K0293 · Forestview (PA)
Surveyed 08/18/2026 · Spot-checks: monthly for 4 weeks
Acclaim Electric will install lit LED exit lights on the generator to be placed above the FountainView Lounge and Woodlands Lounge. The exit lights will be added to the monthly inspection list…
View Full Plan Text
K0293 Correction Date: 10/02/2026
Acclaim Electric will install lit LED exit lights on the generator to be placed above the FountainView Lounge and Woodlands Lounge. The exit lights will be added to the monthly inspection list completed by Maintenance
K0293 · Williamsport Nursing and Rehabilitation (IN)
Surveyed 08/11/2026 · Spot-checks: weekly for 4 weeks
No residents were 1. directly affected by this deficiency due to the location inside the kitchen area. An exit sign was added to the door leading from the kitchen to the receiving area at the…
View Full Plan Text
K0293
Completion Date: 08/28/2026
No residents were 1. directly affected by this deficiency due to the location inside the kitchen area. An exit sign was added to the door leading from the kitchen to the receiving area at the rear of the kitchen.
2. Any resident located in or around the kitchen area could have been affected by this deficiency. An exit sign was added to the door leading from the kitchen to the receiving area at the rear of the kitchen.
3. All-staff will be educated by 8/28/26 on the placement of the exit sign and exit lighting" QAPI tool (see attachment B) to ensure proper functioning ongoing.Any issues will be corrected immediately, and the audit results will be brought to the QAPI meeting ongoing for discussion and/or resolution.
5. This will be completed 8/28/26.
K0293 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: monthly for 4 weeks
0293: Exit signage The facility failed to provide documentation verifying monthly inspections of exit signage had occurred, within the previous twelve months. No residents were identified. All…
View Full Plan Text
K0293 Correction Date: 08/05/2026
0293: Exit signage The facility failed to provide documentation verifying monthly inspections of exit signage had occurred, within the previous twelve months. No residents were identified. All residents have the potential to be affected. Facility wide audit was completed by the Maintenance Director/designee on 09JUL2026 to ensure that all exit signs were operating properly. On 21JUL2026, NHA educated the Maintenance Director on the importance of maintaining documentation per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits monthly x 3 month and then quarterly, to ensure that documentation for exit signage inspection meet the requirement. NHA/Designee to audit Life safety binder with Maintenance Director quarterly to confirm completion of documentation. Results will be submitted to quarterly to the Quality Assurance Performance Improvement Committee for review and recommendations.
K0293 · Caring Heart Rehabilitation and Nursing Center (PA)
Surveyed 06/03/2026 · Spot-checks: weekly for 4 weeks
The damaged exit sign near the first-floor Laundry Room corridor doors was replaced with a new cover assembly. - The Maintenance Director was re-educated on replacing broken directional…
View Full Plan Text
K0293 Correction Date: 07/20/2026
- The damaged exit sign near the first-floor Laundry Room corridor doors was replaced with a new cover assembly. - The Maintenance Director was re-educated on replacing broken directional signage immediately instead of using temporary tape fixes. - The Director of Maintenance or designee will audit exit signs weekly x4. Monthly audits times 3 will continue with results reported to the QA Committee.
K0293 · Chambersburg Skilled Nursing and Rehabilitation Center (PA)
Surveyed 05/18/2026 · Spot-checks: weekly for 2 months
1. and2. Maintenance Director has completed monthly inspection of verifying exit signage and maintaining the illumination of exit signage since April 2026 to current, maintenance director…
View Full Plan Text
K0293 Correction Date: 06/19/2026
1.and2. Maintenance Director has completed monthly inspection of verifying exit signage and maintaining the illumination of exit signage since April 2026 to current, maintenance director fixed exit sign by resident room G13 to illuminate.
3. Maintenance department will be educated on the standards of ensuring the facility has completed the monthly inspection of verifying exit signage and ensuring the exit signage are illuminating.
4. Maintenance or facility designee will audit the facilities monthly inspection of verifying exit signage and exit signage illumination weekly for 2 months, then every 60 days throughout the year and results of the audit will be reported to the QAPI committee.
