K0521 · Hilltop Heights Health & Rehab Center (PA)
Surveyed 09/09/2026 · Spot-checks: weekly for 4 weeks
Portable air conditioning units immediately taken down and removed on date of survey. No portable units remained in the facility and they were no longer needed due to facility's internal air…
View Full Plan Text
K0521 Correction Date: 09/21/2026
Portable air conditioning units immediately taken down and removed on date of survey. No portable units remained in the facility and they were no longer needed due to facility's internal air conditioning system functioning at that point. Maintenance director educated by nursing home administrator/designee that air conditioners cannot be vented into the corridor space above the ceiling.
K0521 · Graduate Post Acute (PA)
Surveyed 08/11/2026 · Spot-checks: monthly for 4 weeks
1. The portable air-conditioning unit that was improperly vented above the suspended ceiling in the basement laundry was removed from service. 2. The Maintenance Director/designee inspected…
View Full Plan Text
K0521 Correction Date: 09/23/2026
1. The portable air-conditioning unit that was improperly vented above the suspended ceiling in the basement laundry was removed from service.
2. The Maintenance Director/designee inspected the facility for other portable HVAC units that were improperly installed or vented. Identified concerns were corrected.
3. Maintenance staff were educated on properly installing and venting portable HVAC equipment according to manufacturer instructions and applicable Life Safety requirements.
4. The Maintenance Director/designee will audit the facility for improperly installed or vented portable HVAC equipment monthly for three months. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
K0521 · Delaware Valley Veterans' Home (PA)
Surveyed 07/13/2026 · Spot-checks: weekly for 4 weeks
The approved regulatory guidelines for having dampers inspected every 4 years will be followed. The vendor, Berkshire Systems, Inc., was scheduled on 07/15/2026 to come out to the facility on…
View Full Plan Text
K0521 Correction Date: 09/11/2026
The approved regulatory guidelines for having dampers inspected every 4 years will be followed. The vendor, Berkshire Systems, Inc., was scheduled on 07/15/2026 to come out to the facility on Thursday, 07/23/2026, to replace the old damper and install a new damper and duct access door. This was completed and an access panel will also be added to the ceiling to make the damper accessible. Documentation of the noted actions will be obtained and maintained by the Facility Grounds Director in the Life Safety binder following completion of the installation. The Facility Grounds Director and Maintenance Supervisor completed refresher training on NFPA 80 and NFPA 90A damper requirements, with focus on maintaining accessible access panels. All future damper inspection reports will be reviewed within 72 hours of receipt, and any deficient practice will be assigned a due date, contractor confirmation and required documentation follow up. The Facility Grounds Director will review damper status quarterly until all repairs are complete, then semi-annually thereafter. Report from the Safety Committee chairs will be reviewed at the Quality Assurance Performance Improvement meeting and the Quality Assessment and Assurance (QAA)Committee will determine the need for additional audits/interventions for ongoing compliance.
K0521 · Cliveden Nursing and Rehabilitation Center (PA)
Surveyed 06/22/2026 · Spot-checks: weekly for 4 weeks
All HVACs will be properly vented to outside. Any HVAC that cannot be properly vented to outside will be removed. - Maintenance team conducted a tour of facility and there were no additional…
View Full Plan Text
K0521 Correction Date: 08/10/2026
- All HVACs will be properly vented to outside. Any HVAC that cannot be properly vented to outside will be removed. - Maintenance team conducted a tour of facility and there were no additional HVACs installed improperly. - administrator or designee will In-service the maintenance team on the importance of insuring all HVACs are properly ducted - Maintenance Director and/or team will conduct facility rounds weekly x 4 weeks to ensure compliance in all areas. - Results will be reported in monthly QAPI
K0521 · Yorkview Nursing and Rehabilitation (PA)
Surveyed 06/09/2026 · Spot-checks: monthly for 4 weeks
Development and/or execution of this plan of correction does not constitute admission or agreement by this provider of the truth in the statement of deficiency. This plan of correction is…
View Full Plan Text
K0521 Correction Date: 07/24/2026
Development and/or execution of this plan of correction does not constitute admission or agreement by this provider of the truth in the statement of deficiency. This plan of correction is prepared and/or executed by provision of Federal or State Law.
1. The facility fire dampers have been inspected by 7/15/26.
2. The Maintenance Director updated the due date in the task list in the maintenance software to ensure that the fire dampers are inspected within 4 years.
