K0761 · Arbor Grove Village (IN)
Surveyed 05/27/2026 · Spot-checks: daily for 4 weeks
✓ Passed Re-Inspection
Use K0761 →
1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; Some residents could potentially 2. How other residents having the…
View Full Plan Text
K0761
Completion Date: 06/25/2026
1. What corrective action will be accomplished for those residents found to have been affected by the deficient practice; Some residents could potentially
2. How other residents having the potential to be affected by the same deficient practice will be identified and what corrective action will be taken; Some residents could potentially be affected by this alleged deficient practice. Maintenance director in-serviced on 5/28/26 on conducting annual fire door testing to 400 hall door, 200 hall door and Oxygen Transfilling room door and include on report.
3. What measures will be put into place and what systemic changes will be made to ensure that the deficient practice does not recur; Maintenance director or designee will use Life safety code/QAPI tool to audit annual fire door testing to 400 hall door, 200 hall door and Oxygen Transfilling room door and include on report. Maintenance Director or designee will complete ongoing monitoring via QAPI program with meetings held bi-monthly and is overseen by the Executive Director. The Maintenance Director will audit daily (5x week) for 4 weeks, monthly x 6 months, using Life Safety/QAPI Audit tool and thereafter QAPI committee will determine need for further review. The results of these audits will be reviewed by the QAPI committee, if threshold of 100% is not achieved an action plan will be revised/completed.