K0355 · Fairlane Gardens Nursing and Rehab at Reading (PA)
Surveyed 07/29/2026 · Spot-checks: weekly for 4 weeks
1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random…
View Full Plan Text
K0355 Correction Date: 09/15/2026
1) Laundry cart has been stored away from the fire extinguisher. 2) Laundry staff will be educated to not block access to any fire extinguishers. 3) Laundry supervisor will conduct random audits weekly x 4 weeks then monthly to ensure fire extinguishers are not blocked. 4) A summary of the audit's findings will be submitted to the QAPI committee for recommendations
K0355 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: weekly for 4 weeks
0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No…
View Full Plan Text
K0355 Correction Date: 08/05/2026
0355: Portable Fire Extinguishers: The facility failed to maintain portable fire extinguisher locality indicating signage, affecting one of seven smoke compartments within the component No residents were affected. All residents have the potential to be affected. Signage to be installed by the Maintenance Director/designee near the Laundry Chemical Room to identify the portable fire extinguisher by 05AUG2026. Maintenance Director/Designee completed an audit of all portable fire extinguishers in the facility on 09JUL2026 to ensure proper identifying signage. On 21JUL2026, NHA educated the Maintenance Director and maintenance department on the importance of maintaining proper identifying signage for portable fire extinguishers per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits weekly x4 weeks then monthly x 2 months to ensure fire extinguisher signage meets the regulatory requirement. Results will be submitted to the quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0355 · Sanatoga Center (PA)
Surveyed 07/01/2026 · Spot-checks: monthly for 4 weeks
The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide…
View Full Plan Text
K0355 Correction Date: 08/11/2026
The deficient portable fire extinguisher was immediately corrected. The fire extinguisher was mounted on the wall following NFPA guidelines The maintenance director completed a facility wide audit of all fire extinguishers to verify they are properly installed, accessible, fully charged, inspected, and hung accordingly. The Maintenance Director/designee was educated on placement of portable fire extinguishers The Maintenance Director/designee will conduct monthly audits of all portable fire extinguishers x 3 months to verify continued compliance. Audit results will be reviewed through QAPI x 3 months
K0355 · Arbor Grove Village (IN)
Surveyed 05/27/2026 · Spot-checks: daily for 4 weeks
1. What corrective action will this alleged deficient practice. Sign was placed on activity room door on 5/28/26 identifying fire extinguisher location in activity room. (See attachment I) 2.…
View Full Plan Text
K0355
Completion Date: 06/25/2026
1. What corrective action will this alleged deficient practice. Sign was placed on activity room door on 5/28/26 identifying fire extinguisher location in activity room. (See attachment I)
2. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action will be taken; All residents could potentially be affected by this alleged deficient practice. Maintenance director in-serviced on 5/28/26 on sign placement on all room doors identifying fire extinguisher location.
3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or designee will use Life safety code/QAPI tool to audit sign placement on all doors identifying fire extinguisher location where applicable.
4. How the corrective action will be monitored to ensure the deficient practice will not monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The Maintenance Director will audit daily (5x week) for 4 weeks, monthly x 6 months, using Life Safety/QAPI Audit tool and thereafter QAPI committee will determine need for further review. The results of these audits will be reviewed by the QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed.
K0355 · Northampton Post Acute (PA)
Surveyed 05/27/2026 · Spot-checks: weekly for 4 weeks
1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1,…
View Full Plan Text
K0355 Correction Date: 06/12/2026
1. The K-Type portable fire extinguisher located in the Dietary department had signage posted stating staff are to employ the ansul system before using the fire extinguishing device on June 1, 2026.
2. Maintenance Director/Designee will conduct weekly random audits for 4 weeks to ensure that signage stating staff are to employ the ansul system before using the fire extinguishing device is present by the K-Type portable fire extinguisher located in the dietary department. Findings of the audits will be reported to the Quality Assurance Performance Improvement (QAPI) Committee for further action planning if required.
K0355 · Chambersburg Skilled Nursing and Rehabilitation Center (PA)
Surveyed 05/18/2026 · Spot-checks: weekly for 2 months
1. and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current. 3. Maintenance department will be educated on the standards of…
View Full Plan Text
K0355 Correction Date: 06/19/2026
1.and2. Maintenance Director has completed monthly inspection of portable fire extinguishers since March 2026 to current.
3. Maintenance department will be educated on the standards of ensuring the facility has completed the monthly inspection of portable fire extinguishers.
4. Maintenance or facility designee will audit the facilities monthly inspection of portable fire extinguishers weekly for 2 months, then every 60 days throughout the year and results of the audit will be reported to the QAPI committee.
K0355 · Cedarbrook Senior Care and Rehabilitation (PA)
Surveyed 04/29/2026 · Spot-checks: monthly for 3 months
1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for…
View Full Plan Text
K0355 Correction Date: 06/09/2026
1. a) D7 portable fire extinguisher indicator light near Resident resident room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee. b) D7 portable fire extinguisher indicator light near Dining Room was replaced. Facility staff will monitor all portable fire extinguisher indicator lights on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
2. The facility's vendor will ensure all portable fire extinguisher will be inspected on a monthly basis. Facility staff will monitor all portable fire extinguishers on a monthly basis for 3 months. Any non-compliance will be reported at the Quality Assurance Committee.
K0355 · Twinbrook Healthcare and Rehabilitation Center (PA)
Surveyed 04/22/2026 · Spot-checks: monthly for 4 weeks
1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10,…
View Full Plan Text
K0355 Correction Date: 05/08/2026
1. The Maintenance Director immediately inspected fire extinguisher #11 on the main floor, south hallway. The Regional Maintenance Director will re-educate the maintenance staff on NFPA 10, Standard for Portable Fire Extinguishers by May 1,2026.