3. The Maintenance Department will be educated by NHA that the scheduling of various facility inspections are to be completed per regulations. These inspections will be added to the task items in the maintenance software to ensure that they flag for completion according to established time frames.
4. NHA/Designee will review the life safety book annually to confirm the latest fire damper report is present and any deficiencies have been addressed. NHA/Designee will report on findings at the monthly Quality Assurance and Performance Improvement Committee to address further action planning or the need for further review.
5. Date of compliance: 7/24/26
K0521 · Walnut Creek Nursing and Rehab (PA)
Surveyed 05/20/2026 · Spot-checks: daily for 4 weeks
Facility Maintenance Director has been in contact with vendors to have fire/smoke damper access panel options quoted. Facility Maintenance Director completes daily fire alarm system panel…
View Full Plan Text
K0521 Correction Date: 07/16/2026
Facility Maintenance Director has been in contact with vendors to have fire/smoke damper access panel options quoted. Facility Maintenance Director completes daily fire alarm system panel checks to ensure system functionality. Facility Maintenance Director will ensure fire/smoke damper accesses are quoted, and a purchase order has been completed, down payment processed for work to be started with a timeline available for completion. Maintenance Director will conduct weekly Audits of the fire alarm panel for trouble signals for twelve weeks to ensure compliance. The results of these audits will be reviewed by the facility quality assurance and process improvement committee until substantial compliance is achieved.
K0521 · The Ball Pavilion (PA)
Surveyed 03/31/2026 · Spot-checks: weekly for 4 weeks
The three fire/smoke dampers noted as deficient on the facility's 3/31 inspection were repaired and brought into compliance as of April 6, 2026. Repairs were completed by Swartz, and…
View Full Plan Text
K0521 Correction Date: 04/09/2026
The three fire/smoke dampers noted as deficient on the facility's 3/31 inspection were repaired and brought into compliance as of April 6,
2026. Repairs were completed by Swartz, and documentation verifying completion was obtained by the Maintenance Director and submitted to the Administrator. The facility will continue routine maintenance and inspection of HVAC systems and fire/smoke dampers in accordance with NFPA 101 and facility preventive maintenance schedules to ensure ongoing compliance.
K0521 · York North Skilled Nursing and Rehabilitation Center (PA)
Surveyed 03/12/2026 · Spot-checks: weekly for 4 weeks
1. Unable to retroactively provide the 4-year fire damper maintenance and exercise completion report.The 4-year fire damper inspection and maintenance is scheduled to be performed on April 7,…
View Full Plan Text
K0521 Correction Date: 03/31/2026
1. Unable to retroactively provide the 4-year fire damper maintenance and exercise completion report.The 4-year fire damper inspection and maintenance is scheduled to be performed on April 7, 2026.
2. Audit of required 4-year fire damper maintenance and exercise completion report completed to determine if any additional reports were missing.
3. Education to be completed with Maintenance Director and Maintenance Assistant related to ensuring the 4-year fire damper maintenance and exercise completion report is completed timely.
4. Maintenance Director/Designee will conduct semi-annual audits x 3 quarters to ensure facility s4-year fire damper maintenance and exercise is performed timely.Results will be forwarded to the QAPI committee to determine the need for future follow up/monitoring.
K0521 · Onyx Nursing & Rehabilitation (PA)
Surveyed 03/11/2026 · Spot-checks: weekly for 4 weeks
1. Maintenance staff removed portable air conditioner from Nursing station 2. NHA/designee conducted audit to ensure no other portable air conditioners are venting into ceiling incorrectly. No…
View Full Plan Text
K0521 Correction Date: 04/08/2026
Preparation and submission of this Plan of Correction does not constitute an admission or agreement with the facts alleged or conclusions stated in the Statement of Deficiencies. This Plan of Correction is submitted solely because it is required by Federal and State regulations.
1. Maintenance staff removed portable air conditioner from Nursing station
2. NHA/designee conducted audit to ensure no other portable air conditioners are venting into ceiling incorrectly. No other issues identified.
