K0353 · Concordia at Rp Home (PA)
Surveyed 08/17/2026 · Spot-checks: weekly for 4 weeks
1) Mongovi Fire Service to repair faulty control valve and 2 sprinklery switches on 8/28/26. Workorder on file with NHA. 2) Escutcheon Plates replaced on office area to reported locations.…
View Full Plan Text
K0353 Correction Date: 10/01/2026
1) Mongovi Fire Service to repair faulty control valve and 2 sprinklery switches on 8/28/26. Workorder on file with NHA. 2) Escutcheon Plates replaced on office area to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads. 3) Escutcheon Plates replaced on 3rd Floor nears front stairwell area to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads. 4) Escutcheon Plates replaced on foyer to reported locations. Workers completing ceiling tile work re-educated to requirement of sprinkler heads. 5) All sprinkler head audited to ensure escutcheon places to ensure located in place. 6) Wires removed from the sprinkler line near resident room upon discovery. 7) Supply room on the third floor ceiling tile will be replaced to cover conduit. work order available.
8. Penetration in the electoral equipment room applied to meet requirement. Work order on file with NHA. 9_ QAPI Committee aware of citations and updates
K0353 · Majestic Care of McCordsville (IN)
Surveyed 08/11/2026 · Spot-checks: weekly for 4 weeks
Corrective Action for the Finding: The facility reviewed the deficiency of Sprinkler System - Maintenance and Testing. The water storage tank will need to have temperature tested weekly to…
View Full Plan Text
K0353
Completion Date: 09/30/2026
K353 Corrective Action for the Finding: The facility reviewed the deficiency of Sprinkler System - Maintenance and Testing. The water storage tank will need to have temperature tested weekly to ensure the proper water temperature. The storage tank interior shall be inspected every 3 -yrs for signs of pitting, corrosion, spalling, rot, and other forms of deterioration. Identification of Other Residents/Areas Potentially Affected: All residents, staff and visitors have the potential to be affected but none were identified. Systemic Correction: Pittsburgh Tank & Tower Group will complete an inspection of the tank on or before 9/30/2026. Documentation will be provided in TELS that service has been performed and completed. Monitoring:
K0353 · Graduate Post Acute (PA)
Surveyed 08/11/2026 · Spot-checks: monthly for 4 weeks
1. The required fire-pump run was completed and documented. 2. The Maintenance Director/designee audited the available fire-pump testing records for the previous 12 months. Missing…
View Full Plan Text
K0353 Correction Date: 09/23/2026
1. The required fire-pump run was completed and documented.
2. The Maintenance Director/designee audited the available fire-pump testing records for the previous 12 months. Missing documentation was identified, and the testing calendar was verified.
3. Maintenance staff were educated on the required frequency, duration, documentation, and retention of fire-pump testing records.
4. The Administrator/designee will audit fire-pump testing records monthly for three months. Missed testing or documentation will be immediately addressed. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
K0353 · Asbury Health Center (PA)
Surveyed 08/10/2026 · Spot-checks: weekly for 4 weeks
The automatic sprinkler system will be fixed before POC completion date. NHA or designee will educate maintenance director on sprinkler system requirements and routine inspections. Maintenance…
View Full Plan Text
K0353 Correction Date: 09/16/2026
The automatic sprinkler system will be fixed before POC completion date. NHA or designee will educate maintenance director on sprinkler system requirements and routine inspections. Maintenance director or designee will audit the sprinkler system and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
K0353 · Fairlane Gardens Nursing and Rehab at Reading (PA)
Surveyed 07/29/2026 · Spot-checks: monthly for 4 weeks
1) Sprinkler head missing an escutcheon, in the Emergency Storage was repaired. Sprinkler assembly was below the level of the ceiling above the washer, in the Laundry Room has been repaired.…
View Full Plan Text
K0353 Correction Date: 09/15/2026
1) Sprinkler head missing an escutcheon, in the Emergency Storage was repaired. Sprinkler assembly was below the level of the ceiling above the washer, in the Laundry Room has been repaired. 2) Maintenance director to be educated in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained. 3) NHA/designee will conduct random audits monthly to ensure sprinkler heads and sprinkler assembly is maintained as required. 4) A summary of the audit's findings will be submitted to the QAPI committee for recommendations.
