2025–26 IN Citations: 124
✓
Common Audit Schedule: weekly for 4 weeks
✓
Checklist Source: LSC-K0321
In Indiana, state surveyors recorded 124 citations for K0321 (K-321: Hazardous Areas - Enclosure and Self-Closing Smoke Doors) across recent 2025-2026 skilled nursing facility inspections. Recent citations in Indiana were most active in Marion, Madison, Hamilton counties. To clear an onsite revisit without repeat deficiencies, Maintenance Director or designee teams typically pair immediate resident or building remediation with signed staff shift huddles and weekly for 4 weeks audit logs reviewed by the monthly QAPI committee.
What Surveyors Check Onsite
- Do all soiled utility, laundry, storage (>50 sq ft), and mechanical room doors self-close and positive-latch completely?
- Are wooden wedges, kick-down stops, or propped linen hampers completely absent from fire and smoke doors?
- Are penetrations around pipes and data cables in smoke/fire walls sealed with listed firestop material?
3-Question Hallway Spot-Quiz
Review with nurses & CNAs during your 5-minute shift huddle:
- Why can staff never use a wedge or linen cart to prop open a soiled utility or storage room door, even for two minutes?
- If you notice a hallway or storage door failing to latch shut on its own, how do you submit an urgent maintenance work order?
- When the fire alarm sounds, what should happen automatically to corridor smoke-barrier doors?
Approved State Plan Examples for K0321
Brickyard Healthcare - Twelfth Street Care Center (IN)
Spot-checks: weekly × 4 weeks
✓ Passed Re-Inspection
A door closer was added to the IT server/activity storage room. resident room was cleared of all storage. All residents in adjacent areas have potential to be affected by the alleged deficient…
View Full Plan Text (12/09/2025)
K0321
Completion Date: 02/03/2026
A door closer was added to the IT server/activity storage room. resident room was cleared of all storage. All residents in adjacent areas have potential to be affected by the alleged deficient practice. A monthly task was added to TELS to Ensure all areas used for storage of hazardous materials are equipped with a door closer and are self-latching. Ensure all areas over 50 square feet and are used for storage of flammable materials such as boxes or other flammable materials are equipped with a door closer and self-latch into the frame. Maintenance will report to QAPI no less than quarterly in perpetuity regarding life safety issues. kitchen hood pull station and using the type K only after to extinguish any residual fire if necessary in case of a fire under the kitchen hood. The dietary manager then trained all kitchen staff on manually activating the kitchen hood pull station and using the type K only after to extinguish any residual fire if necessary in case of a fire under the kitchen hood. This alleged deficient practice could affect all residents. The Kitchen manager will educate staff weekly for a month and then continuing monthly thereafter and document as a part of the kitchen staff training to ensure the alleged deficient practice does not recur. The kitchen manager and maintenance will report to QAPI no less than quarterly regarding this life safety issue.
Harrison Terrace (IN)
Spot-checks: weekly × 4 weeks
Approved Filing
Hazardous Areas - Enclosure What corrective action will be accomplished for those residents found to have been affected by the deficient practice? Mechanical room by the kitchen. How will you…
View Full Plan Text (10/14/2026)
K0321 - Hazardous Areas - Enclosure What corrective action will be accomplished for those residents found to have been affected by the deficient practice? Mechanical room by the kitchen. How will you identify other residents having the potential to be affected by the same deficient practice and what corrective action will be taken? - All residents have the potential to be affected by the alleged deficient practice. - Maintenance Director/Designee inspected all hazardous areas separated by smoke resistant partitions and doors. What measures will be put into place or what systemic changes will be made to ensure that the deficient practice does not recur? - Maintenance Director/Designee was educated on appropriate wall coverings for the How the corrective action (s) will be monitored to ensure the deficient practice will not recur, i.e. what quality assurance program will be put into place? - To ensure compliance Maintenance Director/Designee will have an audit tool that is to be completed annually. - The results of these audit tools will be reviewed by the QAPI committee overseen by the ED. Date of Compliance 11/02/2026
Majestic Care of North Vernon (IN)
Spot-checks: weekly × 4 weeks
Approved Filing
Self-closing devices were immediately installed on the C Hall Electronics Room door and the D Hall Chemical Storage Room door. Both How other residents having the potential to be affected by…
View Full Plan Text (08/11/2026)
K0321
Completion Date: 08/28/2026
POC-K0321 What corrective action(s) will be accomplished for those residents found to have been affected by the deficient practice? Self-closing devices were immediately installed on the C Hall Electronics Room door and the D Hall Chemical Storage Room door. Both How other residents having the potential to be affected by the same deficient practice will be identified and what corrective actions(s) will be taken? C and D hall had the potential to be affected by the deficient practice. A facility-wide inspection of hazardous area doors was conducted to identify any additional rooms requiring self-closing devices. Any deficiencies identified were immediately corrected. What measures will be put into place and what systematic changes will be made to ensure that the deficient practice does not recur? The Maintenance Director was educated regarding Life Safety Code requirements for hazardous area doors, including self-closing and positive latching requirements. Maintenance director will audit the deficient practice will not recur, i.e., what quality assurance program will be put into place? The Executive Director or designee will conduct weekly audits of hazardous area doors for six months to ensure self-closing devices are present, functional, and doors positively latch when closed. Any concerns identified will be immediately corrected. Results will be reported through the QAPI process. By what date the systematic changes for each deficiency will be completed? 8/28/2026