K0344 · Caring Heart Rehabilitation and Nursing Center (PA)
Surveyed 06/03/2026 · Spot-checks: weekly for 4 weeks
✓ Passed Re-Inspection Use K0344 →

A new self-closer mechanism was installed on the first-floor Laundry Room magnetic fire door to ensure automatic positive-latching upon alarm. - The Maintenance Director was re-educated on…

View Full Plan Text
K0344 Correction Date: 07/20/2026 - A new self-closer mechanism was installed on the first-floor Laundry Room magnetic fire door to ensure automatic positive-latching upon alarm. - The Maintenance Director was re-educated on inspecting automatic door-closing hardware and maintaining positive latching functions. - The Director of Maintenance or designee will audit magnetic door release functions weekly x4. Monthly audits times 3 will continue with results reported to the QA Committee.
K0344 · Care Pavilion Nursing and Rehabilitation Center (PA)
Surveyed 09/28/2026 · Spot-checks: weekly for 4 weeks
Approved Filing Use K0344 →

0344- Fire Alarm Magnetically held fire door Deficiencies (latching failures) at the following locations: 1). Double Kitchen doors near (employee) locker resident room). Corridor Door 1 West…

View Full Plan Text
K0344 Correction Date: 10/24/2026 0344- Fire Alarm Magnetically held fire door Deficiencies (latching failures) at the following locations: 1). Double Kitchen doors near (employee) locker resident room). Corridor Door 1 West Nurses Station 3). Double doors separation between 3 east/ 3 west Actions taken: Doors were adjusted to allow proper closer into door jam and positive latching was achieved on September 29, 2026 POC: Corridor doors will be Audit/tested by Maintenance Department weekly x 2 weeks and monthly x 2 months. Any findings will be reviewed and discussed in QAPI