Corrective Action for the Finding: The facility reviewed the weekly exercising documentation cannot be retroactively completed. Any required generator exercising, testing, inspection,…
Past Winning Plans
Real state-approved Plans of Correction and their spot-check schedules.
K0918 · Majestic Care of McCordsville (IN)
Surveyed 08/11/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection
Use K0918 →
K0918
Completion Date: 09/30/2026
K0918 Corrective Action for the Finding: The facility reviewed the weekly exercising documentation cannot be retroactively completed. Any required generator exercising, testing, inspection, maintenance, or documentation that was non-compliant was reviewed, along with identifying corrective steps to maintain full compliance moving forward. Identification of Other Residents/Areas Potentially affected: The facility recognizes that a deficiency involving the generator and related essential electrical system components may potentially affect all residents, staff, and visitors during a power interruption or emergency. The facility therefore reviewed its exercise and testing schedule and documentation process to ensure compliance with this mandatory requirement. Systemic Correction: Tutorial with the Maintenance Director regarding documentation for monthly generator and essential testing results, generator logs, and other applicable records will be maintained in the facility's Life Safety/ Generator records and in TELS. The Maintenance Director will provide monthly testing of the generator starting battery before 9/30/2026. The Maintenance Director will work with Generator Systems to complete the 3-year, 4-hour testing on or before 9/30/2026. Monitoring: The QAPI Committee will monitor the monthly generator battery testing X 6 months to ensure we are in compliance with monthly testing. The QAPI Committee will review the 3-year, 4-hour generator testing yearly in January to schedule Generator Systems for the 3-year, 4-hour test when needed. The ED/Designee will oversee.
K0918 · Richland Bean Blossom Health Care Center (IN)
Surveyed 04/27/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection
Use K0918 →
A maintenance records review was conducted for weekly generator inspections. All residents residing in the facility have the potential to be affected by a deficiency in this practice. The TELS…
View Full Plan Text
K0918
Completion Date: 05/30/2026
K0918 A maintenance records review was conducted for weekly generator inspections. All residents residing in the facility have the potential to be affected by a deficiency in this practice. The TELS monitoring system will be utilized for monitoring and documentation of weekly generator inspections. Maintenance Director and Maintenance Assistant were re-educated on required compliance for weekly generator testing. Audits for monitoring weekly generator inspections will be conducted by the Executive Director or designee monthly x 6 months or until 100% compliance is achieved. Results of these audits will be presented to the QA committee, and any recommendations for changes or updates by the QA committee will be put into place as indicated. These systemic changes will be
K0918 · Hickory Creek at Peru (IN)
Surveyed 01/15/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection
Use K0918 →
Weekly generator testing has remained ongoing. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action(s) will be…
View Full Plan Text
K0918
Completion Date: 02/15/2026
What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice: Weekly generator testing has remained ongoing. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action(s) will be taken: What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur: We have continued with our weekly generator testing. We have added to our Preventative Maintenance Program monthly conductance testing for our sealed generator batteries. How the corrective action(s) will be monitored to ensure the deficient practice will not recur: Weekly generator testing will continue and completed per weekly TELS schedule. Monthly generator conductance testing will be completed monthly. Documentation will be completed for compliance. Testing compliance will be reviewed during our monthly Safety Meetings and Quality Assurance Meetings. If and monthly conductance test for our emergency generator is missing, the Safety and Quality Assurance Committees will complete an action plan for compliance.
K0918 · Brickyard Healthcare - Twelfth Street Care Center (IN)
Surveyed 12/09/2025 · Spot-checks: monthly for 4 weeks
✓ Passed Re-Inspection
Use K0918 →
The battery conductivity testing equipment has been purchased and will be completed monthly. The alleged deficient practice could potentially affect all residents. A monthly task was added to…
View Full Plan Text
K0918
Completion Date: 02/03/2026
The battery conductivity testing equipment has been purchased and will be completed monthly. The alleged deficient practice could potentially affect all residents. A monthly task was added to tels to include Battery specific gravity or (conductivity testing on maintenance free batteries) Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues. by the alleged deficient practice. A monthly task has been added to TELS instructing while inspecting the facility make sure no electrical power strips are dangling from the outlet. Ensure power strips in resident rooms are UL60601 or UL1363A (these will have green dots, but green dots do not always mean they are the proper UL listing) Ensure that only resident medical equipmen OR resident personal equipment are plugged into the power strips and are not mixed together. Make sure no high draw electrical devices are plugged into the power strips such as refrigerators, coffee pots, or microwaves. Coffee pots and microwaves are not allowed in resident rooms. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues. Check oxygen rooms to ensure there is ample room to enter and close the door for the nurses to complete transfilling as per life safety regulations. Oxygen concentrators and other medical devices should not be stored in this room. Flammables should not be stored in the O2 room. Cylinders should be seperated accurately under the empty or the full sign. The fan should be working properly to exhaust to the outside. A slider on the outside of the door should be present to denote open or in use. Gloves, gown, and face shield should be present. Door should be fire rated and inspected annually. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues. Director (X6) DATE12/22/2025