K0353 · John J Kane Regional Center- Ross Township (PA)
Surveyed 07/21/2026 · Spot-checks: daily for 4 weeks
1. The three identified deficient items were corrected. Penetration in W-352 was filled and patched. Missing ceiling tile in W-250 replaced. Damaged escutcheon replaced outside supervisor…
View Full Plan Text
K0353 Correction Date: 08/14/2026
1. The three identified deficient items were corrected. Penetration in W-352 was filled and patched. Missing ceiling tile in W-250 replaced. Damaged escutcheon replaced outside supervisor office.
2. ESM or designee will audit for penetrations and damaged escutcheons throughout facility.
3. Maintenance and Housekeeping staff will be educated on identifying and reporting penetrations and damaged escutcheons.
4. ESM or designee will audit for penetrations and damaged escutcheon's during environmental rounds daily x1 business week, weekly x3 until substantial compliance is achieved.
5. Date of compliance: 8/14/2026
K0353 · John J Kane Regional Center - Glen Hazel (PA)
Surveyed 07/15/2026 · Spot-checks: weekly for 4 weeks
It is the policy of the facility to comply with NFPA 101 Life Safety Code: Sprinkler System-Maintenance and Testing. The facility had the five year obstruction completed on July 24, 2026. The…
View Full Plan Text
K0353 Correction Date: 08/13/2026
It is the policy of the facility to comply with NFPA 101 Life Safety Code: Sprinkler System-Maintenance and Testing. The facility had the five year obstruction completed on July 24,
2026. The boxes stored within 18 inches of a sprinkler head in the supply closet next to resident room were removed. The Environmental Services Manager (ESM) or designee will do routing monitoring to prevent reoccurrence.
K0353 · Centennial Healthcare and Rehabilitation Center (PA)
Surveyed 07/15/2026 · Spot-checks: monthly for 4 weeks
The 5-year internal pipe and valve inspection was completed. Automatic sprinkler system components have the potential to be effected. Maintenance will be educated on maintaining automatic…
View Full Plan Text
K0353 Correction Date: 09/01/2026
The 5-year internal pipe and valve inspection was completed. Automatic sprinkler system components have the potential to be effected. Maintenance will be educated on maintaining automatic sprinkler system components. Random audits will be conducted by the Maintenance or designee to ensure automatic sprinkler system components are maintained Monthly x2 with reports to QAPI
K0353 · Delaware Valley Veterans' Home (PA)
Surveyed 07/13/2026 · Spot-checks: monthly for 4 weeks
Procurement Specialist removed items from the top shelf of the Basement Bulk Storage Room to allow for 18" clearance. Quarterly Basement Environmental Rounds were completed on Monday,…
View Full Plan Text
K0353 Correction Date: 09/11/2026
Procurement Specialist removed items from the top shelf of the Basement Bulk Storage Room to allow for 18" clearance. Quarterly Basement Environmental Rounds were completed on Monday, 07/20/2026, with no obstructions indicated. Facility Grounds Director/Designee will review and assess all storage rooms and clearly mark all walls or shelves appropriately for correct storage height limit. The Procurement specialist was reeducated by the Deputy Commandant related to clearance requirements with a focus on the 18-inch minimum clearance guideline for protected sprinkler spaces. Monthly environmental rounds checklist updated by the Facility Grounds Director/Designee to include verification of all sprinkler areas in storage rooms maintain proper clearance. Audits will be conducted by Procurement Specialist to ensure storage rooms do not contain any items beyond the appropriate height 1x/week for four (4) weeks, then 1x/month. Thereafter, quarterly Basement Environmental Rounds will include completing corrective actions within 7 days. Audit results will be reviewed in the Quality Assurance Performance Improvement (QAPI) meeting, and the Quality Assessment and Assurance (QAA) Committee will determine the need for additional audits/interventions for ongoing compliance.
