Nevada K-345 Plan of Correction Guide
K0345 · Fire Alarm System Testing, Inspection, and Out-of-Service Fire Watch
Build K-345 Plan & Binder →
✓
2025–26 NV Citations: 32
✓
Common Audit Schedule: weekly for 4 weeks
✓
Checklist Source: LSC-K0345
In Nevada, state surveyors recorded 32 citations for K0345 (K-345: Fire Alarm System Testing, Inspection, and Out-of-Service Fire Watch) across recent 2025-2026 skilled nursing facility inspections. Recent citations in Nevada were most active in Clark, Washoe, White Pine counties. To clear an onsite revisit without repeat deficiencies, Maintenance Director or designee teams typically pair immediate resident or building remediation with signed staff shift huddles and weekly for 4 weeks audit logs reviewed by the monthly QAPI committee.
What Surveyors Check Onsite
- Are semi-annual smoke detector sensitivity checks and annual fire alarm vendor inspection reports complete in the binder?
- Is the main fire alarm panel clear of unaddressed trouble signals during maintenance shift rounds?
- Do staff know the written Fire Watch log procedure if the fire alarm system goes offline for more than 4 hours?
3-Question Hallway Spot-Quiz
Review with nurses & CNAs during your 5-minute shift huddle:
- If you hear a yellow trouble beep on the main fire alarm panel at the nurses' station, who do you call right away?
- Where is our facility Fire Watch clipboard kept if the alarm system is temporarily offline for maintenance?
- Where does the maintenance director file quarterly and annual fire alarm testing certificates?
Approved State Plan Examples for K0345
Asbury Health Center (PA)
Spot-checks: weekly × 4 weeks
✓ Passed Re-Inspection
Fire alarm system will be repaired before POC completion date. NHA or designee will educate maintenance director on fire system requirements and routine inspections. Maintenance director or…
View Full Plan Text (08/10/2026)
K0345 Correction Date: 09/16/2026
Fire alarm system will be repaired before POC completion date. NHA or designee will educate maintenance director on fire system requirements and routine inspections. Maintenance director or designee will audit the fire alarm system and submit repair orders as needed weekly x 4 weeks, then monthly x 2 months. Results will be reviewed and adjusted at QAPI as needed.
Markley Rehabilitation and Healthcare Center (PA)
Spot-checks: weekly × 2 months
✓ Passed Re-Inspection
1. The facility fire alarm service provider is scheduled to troubleshoot and clear all trouble signals on the fire panel. Acknowledgement buttons replaced annunciators on the 2nd and 3rd…
View Full Plan Text (07/23/2026)
K0345 Correction Date: 09/21/2026
1. The facility fire alarm service provider is scheduled to troubleshoot and clear all trouble signals on the fire panel. Acknowledgement buttons replaced annunciators on the 2nd and 3rd floors.
2. Maintenance staff checked the fire panel for additional issues and found that the fire panel was operating correctly except for the trouble signals that were indicated.
3. NHA/Maintenance Director/Designee will in-service managers on duty, receptionists, and nursing supervisors on the importance of not having trouble signals on the fire panels and directions to use when one is identified.
4. The Maintenance Director/Designee will check the panel 3x a week for four weeks, then once a week for 2 months thereafter to make sure the panel is functioning appropriately. Audit findings will be addressed and submitted to the Quality Assurance Performance Improvement Committee for further review and recommendations needed. TLW: Markley Rehabilitation and healthcare center would like to request a Time Limited Waiver (TLW) For deficiency K0345 Fire Alarm Testing and Maintenance as the facility failed to correct the deficiencies on the fire alarm system for troubles on our panel this was identified on the recent Department of Health Life Safety Survey completed on July 23,
2026. Markley Rehabilitation and Healthcare Center called our provider to clear troubles on panel. they need to order new smoke heads and have Siemens reprogram panel which will take several weeks to obtain. The vendor has a projected due date of September 15, 2026 for parts to arrive. Once this is completed and cleared, we will immediately notify the division of life safety and the local field office. Because of vendor limitations, Markley rehabilitation and Healthcare Center is requesting a TLW until September 30, 2026, we will gladly notify you if the project is completed sooner than the date requested. Thank you for your time and consideration in this matter. If you have any questions, please contact Dean McGroaty at 856-912-6141 or at dmcgroatry@Markleyrehab.com