K0923 · Graduate Post Acute (PA)
Surveyed 08/11/2026 · Spot-checks: monthly for 4 weeks
1. The freestanding oxygen cylinder identified in the ground-floor Dialysis area was properly secured. 2. The Maintenance Director/designee inspected all resident-care and oxygen-storage areas…
View Full Plan Text
K0923 Correction Date: 09/23/2026
1. The freestanding oxygen cylinder identified in the ground-floor Dialysis area was properly secured.
2. The Maintenance Director/designee inspected all resident-care and oxygen-storage areas for unsecured or improperly stored cylinders. Identified concerns were immediately corrected.
3. Dialysis staff and applicable facility staff were educated on safely handling and storing oxygen cylinders, including the requirement that all cylinders remain properly secured.
4. The Maintenance Director/designee will audit oxygen-cylinder storage monthly for three months. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
K0923 · Asbury Health Center (PA)
Surveyed 08/10/2026 · Spot-checks: weekly for 4 weeks
The oxygen tanks identified were returned to proper storage. The other areas of facility were audited for improperly stored oxygen tanks and none identified. NHA or designee will educate…
View Full Plan Text
K0923 Correction Date: 09/16/2026
The oxygen tanks identified were returned to proper storage. The other areas of facility were audited for improperly stored oxygen tanks and none identified. NHA or designee will educate maintenance director on oxygen storage and routine inspections. Maintenance director or designee will audit oxygen storage for compliance weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
K0923 · Markley Rehabilitation and Healthcare Center (PA)
Surveyed 07/23/2026 · Spot-checks: weekly for 4 weeks
The oxygen tank in resident resident room was removed. Maintenance staff conducted an audit of resident rooms, and no additional freestanding oxygen tanks were observed. NHA/Maintenance…
View Full Plan Text
K0923 Correction Date: 08/26/2026
The oxygen tank in resident resident room was removed. Maintenance staff conducted an audit of resident rooms, and no additional freestanding oxygen tanks were observed. NHA/Maintenance Director/Designee will in-service staff on the regulations regarding securing oxygen tanks while in resident rooms. The Maintenance Director/Designee will conduct an audit on random resident rooms once a week for 4 weeks, then once a month for 2 months to ensure that there are no freestanding oxygen tanks. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendations needed.
K0923 · Manchester Commons of Presbyterian Seniorcare (PA)
Surveyed 07/22/2026 · Spot-checks: weekly for 4 weeks
1) The oxygen storage room will be physically labeled and color coded to assure team members know how/where to appropriately store the E tanks. Signage was placed informing team once the seal…
View Full Plan Text
K0923 Correction Date: 09/14/2026
1) The oxygen storage room will be physically labeled and color coded to assure team members know how/where to appropriately store the E tanks. Signage was placed informing team once the seal of an O2 tank is removed it cannot be placed back in the full section no matter how much O2 is left. Signage was also updated to state the total capacity of tanks for the closet is 12. 2) The Oxygen closets will be audited by the Director of Maintenance or designee weekly for one month. This deficient practice and resulting citation will be reviewed with the nursing team at the next department meeting. The citation and audit results will be reviewed at the monthly safety meeting and with the IDT at Quarterly Quality.
K0923 · Providence Point Healthcare Residence (PA)
Surveyed 07/06/2026 · Spot-checks: weekly for 8 weeks
1. Signs were placed on Utility rooms containing Oxygen on 7/6/2026. 2. Utility and Storage Rooms in Skilled Nursing will audited each week for 8 weeks to proper signage is in place if any…
View Full Plan Text
K0923 Correction Date: 07/31/2026
1. Signs were placed on Utility rooms containing Oxygen on 7/6/2026.
2. Utility and Storage Rooms in Skilled Nursing will audited each week for 8 weeks to proper signage is in place if any oxygen is being stored in those rooms.
3. Results of audits will be reported at quarterly QA meetings.
4. EVS Director will be responsible for this plan of correction.
K0923 · Phoebe Allentown Health Care Center (PA)
Surveyed 06/23/2026 · Spot-checks: monthly for 4 weeks
Oxygen tank storage corrected on 06/22/26. Education to staff regarding proper oxygen tank storage and handling of portable gas cylinders will be conducted. Perform monthly rounds for a…
View Full Plan Text
K0923 Correction Date: 08/03/2026
Oxygen tank storage corrected on 06/22/26. Education to staff regarding proper oxygen tank storage and handling of portable gas cylinders will be conducted. Perform monthly rounds for a quarter to make sure we are compliant and report out on our findings in our monthly QAPI meeting.