K0353 · Aventura at Pembrooke (PA)
Surveyed 07/08/2026 · Spot-checks: weekly for 4 weeks
353: Sprinkler System - Maintenance and Testing: The facility failed to provide documentation verifying quarterly inspections of mechanical waterflow devices had occurred within the previous…
View Full Plan Text
K0353 Correction Date: 08/05/2026
353: Sprinkler System - Maintenance and Testing: The facility failed to provide documentation verifying quarterly inspections of mechanical waterflow devices had occurred within the previous twelve months, and to maintain the automatic sprinkler system in a continuously reliable operating condition, which serves the entire component. No residents were affected. All residents have the potential to be affected. Certified Sprinkler Vendor completed inspection of the water flow devices and supervisor switches on 10JUL2026. Facility wide visual audit of the facilities mechanical waterflow devices was completed by the Maintenance Director and documented on 17JUL2026 per regulatory requirements. The open area in the suspended ceiling of the salon was repaired by the Maintenance Director/designee on 21JUL2026. On 21JUL2026, NHA educated the Maintenance Director on the importance of maintaining documentation per regulatory requirements. The Maintenance Director/Designee will conduct compliance audits weekly x4 weeks then monthly x2 months, to ensure that documentation for mechanical waterflow devices meet the regulatory requirement. The Maintenance Director/Designee will conduct compliance audits weekly x4 weeks to ensure that there are no open areas in walls, then monthly x2 months and quarterly x 4 quarters. NHA/Designee will audit quarterly Life Safety Binder with Maintenance Director to ensure compliance. Results will be submitted to quarterly Quality Assurance Performance Improvement Committee for review and recommendations.
K0353 · Germantown Home (PA)
Surveyed 07/01/2026 · Spot-checks: daily for 3 months
1) In review of the annual inspection report it was identified the diesel fire pump/sprinkler system met the 100% but did not meet maximum capacity of 150%. Impact Fire was contacted and…
View Full Plan Text
K0353 Correction Date: 08/25/2026
1) In review of the annual inspection report it was identified the diesel fire pump/sprinkler system met the 100% but did not meet maximum capacity of 150%. Impact Fire was contacted and facility was referred to the Philadelphia Water Department (PWD). Impact identified it was not on the part of the facility but external factors with PWD. PWD was called and PWD has identified they have an obstructive valve box identified during inspection on July 2nd under the street and have an open ticket. Facility has informed PWD emergency department this has affected the diesel fire pump/sprinkler system and is not allowing the sprinkler system to meet the maximum of 150% capacity in case of a fire thus not meeting Life Safety NFPA standard. Facility has also informed PWD this is a nursing home with the capacity to house 180 seniors and employs 250+ staff. Systemic Changes: All Fire Sprinkler vendor reports that are due quarterly, annually, and monthly will be reviewed with the administrator to ensure recommendations are addressed timely to meet compliance and provide support for 3 months. The Maintenance Director will review monthly inspections and findings in QAPI monthly for 3 months. 2) Boxes stored with in 18 inches were removed immediately below 18 inches in central supply room. - Education will be provided Central Supply coordinator on stocking guidelines within NFPA?18 inches and safety. Systematic change: will include marking the walls to show representation of 18 inches stock level. Maintenance Director/Designee will monitor weekly for 3 months and report in QAPI monthly for three months. 3) The two gauges dated 2017 on the sprinkler riser, Ground Floor Sprinkler Riser / Fire Pump Room were identified. Sprinkler company have been scheduled to inspect the sprinkler riser/fire pump and provide updated tags after inspection. Systematic Change: Maintenance Director and Maintenance team will add the annual schedule to TELS maintenance system calendar for reminder to have annual sprinkler riser/fire pump inspection completed. Maintenance Director /Designee will report in QAPI the completion of sprinkler riser/fire pump inspection for two months. 4) Observed sprinkler cap covered with a medicine cup and it was removed immediately at time of survey. No residents or staff were affected. Systematic Changes: Maintenance Director/Designee will perform daily checks in back dining room/lounge area second floor daily for 1 month and weekly for 2 months to ensure sprinkler heads are not covered. Staff will be educated to report medicine cups obstructing sprinklers immediately to maintenance or supervisors. - Maintenance Director will report findings in QAPI for three months.
