2025–26 PA Citations: 37
✓
Common Audit Schedule: weekly for 4 weeks
✓
Checklist Source: CMS Life Safety Code
In Pennsylvania, state surveyors recorded 37 citations for K0541 (K-541: Services Deficiencies) across recent 2025-2026 skilled nursing facility inspections. Recent citations in Pennsylvania were most active in Montgomery, Philadelphia, Bucks counties. To clear an onsite revisit without repeat deficiencies, Maintenance Director or designee teams typically pair immediate resident or building remediation with signed staff shift huddles and weekly for 4 weeks audit logs reviewed by the monthly QAPI committee.
What Surveyors Check Onsite
- Are physical building zones cited under K0541 inspected on every shift and logged in the maintenance binder?
- Have maintenance staff verified and documented immediate physical repair with dated work orders?
- Are weekly audit logs signed by the Maintenance Director and reviewed at monthly QAPI meetings?
3-Question Hallway Spot-Quiz
Review with nurses & CNAs during your 5-minute shift huddle:
- If you spot an equipment or corridor safety issue related to K-541, how do you report an urgent maintenance order?
- Where are weekly Life Safety inspection logs kept when state surveyors arrive?
- What safety check happens on your unit before ending your shift?
Approved State Plan Examples for K0541
Graduate Post Acute (PA)
Spot-checks: monthly × 4 weeks
✓ Passed Re-Inspection
1. A self-closing device was installed on the first-floor linen chute door. The door was adjusted and tested to ensure it fully self-closed and positively latched. 2. The Maintenance…
View Full Plan Text (08/11/2026)
K0541 Correction Date: 09/23/2026
1. A self-closing device was installed on the first-floor linen chute door. The door was adjusted and tested to ensure it fully self-closed and positively latched.
2. The Maintenance Director/designee inspected all linen and laundry chute doors throughout the facility. Identified deficiencies were immediately corrected.
3. Maintenance staff were educated on inspecting, testing, and maintaining linen and laundry chute doors, including self-closing and positive-latching functionality.
4. The Maintenance Director/designee will audit all linen and laundry chute doors monthly for three months. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
Centennial Healthcare and Rehabilitation Center (PA)
Spot-checks: monthly × 4 weeks
✓ Passed Re-Inspection
The trash chute door on the third floor positively latches. Trash chute doors in the facility have the potential to be effected. Maintenance will be educated on maintaining Trash Chute doors…
View Full Plan Text (07/15/2026)
K0541 Correction Date: 09/01/2026
The trash chute door on the third floor positively latches. Trash chute doors in the facility have the potential to be effected. Maintenance will be educated on maintaining Trash Chute doors Random audits will be conducted by the Maintenance or designee to ensure trash Chutes are maintained Monthly x2 with reports to QAPI
Germantown Home (PA)
Spot-checks: daily × 4 weeks
✓ Passed Re-Inspection
During annual Life Safety Survey, the ground floor linen chute access room door did not positively latch. All linen/trash room doors were checked and all others positively latched during…
View Full Plan Text (07/01/2026)
K0541 Correction Date: 08/25/2026
During annual Life Safety Survey, the ground floor linen chute access room door did not positively latch. All linen/trash room doors were checked and all others positively latched during survey. Ground floor linen room access door has been scheduled to be repaired to positively latch. Daily inspections of the ground floor linen access door will be added to the preventive maintenance inspections for one month. Weekly x 3 months to ensure continued compliance. Maintenance Director will report in QAPI monthly inspection findings for three months.