K0293 · Southmont of Presbyterian Seniorcare (PA)
Surveyed 05/13/2026 · Spot-checks: monthly for 4 weeks
The facility immediately replaced the faulty battery backup exit sign on the second-floor elevator lobby with a new battery backup exit sign. Maintenance Director will reeducate maintenance…
View Full Plan Text
K0293 Correction Date: 06/15/2026
The facility immediately replaced the faulty battery backup exit sign on the second-floor elevator lobby with a new battery backup exit sign. Maintenance Director will reeducate maintenance staff during the monthly exit sign inspection that any exit signs that fail to light up during battery test will be replaced immediately and report his findings to the Maintenance Director. Maintenance Director will audit 3 exit signs once a month for the next three months and report his findings to the QA committee.
K0293 · Champion City Nursing and Rehabilitation Center (PA)
Surveyed 03/30/2026 · Spot-checks: weekly for 4 weeks
Batteries in the 3 exit signs (5 East and 2 East smoke doors, and 2 East Nurse's station) have been replaced. All exit signs will be tested weekly x 3 weeks, monthly foe 12 months. Findings…
View Full Plan Text
K0293 Correction Date: 05/01/2026
Batteries in the 3 exit signs (5 East and 2 East smoke doors, and 2 East Nurse's station) have been replaced. All exit signs will be tested weekly x 3 weeks, monthly foe 12 months. Findings will be reported to QAA for further review and monitoring.
K0293 · Carnegie Park Post Acute (PA)
Surveyed 03/10/2026 · Spot-checks: monthly for 4 weeks
The defective exit sign battery was replaced, and all exit signs were inspected to ensure proper operation. A monthly inspection log was implemented to document required exit sign testing. The…
View Full Plan Text
K0293 Correction Date: 04/27/2026
the defective exit sign battery was replaced, and all exit signs were inspected to ensure proper operation. A monthly inspection log was implemented to document required exit sign testing. The Maintenance Director or designee will monitor compliance by completing and reviewing monthly exit sign inspections to ensure all signs remain functional.
K0293 · New Eastwood Healthcare and Rehabilitation Center (PA)
Surveyed 01/22/2026 · Spot-checks: monthly for 4 weeks
1. New exit signage was placed in two locations on both floors: exit signage directed building occupants from the exit access corridor and through the adjacent Therapy Suite to exit discharge,…
View Full Plan Text
K0293 Correction Date: 02/24/2026
1. New exit signage was placed in two locations on both floors: exit signage directed building occupants from the exit access corridor and through the adjacent Therapy Suite to exit discharge, and on each side of the smoke barrier separation doors.
2. All doors were auditing to ensure there were no identified areas in facility in which needs exit signage
3. The Director of Maintenance or designee will audit monthly to ensure exit signage is places appropriately.
4. The Director of Maintenance or designee will report identified areas of concern through the Quality Assurance process monthly.
K0293 · Care Pavilion Nursing and Rehabilitation Center (PA)
Surveyed 12/15/2025 · Spot-checks: daily for 4 weeks
Correction: All exit signs were inspected and repaired or replaced as necessary. Systemic Changes: Exit sign inspections were added to monthly safety rounds. Monitoring: Maintenance…
View Full Plan Text
K0293 Correction Date: 01/30/2026
Correction: All exit signs were inspected and repaired or replaced as necessary. Systemic Changes: Exit sign inspections were added to monthly safety rounds. Monitoring: Maintenance Director/Designee will round community daily for x 2 weeks, weekly x 2 weeks and monthly x 2 months.
Completion Date: 1/30/26.
K0293 · Monroeville Post Acute (PA)
Surveyed 11/19/2025 · Spot-checks: monthly for 6 months
1. Corrective Action Taken for the Affected Area- Upon identification of the deficient practice, all exit signs and emergency lighting fixtures throughout the facility were immediately…
View Full Plan Text
K0293 Correction Date: 12/03/2025
1. Corrective Action Taken for the Affected Area- Upon identification of the deficient practice, all exit signs and emergency lighting fixtures throughout the facility were immediately inspected on 12/2/2025 by the Maintenance Director. Any device found inoperable was repaired or replaced the same day. Documentation of the inspection and repairs was completed and placed in the Life Safety binder.
2. Because all residents, staff, and visitors could be affected by failure of exit lighting, a facility-wide assessment of all exit signs and emergency lighting fixtures was completed on 12/2/2025. No additional deficiencies were identified outside the initial findings. Any units with non-functioning bulbs, backup batteries, or low-illumination levels were corrected immediately.
