Pennsylvania K-351 Plan of Correction Guide

K0351 · Smoke Deficiencies

Build K-351 Plan & Binder →
✓ 2025–26 PA Citations: 22
✓ Common Audit Schedule: weekly for 4 weeks
✓ Checklist Source: CMS Life Safety Code

In Pennsylvania, state surveyors recorded 22 citations for K0351 (K-351: Smoke Deficiencies) across recent 2025-2026 skilled nursing facility inspections. Recent citations in Pennsylvania were most active in Montgomery, Delaware, Centre counties. To clear an onsite revisit without repeat deficiencies, Maintenance Director or designee teams typically pair immediate resident or building remediation with signed staff shift huddles and weekly for 4 weeks audit logs reviewed by the monthly QAPI committee.

Active PA Counties: Montgomery County (4) → Delaware County (2) → Centre County (2) → York County (1) → Washington County (1) →

What Surveyors Check Onsite

  • Are physical building zones cited under K0351 inspected on every shift and logged in the maintenance binder?
  • Have maintenance staff verified and documented immediate physical repair with dated work orders?
  • Are weekly audit logs signed by the Maintenance Director and reviewed at monthly QAPI meetings?

3-Question Hallway Spot-Quiz

Review with nurses & CNAs during your 5-minute shift huddle:

  1. If you spot an equipment or corridor safety issue related to K-351, how do you report an urgent maintenance order?
  2. Where are weekly Life Safety inspection logs kept when state surveyors arrive?
  3. What safety check happens on your unit before ending your shift?

Approved State Plan Examples for K0351

Margaret E. Moul Home (PA)
Spot-checks: weekly × 4 weeks ✓ Passed Re-Inspection

1. The 2 upright sprinkler heads located in the laundry room dryer change have been relocated down by Johnson Controls, to ensure a minimum of 1 inch from the overhead. 2. All upright…

View Full Plan Text (08/24/2026)
K0351 Correction Date: 09/30/2026 1. The 2 upright sprinkler heads located in the laundry room dryer change have been relocated down by Johnson Controls, to ensure a minimum of 1 inch from the overhead. 2. All upright sprinkler heads will be inspected to ensure they were installed with a minimum of 1 inch clearance from the overhead. 3. Director of Environmental Services or designee will audit upright sprinkler heads quarterly for 3 quarters to ensure compliance. Findings will be reported to the Quality Assessment and Assurance Committee for recommendations and need for further audits.
Manatawny Center for Rehabilitation and Nursing (PA)
Spot-checks: monthly × 4 weeks ✓ Passed Re-Inspection

1. The Maintenance Director will engage a qualified fire sprinkler contractor (Johnson Controls) to evaluate and extend sprinkler coverage into the basement Electrical room, Transfer Switch…

View Full Plan Text (03/04/2026)
K0351 Correction Date: 05/03/2026 1.The Maintenance Director will engage a qualified fire sprinkler contractor (Johnson Controls) to evaluate and extend sprinkler coverage into the basement Electrical room, Transfer Switch Control Room to ensure complete sprinkler protection of all useable areas. The work will be scheduled and completed in accordance with NFPA 13 requirements. Plan review contacted for corrective action requirements. The vendor will provide plan drawings and hydraulic calculations for submission to plan review for approval. 2.The Maintenance Director and relevant staff members will be educated on NFPA 101 Sprinkler System - Installation requirements, with specific focus on the requirement for complete sprinkler coverage of all useable areas. 3.The Maintenance Director/designee will conduct a thorough inspection of all sprinklered areas within the facility to verify complete coverage. Any additional areas of concern will be addressed immediately. Monthly audits will be conducted to ensure no new areas of incomplete coverage develop. 4.Findings will be reviewed at the Quality Assurance Performance Improvement meeting.
Rose View Rehab and Care Center (PA)
Spot-checks: weekly × 4 weeks ✓ Passed Re-Inspection

1. Bid will be approved to install sprinkler to the Therapy Department Closet. 2. Other closets will be checked to ensure proper sprinkler protection. 3. Maintenance will be re-educated on…

View Full Plan Text (12/10/2025)
K0351 Correction Date: 01/20/2026 1. Bid will be approved to install sprinkler to the Therapy Department Closet. 2. Other closets will be checked to ensure proper sprinkler protection. 3. Maintenance will be re-educated on ensuring that all Therapy Department Closets will have sprinkler protection. 4. Maintenance Director/ designee will conduct random audits to verify that department closets will be checked for proper sprinkler protection weekly for 4 weeks and then monthly for 2 months thereafter. Audit results will be presented at QAPI meeting for review and recommendations.