K0347 · Graduate Post Acute (PA)
Surveyed 08/11/2026 · Spot-checks: weekly for 4 weeks
1. A fire watch was initiated for the fifth-floor Physical Therapy area while the system was impaired. The ceiling assembly was restored, and the affected smoke detectors were properly…
View Full Plan Text
K0347 Correction Date: 09/23/2026
1. A fire watch was initiated for the fifth-floor Physical Therapy area while the system was impaired. The ceiling assembly was restored, and the affected smoke detectors were properly supported, installed, and tested for correct operation on September 23rd.
2. The Maintenance Director/designee inspected all construction areas to ensure smoke detectors were properly installed and working in enclosed rated ceilings. Identified deficiencies were corrected.
3. Maintenance staff and contractors were educated on protecting smoke detection systems during construction and implementing interim fire-safety measures when systems are impaired.
4. The Maintenance Director/designee will audit construction areas weekly until construction is completed. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
K0347 · Quality Life Services - New Castle (PA)
Surveyed 05/27/2026 · Spot-checks: monthly for 3 months
All battery operated smoke detectors have been labeled with install date from install paperwork. Monthly testing has been added to TELs Battery Operated Smoke detector Policy has been obtained…
View Full Plan Text
K0347 Correction Date: 07/14/2026
All battery operated smoke detectors have been labeled with install date from install paperwork. Monthly testing has been added to TELs Battery Operated Smoke detector Policy has been obtained and reviewed Monthly audits for 3 months times 3 will be completed to ensure compliance. Results will be brought to QAPI for review.
K0347 · Concordia of the South Hills (PA)
Surveyed 03/26/2026 · Spot-checks: weekly for 3 months
1. The maintenance employee secured the mounting plate for the smoke detector in the ceramic room on 03/26/2026. The smoke detector is in compliance. 2. The Administrator and or designee will…
View Full Plan Text
K0347 Correction Date: 04/14/2026
1.The maintenance employee secured the mounting plate for the smoke detector in the ceramic room on 03/26/2026. The smoke detector is in compliance.
2. The Administrator and or designee will audit this detector to ensure it is securely attached . If it is found to not be secure, corrective action will be taken immediately. The administrator and or designee will complete audit monitoring the dector's mounting weekly x4 weeks then monthly for 3 months to validate its placement according to the K 0347 regulation.
3. Administrator and or designee will educate Maintenance Staff and Housekeeping/Laundry Staff on the regulation K0347.
K0347 · Abbeyville Skilled Nursing and Rehabilitation Center (PA)
Surveyed 03/17/2026 · Spot-checks: weekly for 4 weeks
1. Education provided to maintenance department related to requirements of K347. Policy has been written and approved by QAPI committee for battery operated smoke detectors including changing…
View Full Plan Text
K0347 Correction Date: 05/13/2026
1. Education provided to maintenance department related to requirements of K347. Policy has been written and approved by QAPI committee for battery operated smoke detectors including changing batteries every 6 months.
2. Audits will be completed weekly x 4 weeks, then monthly x 12 months to ensure inspections and testing (including being audible) occur per new policy.
3. Audits will be presented to QAPI committee until substantial compliance is demonstrated.
4. Date of compliance: 5/13/2026
K0347 · Spring Creek Rehabilitation and Nursing Center (PA)
Surveyed 04/29/2025 · Spot-checks: monthly for 4 weeks
The Maintenance Director/Designee will perform an audible test on the battery-operated smoke detectors on a monthly basis in the McBride resident rooms, 1st floor and maintain documentation in…
View Full Plan Text
K0347 Correction Date: 05/28/2025
The Maintenance Director/Designee will perform an audible test on the battery-operated smoke detectors on a monthly basis in the McBride resident rooms, 1st floor and maintain documentation in the Life Safety Binder. The Nursing Home Administrator will educate the maintenance team to ensure that all battery-operated smoke detectors in residents' rooms are tested monthly for an audible test. The Nursing Home Administrator will educate the maintenance team to ensure that all battery-operated smoke detectors in residents' rooms are tested. Random monthly audits will be done by Nursing Home Administrator/designee monthly to ensure battery-operated smoke detectors are inspected and the inspections are filed in the safety book. Results of the audits will be reviewed/reported to the monthly QAPI committee to determine trends/compliance. QAPI committee will determine the need for continuance of audits.
K0347 · Greenfield Healthcare and Rehabilitation Center (PA)
Surveyed 01/23/2025 · Spot-checks: monthly for 4 months
Monthly testing and battery replacements were completed for the facility battery operated smoke detectors January 30, 2025. Education was provided to the Maintenance Director by the…
View Full Plan Text
K0347 Correction Date: 02/28/2025
Monthly testing and battery replacements were completed for the facility battery operated smoke detectors January 30,
2025. Education was provided to the Maintenance Director by the Administrator on January 24, 2025, regarding the monthly testing and semi-annal battery replacement of the facility battery-operated smoke detectors. An audit will be conducted monthly for 4 months by the Maintenance Director to ensure that the monthly testing and semi-annual battery replacement for the facility battery-operated smoke detectors are completed. The audit will be monitored by the Administrator. Results of the audit will be presented at the quarterly QAPI meeting and recommendations will be implemented.
K0347 · Independence Rehab and Nursing (PA)
Surveyed 09/16/2026 · Spot-checks: weekly for 4 weeks
The Maintenance Director re-installed the ceiling tiles around the linen chute to ensure that the smoke detector will properly activate. The Maintenance Director will inspect the ceiling tiles…
View Full Plan Text
K0347 Correction Date: 10/13/2026
The Maintenance Director re-installed the ceiling tiles around the linen chute to ensure that the smoke detector will properly activate. The Maintenance Director will inspect the ceiling tiles weekly for four weeks to ensure they remain correctly installed. The QAPI Committee will monitor the facility's ongoing compliance with door maintenance and inspection procedures to ensure that corrective actions remain effective and are consistently maintained.
K0347 · Kadima Rehabilitation & Nursing at New Castle (PA)
Surveyed 05/29/2025 · Spot-checks: weekly for 4 weeks
Smoke Detection 1. The Maintenance Director was in the process of scheduling the sensitivity testing of the smoke detectors at the time of the survey. 2. Sensitivity testing was completed on…
View Full Plan Text
K0347 Correction Date: 07/18/2025
K0347: Smoke Detection 1.The Maintenance Director was in the process of scheduling the sensitivity testing of the smoke detectors at the time of the survey. 2.Sensitivity testing was completed on 6/3/2025. 3.The Maintenance Director will review results to the Safety and Quality Assurance and Performance Improvement Committees.