3. To ensure ongoing compliance: A written Exit Sign & Emergency Lighting Audit Procedure was developed and added to the facility's Life Safety and Preventative Maintenance (PM) Program. The Maintenance Director has created a monthly audit schedule with checklists documenting: Functionality of each exit sign, Battery backup operation, Illumination level, Unobstructed visibility. A quarterly 90-minute emergency lighting test was added to the PM calendar in accordance with NFPA 101 and NFPA 70.
4. All maintenance staff were educated on the updated auditing procedures on 12/2/2025.
5. Monitoring and Quality Assurance The Maintenance Director will complete and document monthly exit lighting audits using the standardized checklist. Results will be reviewed by the Administrator and Safety Committee each month. Deficiencies will be corrected within 24 hours, and corrective actions will be logged. Continuous compliance will be monitored under the facility's QAPI Performance Improvement Plan. This monitoring process will continue for 6 months, after which the Safety Committee will determine if the process requires extension.
6. The facility will achieve full compliance by 12/5/2025.
K0293 · Jewel Healthcare and Rehabilitation Center (PA)
Surveyed 08/14/2025 · Spot-checks: weekly for 4 weeks
1. Exit sign on basement level was fixed and is illuminating 2. Maintenance director and or designee will conduct random audits ensuring exit signs are illuminated. 3. Maintenance director and…
View Full Plan Text
K0293 Correction Date: 08/25/2025
1. Exit sign on basement level was fixed and is illuminating
2. Maintenance director and or designee will conduct random audits ensuring exit signs are illuminated.
3. Maintenance director and or designee will be educated on ensuring exit signs are illuminated.
4. Maintenance director and or designee will conduct weekly audits x4 , then monthly x3 ensuring exit signs are illuminated. Findings to be discussed in qapi
K0293 · Aventura at Pembrooke (PA)
Surveyed 08/05/2025 · Spot-checks: weekly for 4 weeks
The facility failed to maintain exit signs to be continuously illuminated, on one of four floors. No residents were identified. All residents have the potential to be affected. The exit sign,…
View Full Plan Text
K0293 Correction Date: 09/12/2025
The facility failed to maintain exit signs to be continuously illuminated, on one of four floors. No residents were identified. All residents have the potential to be affected. The exit sign, above the door leading to grade from the stair tower near the Elevator Lobby, was repaired to ensure it is continuously illuminated as required. Facility wide audit was completed by the Maintenance Director to ensure that there are no other open areas in walls. The Maintenance Director was educated on the requirement by the Administrator. The Maintenance Director/Designee will conduct compliance audits to ensure that exit signs meet the requirement. The audits will be weekly for four weeks, then monthly ongoing thereafter. The administrator will conduct quarterly random audits thereafter to spot check. The results of the audits will be discussed monthly and quarterly by the Quality Assurance and Performance Improvement Committee for the duration of the audit process (3 months). Based on the results of these audits a decision will be made regarding the need for continued submissions and reporting
K0293 · Delaware Valley Veterans' Home (PA)
Surveyed 07/28/2025 · Spot-checks: monthly for 4 weeks
Preparation and submission of this plan of correction is required by state and federal law. This plan of correction does not constitute an admission for purposes of general liability, of…
View Full Plan Text
K0293 Correction Date: 09/22/2025
Preparation and submission of this plan of correction is required by state and federal law. This plan of correction does not constitute an admission for purposes of general liability, of professional malpractice or for purposes of any judicial or administrative proceeding. Missing emergency exit sign on first floor, A-wing dining room rear exit door leading to the courtyard was replaced on 7-31-25. Moving forward inspections of emergency exit signs will be done monthly to confirm signs are in place. The results of the audit will be reviewed at the Quality Assurance & Performance Improvement meetings. The Quality Assurance Committee will determine the need for additional audits/ interventions for ongoing compliance.
K0293 · The Gardens at Camp Hill (PA)
Surveyed 07/21/2025 · Spot-checks: monthly for 4 weeks
Documentation will be completed verifying that signage was visually inspected on a monthly basis. Maintenance Director given an inservice on appropriate documentation to verify exit signage…
View Full Plan Text
K0293 Correction Date: 08/15/2025
Documentation will be completed verifying that signage was visually inspected on a monthly basis. Maintenance Director given an inservice on appropriate documentation to verify exit signage was visually inspected monthly. Random audit will be completed to ensure documentation completed with results to QAPI committee.