2. The Maintenance Director or Designee will ensure that all portable fire extinguishers will audit monthly for three months. The Maintenance Director will add the inspection of all portable fire extinguishers to the monthly Preventative Maintenance schedule beginning May 2026.
3. The results of the audits will be reported to the Quality Assurance and Performance Improvement Committee for review at the next monthly meeting.
K0355 · Edenbrook North (PA)
Surveyed 04/15/2026 · Spot-checks: weekly for 4 weeks
The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no…
View Full Plan Text
K0355 Correction Date: 06/02/2026
The fire extinguisher in the Dining room was moved to be less than 60 inches from the floor to the top of the handle. The maintenance director/designee will conduct an audit to ensure that no other fire extinguishes are hung in excess of 60 inches from the floor to the top of the handle. Results of this audit will be reported to the QA steering committee, at which time the committee will determine the need for future audits.
K0355 · Pocopson Home (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to…
View Full Plan Text
K0355 Correction Date: 04/02/2026
1. Portable fire extinguisher deficiencies corrected as follows: a. Maintenance lowered the K-Type fire extinguisher, located within Dietary Overflow, to sixty inches from finished floor to handle. b. The portable fire extinguisher, located within the penthouse level Elevator Machine Room, has been checked. Maintenance will maintain fire extinguisher inspections on a monthly basis. Audit results will be reported to the Quality Improvement/Infection Control Committee. Preparation and submission of this Plan of Correction is required by State and Federal law. This Plan of Correction does not constitute an admission for purposes of general liability, professional malpractice or any other court proceeding
K0355 · Immaculate Mary Center for Rehabilitation & Healthcare (PA)
Surveyed 04/01/2026 · Spot-checks: monthly for 4 weeks
It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency. 1. The Fire Extinguisher in…
View Full Plan Text
K0355 Correction Date: 05/08/2026
It is the practice of the facility to ensure Fire Extinguishers are properly accessible and all residents have the potential to be affected by this deficiency.
1. The Fire Extinguisher in basement hallway has had the obstruction removed to remain accessible for use.
2. All Fire Extinguishers in the facility have been reinspected and are ready for use and the staff inspect the extinguisher areas to prevent this from happening in the future.
3. The Director of Maintenance has completed education with Maintenance staff regarding monitoring Fire Extinguishers by Maintenance Staff.
4. Every quarter for a year the Maintenance Director or designee will check Fire Extinguishers throughout the facility to ensure they are ready for use. This information will then be entered on a log and will be presented by the director to the monthly QAPI meeting for one year.
K0355 · Marywood Heights (PA)
Surveyed 03/10/2026 · Spot-checks: monthly for 4 weeks
Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to…
View Full Plan Text
K0355 Correction Date: 03/31/2026
Portable fire extinguisher located in the Elevator Machine room has replaced with one that is inspected up to date. Maintenance Director or designee will complete monthly audits and submit to QAPI committee to ensure portable fire extinguishers are inspected.
K0355 · Embassy of Hearthside (PA)
Surveyed 02/09/2026 · Spot-checks: monthly for 4 weeks
Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS.…
View Full Plan Text
K0355 Correction Date: 03/30/2026
Extinguisher in first floor soiled laundry area was inspected and tagged. Monthly inspection of fire extinguishers is scheduled and monitored via the preventive maintenance system, TELS. Maintenance will continue to monitor and report findings to monthly QAPI meetings.
K0355 · Liberty Pointe Rehabilitation and Healthcare Center (PA)
Surveyed 01/20/2026 · Spot-checks: weekly for 4 weeks
Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to…
View Full Plan Text
K0355 Correction Date: 02/23/2026
Certification of the fire extinguisher inspector was obtained. Maintenance to be educated on the inspector certification requirements. Administrator to monitor & findings will be brought to the QAPI committee.
K0355 · Hickory Creek at Peru (IN)
Surveyed 01/15/2026 · Spot-checks: monthly for 4 weeks
It is the intent of this facility to be accomplished for those residents found to have been affected by the alleged deficient practice. All residents have the potential to be affected, The…
View Full Plan Text
K0355
Completion Date: 01/30/2026
It is the intent of this facility to be accomplished for those residents found to have been affected by the alleged deficient practice. All residents have the potential to be affected, The fire extinguisher map on our facility floor plan has been updated to reflect all fire extinguishers available for facility. The fire extinguisher outside the kitchen door way has been inspected and labeled appropriately. How will you identify other residents having the potential to be affected by the same alleged deficient practice and what corrective action will be taken. All residents have the potential to be affected, The fire extinguisher map on our facility floor plan has been updated to reflect all fire extinguishers available for facility. Facility confirmed location of all fire extinguishers. All fire extinguishers were checked by the Maintenance Director to ensure they were inspected and properly labeled. What measures will be put into place or what systemic changes you will make to facility floor plan. Our fire extinguisher locations have been added to our Preventative Maintenance Program. Maintenance Director will round each month to ensure fire extinguishers were inspected and properly labeled. How the corrective action(s) will be monitored to ensure the alleged deficient practice will not recur, i.e., what quality assurance program will be put into place. All facility fire extinguishers will be inspected and documented monthly in our Preventative Maintenance Program, which will be conducted by our Maintenance Director. These inspections will be documented and reviewed for compliance during our monthly Safety Committee Meeting and our Quality Assurance Committee Meeting. If any fire extinguisher inspections are missing, the Safety Committee and Quality Assurance Committee will submit action plans for compliance.