plan Text
K0355 Correction Date: 09/22/2025
Preparation and submission of this Plan of Correction is required by State and Federal law. This plan does not constitute an admission for purposes of general liability, professional malpractice, or any other court proceedings. Homeland Center appreciates the efforts of the state survey team to serve the best interest of Homeland Center Residents. Observation 1 was corrected immediately by removing the ladder, and a chair obstructing fire extinguisher. Maintenance employee directly associated to the ladder not being removed will receive in-service education for complete understanding of not obstructing portable fire extinguishers with any item, and correct placement of a ladder when work associated is completed. All staff will receive additional in-service education for complete understanding of not obstructing portable fire extinguishers, with any item, including a chair. Quality Assurance Performance Improvement (QAPI) Performance Improvement Plan will be created. The Director of Quality Assurance Performance Improvement, or designee, will be responsible for on-going quality assurance to ensure no items are placed obstructing the location of Observation 1, and all locations where fire extinguishers reside. The process will be on-going, occur monthly, on a permanent basis with all locations being observed. Results of QAPI Performance Improvement Plan will be presented at the weekly Clinical/QAPI meeting. Further interventions will occur if determined 100% compliance is not achieved. Administrator/NHA will receive results of QAPI Performance Improvement Plan at weekly Clinical/QAPI meeting. The Administrator, Director of Maintenance/Emergency Preparedness/Purchasing and Director of QAPI will be responsible for consistent, on-going compliance.