2025–26 PA Citations: 100
✓
Common Audit Schedule: weekly for 4 weeks
✓
Checklist Source: CMS Life Safety Code
In Pennsylvania, state surveyors recorded 100 citations for K0521 (K-521: Services Deficiencies) across recent 2025-2026 skilled nursing facility inspections. Recent citations in Pennsylvania were most active in Montgomery, Philadelphia, Allegheny counties. To clear an onsite revisit without repeat deficiencies, Maintenance Director or designee teams typically pair immediate resident or building remediation with signed staff shift huddles and weekly for 4 weeks audit logs reviewed by the monthly QAPI committee.
What Surveyors Check Onsite
- Are physical building zones cited under K0521 inspected on every shift and logged in the maintenance binder?
- Have maintenance staff verified and documented immediate physical repair with dated work orders?
- Are weekly audit logs signed by the Maintenance Director and reviewed at monthly QAPI meetings?
3-Question Hallway Spot-Quiz
Review with nurses & CNAs during your 5-minute shift huddle:
- If you spot an equipment or corridor safety issue related to K-521, how do you report an urgent maintenance order?
- Where are weekly Life Safety inspection logs kept when state surveyors arrive?
- What safety check happens on your unit before ending your shift?
Approved State Plan Examples for K0521
Hilltop Heights Health & Rehab Center (PA)
Spot-checks: weekly × 4 weeks
✓ Passed Re-Inspection
Portable air conditioning units immediately taken down and removed on date of survey. No portable units remained in the facility and they were no longer needed due to facility's internal air…
View Full Plan Text (09/09/2026)
K0521 Correction Date: 09/21/2026
Portable air conditioning units immediately taken down and removed on date of survey. No portable units remained in the facility and they were no longer needed due to facility's internal air conditioning system functioning at that point. Maintenance director educated by nursing home administrator/designee that air conditioners cannot be vented into the corridor space above the ceiling.
Graduate Post Acute (PA)
Spot-checks: monthly × 4 weeks
✓ Passed Re-Inspection
1. The portable air-conditioning unit that was improperly vented above the suspended ceiling in the basement laundry was removed from service. 2. The Maintenance Director/designee inspected…
View Full Plan Text (08/11/2026)
K0521 Correction Date: 09/23/2026
1. The portable air-conditioning unit that was improperly vented above the suspended ceiling in the basement laundry was removed from service.
2. The Maintenance Director/designee inspected the facility for other portable HVAC units that were improperly installed or vented. Identified concerns were corrected.
3. Maintenance staff were educated on properly installing and venting portable HVAC equipment according to manufacturer instructions and applicable Life Safety requirements.
4. The Maintenance Director/designee will audit the facility for improperly installed or vented portable HVAC equipment monthly for three months. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendation.
Delaware Valley Veterans' Home (PA)
Spot-checks: weekly × 4 weeks
✓ Passed Re-Inspection
The approved regulatory guidelines for having dampers inspected every 4 years will be followed. The vendor, Berkshire Systems, Inc., was scheduled on 07/15/2026 to come out to the facility on…
View Full Plan Text (07/13/2026)
K0521 Correction Date: 09/11/2026
The approved regulatory guidelines for having dampers inspected every 4 years will be followed. The vendor, Berkshire Systems, Inc., was scheduled on 07/15/2026 to come out to the facility on Thursday, 07/23/2026, to replace the old damper and install a new damper and duct access door. This was completed and an access panel will also be added to the ceiling to make the damper accessible. Documentation of the noted actions will be obtained and maintained by the Facility Grounds Director in the Life Safety binder following completion of the installation. The Facility Grounds Director and Maintenance Supervisor completed refresher training on NFPA 80 and NFPA 90A damper requirements, with focus on maintaining accessible access panels. All future damper inspection reports will be reviewed within 72 hours of receipt, and any deficient practice will be assigned a due date, contractor confirmation and required documentation follow up. The Facility Grounds Director will review damper status quarterly until all repairs are complete, then semi-annually thereafter. Report from the Safety Committee chairs will be reviewed at the Quality Assurance Performance Improvement meeting and the Quality Assessment and Assurance (QAA)Committee will determine the need for additional audits/interventions for ongoing compliance.