K0923 · Cliveden Nursing and Rehabilitation Center (PA)
Surveyed 06/22/2026 · Spot-checks: weekly for 4 weeks
The two unsecured oxygen cylinders have since been secured. - The maintenance team has conducted a full facility wide assessment, and there were no other unsecured oxygen cylinders. - Facility…
View Full Plan Text
K0923 Correction Date: 08/10/2026
- The two unsecured oxygen cylinders have since been secured. - The maintenance team has conducted a full facility wide assessment, and there were no other unsecured oxygen cylinders. - Facility Educator or designee will Inservice staff on the importance of oxygen cylinders being secured and stored in the proper location. - Maintenance Director and/or team will conduct facility rounds weekly x 4 weeks to ensure compliance in all areas. - Results will be reported in monthly QAPI
K0923 · Caring Heart Rehabilitation and Nursing Center (PA)
Surveyed 06/03/2026 · Spot-checks: weekly for 4 weeks
A new self-closer was installed on the fourth-floor oxygen door, "No Smoking Oxygen In Use" signs were posted on the third and second-floor doors, the third-floor dragging door was planed to…
View Full Plan Text
K0923 Correction Date: 07/20/2026
A new self-closer was installed on the fourth-floor oxygen door, "No Smoking Oxygen In Use" signs were posted on the third and second-floor doors, the third-floor dragging door was planed to latch, and full/empty markers were placed in the second-floor room. - The Maintenance Director was re-educated on medical gas storage parameters, signage mandates, self-closing setups, and cylinder segregation. - The Director of Maintenance or designee will audit all oxygen storage rooms weekly x
4. Monthly audits times 3 will continue with results reported to the QA Committee.
K0923 · Pottstown Skilled Nursing and Rehabilitation Center (PA)
Surveyed 06/01/2026 · Spot-checks: weekly for 4 weeks
1. The oxygen cylinders' containment racks have been corrected and are now marked with signage indicating "empty" and "full". 2. To ensure there are no other areas of deficient practice,…
View Full Plan Text
K0923 Correction Date: 07/31/2026
1. The oxygen cylinders' containment racks have been corrected and are now marked with signage indicating "empty" and "full".
2. To ensure there are no other areas of deficient practice, oxygen storage areas will be inspected for compliance with signage requirements.
3. The Maintenance Director and staff have been educated on the regulations and safety requirements for proper signage.
4. To prevent recurrence, the oxygen storage areas will be audited weekly X 4 weeks, bi-weekly X 4 weeks, and monthly X 1 month. The results will be reviewed monthly at QAPI. 5.Date of compliance is July 31, 2026.
K0923 · Woodhaven Health & Rehab Center (PA)
Surveyed 05/28/2026 · Spot-checks: weekly for 4 weeks
Director of Maintenance secured the unsecured oxygen cylinder in the first floor oxygen storage room. To prevent the reoccurrence the Director of Maintenance and Director of Nursing was…
View Full Plan Text
K0923 Correction Date: 07/01/2026
Director of Maintenance secured the unsecured oxygen cylinder in the first floor oxygen storage room. To prevent the reoccurrence the Director of Maintenance and Director of Nursing was educated on properly storing oxygen cylinders. To monitor and maintain on-going compliance the Director of Maintenance/designee will audit the oxygen storage rooms to ensure proper storing of the oxygen cylinders weekly x4 weeks and 1x monthly. Results will be taken to QAPI for review and revision as needed.
K0923 · Premier Washington Rehabilitation and Nursing Center (PA)
Surveyed 04/27/2026 · Spot-checks: weekly for 3 months
1. On April 27, 2026, proper signage for oxygen was placed on the 3 east crash cart room and the 2 east crash cart room. 2. On April 27th, 2026 the Director of Maintenance conducted a…
View Full Plan Text
K0923 Correction Date: 06/08/2026
1. On April 27, 2026, proper signage for oxygen was placed on the 3 east crash cart room and the 2 east crash cart room.
2. On April 27th, 2026 the Director of Maintenance conducted a facility-wide inspection of all oxygen cylinder storage locations and crash cart rooms to verify that required oxygen signage was present and no oxygen cylinders were improperly stored.