K0353 · Chapel Manor (PA)
Surveyed 06/30/2026 · Spot-checks: weekly for 4 weeks
1. A sprinkler gauge inspection has been scheduled. 2. NHA will educate the Maintenance department to ensure the automatic sprinkler system components are properly inspected and maintained. 3.…
View Full Plan Text
K0353 Correction Date: 08/12/2026
1.A sprinkler gauge inspection has been scheduled. 2.NHA will educate the Maintenance department to ensure the automatic sprinkler system components are properly inspected and maintained. 3.NHA/designee will complete random weekly audits x 3 weeks and monthly x 1 month to ensure that the sprinkler system components are maintained and inspected. 4.Maintenance Director will report audit findings to the QAPI Committee x 3 months for review.
K0353 · Monticello House (PA)
Surveyed 06/24/2026 · Spot-checks: weekly for 4 weeks
The 5th floor elevator lobby sprinkler head will have an escutcheon installed. As a part of the Maintenance Supervisor's quarterly inspection protocol, the Facility Operations Department will…
View Full Plan Text
K0353 Correction Date: 07/20/2026
The 5th floor elevator lobby sprinkler head will have an escutcheon installed. As a part of the Maintenance Supervisor's quarterly inspection protocol, the Facility Operations Department will inspect all sprinkler heads to ensure escutcheons are in place where applicable. Those found without escutcheons in place will be addressed accordingly. Director of Facility Operations and/or delegate will report areas of concerns, findings, and corrections to the Quality Assurance Performance Improvement (QAPI) Committee for the next two quarters. Disclaimer: Preparation and/or execution of this entire Plan of Correction does not constitute admission or agreement by the Provider of the truth of the facts alleged or conclusion set forth in this Statement of Deficiencies. The entire Plan of Correction is prepared and/or executed solely because it is required by the provisions of Federal and State laws.
K0353 · Phoebe Allentown Health Care Center (PA)
Surveyed 06/23/2026 · Spot-checks: monthly for 4 weeks
1. Penetrations were sealed on 06/23/26. Educate staff on the correct procedures and usage of fire stopping to be completed by 08/03/2026. Perform monthly rounds for a quarter to make sure we…
View Full Plan Text
K0353 Correction Date: 08/03/2026
1. Penetrations were sealed on 06/23/26. Educate staff on the correct procedures and usage of fire stopping to be completed by 08/03/2026. Perform monthly rounds for a quarter to make sure we are compliant and report out on our findings in our monthly QAPI meeting.
2. Scheduled all sprinkler and suppression servicing and inspections with Comunale Fire systems on 4/17/26, PO#33210. We will audit this on a quarterly basis for the next quarter to make sure we are compliant with the inspections needed.
K0353 · Yorkview Nursing and Rehabilitation (PA)
Surveyed 06/09/2026 · Spot-checks: weekly for 4 weeks
Development and/or execution of this plan of correction does not constitute admission or agreement by this provider of the truth in the statement of deficiency. This plan of correction is…
View Full Plan Text
K0353 Correction Date: 07/24/2026
Development and/or execution of this plan of correction does not constitute admission or agreement by this provider of the truth in the statement of deficiency. This plan of correction is prepared and/or executed by provision of Federal or State Law.
1. Various wires identified in F West Wing and F East wing above the ceiling that were supported by the sprinkler piping system were removed.
2. Additional sprinkler heads in building 2 will be observed to ensure they are free from extraneous weight.
3. Maintenance Department will be educated by NHA to audit the area for items laying on the sprinkler pipes after above ceiling work is completed.
4. The Maintenance Director/designee will audit sprinkler heads in the facility to ensure they are free from obstruction weekly for 4 weeks. Trends will be reported to the QAPI committee for further action planning.
5. Date of compliance: 7/24/26