K0163 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/28/2025 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0163 →

This provider submits the following plan of correction in good faith and to comply with Federal Law. This plan is not an admission of wrongdoing, nor does it reflect agreement with the facts…

View Full Plan Text
K0163 Correction Date: 06/01/2025 This provider submits the following plan of correction in good faith and to comply with Federal Law. This plan is not an admission of wrongdoing, nor does it reflect agreement with the facts and conclusions stated in the statement of deficiencies. It is the practice of the facility to have proper sealing of penetration with approved fire rating. 1. The facility has removed the orange unknown expanding spray foam around the fourth-floor wall penetration and properly sealed it with UL rated fire caulk using proper UL approved "through penetration fire stop system". 2. Maintenance checked other similar penetrations throughout the building and confirmed no other areas contained sealant products that are not approved for healthcare facilities. 3. Education is completed with Maintenance staff to understand how to seal penetrations with proper materials. 4. Every quarter for a year, the Maintenance Director or designee reviews random areas for proper penetration seals. This information will then be entered on a log and will be presented to the QAPI meeting