3. The maintenance staff were educated to ensure that proper signage for oxygen storage is posted for all rooms where oxygen is stored.
4. The Director of Maintenance or designee will conduct weekly audits x4 weeks and monthly after for 3 months of oxygen storage areas to verify proper signage. Audit findings will be documented and reviewed during the facility's monthly QAPI meetings
K0923 · Twinbrook Healthcare and Rehabilitation Center (PA)
Surveyed 04/22/2026 · Spot-checks: weekly for 4 weeks
1. The Maintenance Assistant removed the empty oxygen cylinders from the east 1 storeroom upon notification. 2. The Director of Nursing or Designee will re-educate the nursing staff on proper…
View Full Plan Text
K0923 Correction Date: 05/08/2026
1. The Maintenance Assistant removed the empty oxygen cylinders from the east 1 storeroom upon notification.
2. The Director of Nursing or Designee will re-educate the nursing staff on proper storage of the oxygen cylinders. The Maintenance Director or Designee will audit the oxygen cylinders weekly for four weeks, then monthly for three months.
3. The results of the audit will be reported to the Quality Assurance and Performance Improvement Committee at the next monthly meeting.
K0923 · Holy Family Home (PA)
Surveyed 04/06/2026 · Spot-checks: monthly for 4 weeks
1. A self-closing device was installed on the oxygen storage room door. 2. Medical gas room inspection was added to the monthly Life Safety checklist.
View Full Plan Text
K0923 Correction Date: 05/13/2026
1. A self-closing device was installed on the oxygen storage room door.
2. Medical gas room inspection was added to the monthly Life Safety checklist.
K0923 · Pine Run Health Center (PA)
Surveyed 03/18/2026 · Spot-checks: weekly for 4 weeks
Plan of Correction 0923 (Gas Equipment Cylinder and Container Storage) 1. On March 18, 2026 it was observed that the 4th floor Central Oxygen Storage room did not have a door closure…
View Full Plan Text
K0923 Correction Date: 05/13/2026
Plan of Correction 0923 (Gas Equipment Cylinder and Container Storage)
1. On March 18, 2026 it was observed that the 4th floor Central Oxygen Storage room did not have a door closure installed. It was also observed that a resident's wheelchair leg rest bag on second floor was equipped with an unsecured oxygen cylinder. Fourth floor Central Oxygen Storage room door closure is now installed and all resident wheelchair leg rest bags assessed and all oxygen cylinders removed.
2. Director of Environmental Services or designee to conduct a full house audit of all oxygen storage rooms to ensure door closures are present in each. DES or Designee to conduct a full house audit of all resident wheelchair leg rest bags to ensure no oxygen cylinders are stored in them.
3. Director of Nursing or designee to re-educate Nursing staff on not securing oxygen tanks in resident wheelchair leg rest bags.
4. Director of Environmental Services or designee to audit 2 random oxygen storage rooms weekly X4 and then monthly X2 to ensure door closures are functioning properly. DES or designee to audit 3 random residents weekly X4 and then monthly X2 to ensure no oxygen cylinders are stored in resident wheelchair leg rest bags. Any concerns will be corrected immediately. Audits will be brought to the Quality Assurance meeting with reviews and recommendations as needed.
5. Date of completion is scheduled for May 13, 2026.
K0923 · Wesley Enhanced Living - Doylestown (PA)
Surveyed 03/16/2026 · Spot-checks: daily for 4 weeks
The facility acquired necessary storage racks and placed appropriate signage on oxygen storage area. The facility developed a written protocol and in serviced staff on proper oxygen storage…
View Full Plan Text
K0923 Correction Date: 05/15/2026
The facility acquired necessary storage racks and placed appropriate signage on oxygen storage area. The facility developed a written protocol and in serviced staff on proper oxygen storage procedures. Daily oxygen storage inspections placed into TELS maintenance program. To be monitored by Director of Facility Operations. Also placed into semi-annual safety surveillance rounds and reported on during Wesley Enhanced Living's safety committee meetings. Also to be reported during quarterly Quality Assurance committee that includes the Executive Director/Nursing Home Administrator, Director of Nursing, and Director of Facility Operations.