3. NHA/ Designee educated maintenance staff on requirements to maintain HVAC system and ensure proper venting of portable Acs
4. NHA/designee Will audit facility weekly x 4 then monthly x2, to ensure all portable ACs are vented properly. results will be brought to QAPI for further evaluations and recommendations
K0521 · Kadima Rehabilitation & Nursing at Washington (PA)
Surveyed 01/20/2026 · Spot-checks: weekly for 4 weeks
Based on documentation review and interview, it has been determined that the facility failed to ensure fire and smoke dampers were visually inspected and tested every four years.…
View Full Plan Text
K0521 Correction Date: 02/12/2026
-Based on documentation review and interview, it has been determined that the facility failed to ensure fire and smoke dampers were visually inspected and tested every four years. -Communication has been made with Mongiovi & Sons Fire Services about properly inspecting the fire dampers and it will be scheduled as soon as they can do it. - The Maintenance Director will be re-educated by the Licensed Administrator on the requirements and facility policy to ensure this testing is completed. -The Maintenance Director or designee will review quarterly to ensure completion of the plan of correction and report findings to the QA to ensure regulatory compliance.
K0521 · Fairview Rehab and Care Center (PA)
Surveyed 01/13/2026 · Spot-checks: weekly for 4 weeks
4-year smoke damper inspection obtained and was done on 3.31.2025 and passed inspection. Maintenance educated on the four year need and requirement by Regional Maintenance Director.…
View Full Plan Text
K0521 Correction Date: 03/03/2026
K0521 4-year smoke damper inspection obtained and was done on 3.31.2025 and passed inspection. Maintenance educated on the four year need and requirement by Regional Maintenance Director. Maintenance to present update at QAPI
K0521 · Graduate Post Acute (PA)
Surveyed 11/24/2025 · Spot-checks: monthly for 3 weeks
Maintenance will have fire/smoke damper installed in oxygen room, vendor to come out on 12/14 to asses. A TLW may be requested. Maintenance will remove portable AC units in the kitchen,…
View Full Plan Text
K0521 Correction Date: 01/15/2026
Maintenance will have fire/smoke damper installed in oxygen room, vendor to come out on 12/14 to asses. A TLW may be requested. Maintenance will remove portable AC units in the kitchen, resident room, and 2nd floor nursing station Maintenance director will ensure portable AC units are not in the center. NHA/Designee will in-service maintenance director on usage of AC portable units NHA/Designee will audit center to ensure portable AC units are not being utilized. Audits will be completed three times a week for 3 weeks and 2 times monthly for 2 months. Audits will be reviewed by the QAPI committee during Quality Assurance meetings, and any variances will be addressed.
K0521 · Independence Rehab and Nursing (PA)
Surveyed 11/24/2025 · Spot-checks: weekly for 4 weeks
1. The Maintenance Director has contacted a vendor to conduct a Smoke/Fire Damper inspection. Documentation will be available upon completion of the inspection. 2. On 9/22/2025 the Maintenance…
View Full Plan Text
K0521 Correction Date: 12/29/2025
1. The Maintenance Director has contacted a vendor to conduct a Smoke/Fire Damper inspection. Documentation will be available upon completion of the inspection.
2. On 9/22/2025 the Maintenance Director reviewed documentation to verify that all other inspections for the HVAC system were current.
3. On 10/2/2025the NHA educated the maintenance team on maintaining and inspecting the HVAC system.
4. The Maintenance Director and/or designee will conduct audits weekly for 4 weeks of HVAC systems inspections and documentation are current. Results of the audits will be reviewed at the QAPI meeting held monthly.
K0521 · Monroeville Post Acute (PA)
Surveyed 11/19/2025 · Spot-checks: monthly for 4 weeks
1. Paperwork was located. 2. Maintenance Director educated on K0521 and the need for immediate testing and inspection of the facility smoke dampers. 3. Maintenance to conduct monthly audit of…
View Full Plan Text
K0521 Correction Date: 12/03/2025
1. Paperwork was located.
2. Maintenance Director educated on K0521 and the need for immediate testing and inspection of the facility smoke dampers.
3. Maintenance to conduct monthly audit of preventative maintenance to fire safety system and report to safety committee and QAPI.
K0521 · Harborview Rehabilitation and Care Center at Doylestown (PA)
Surveyed 10/20/2025 · Spot-checks: monthly for 4 weeks
1- Facility contacted the HVAC vendor to schedule repair and testing of 31 failed fire dampers. 2. Maintenance staff will be re-educated on the 6-year inspection requirement for dampers and…
View Full Plan Text
K0521 Correction Date: 11/26/2025
1- Facility contacted the HVAC vendor to schedule repair and testing of 31 failed fire dampers.
2. Maintenance staff will be re-educated on the 6-year inspection requirement for dampers and maintaining documentation.
3. Maintenance Director/Designee will conduct audits of damper inspection records monthly x 2.
4. Results will be reported to the QAPI Committee.